China Low Temperature Chiller as Part of Disinfecting and Antibacterial Cleaning, Find details about China Chiller, 63kw Low Temperature Chiller from Low Temperature Chiller as Part of Disinfecting and Antibacterial Cleaning
Model No. | RHT -040WL | RHT -050WL | RHT -060WL | RHT -070WL | ||||||
Power Supply | 3PH-380V-50HZ | |||||||||
Cryogenic Temperature | -8ºC | Kcal/h | 54180 | 69660 | 77400 | 92020 | ||||
KW | 63 | 81 | 90 | 107 | ||||||
-10ºC | Kcal/h | 49020 | 63640 | 70520 | 83420 | |||||
KW | 57 | 74 | 82 | 97 | ||||||
Air Conditioner's Refrigeration Capacity | Kcal/h | 113520 | 141900 | 165980 | 191780 | |||||
KW | 132 | 165 | 193 | 223 | ||||||
Power Consumption | KW | 27.9/27.5/31 | 34.9/34.4/38 | 39.4/38.9/43 | 46.2/45.5/51 | |||||
Operating Current | A | 50.0/49.5/54 | 64.9/61.3/66 | 69.3/68.6/75 | 80.1/79.2/87 | |||||
Starting Current | A | 218D/411DD | 269D/508DD | 290D/485DD | 350D/585DD | |||||
Capacity Control | % | 100-75-50-25-0 | ||||||||
Compressor | Type | Semi-hermetic Screw Type | ||||||||
Qty | 1 | |||||||||
Starting | Fractional Winding | |||||||||
Oil Heater (W) | 200 | |||||||||
Freezing Oil | Type | B320SH | ||||||||
Vol (L) | 9 | 9 | 15 | 15 | ||||||
Refrigerant | Type | Standard R-22 / Eco-friendly R134a or R407c | ||||||||
Vol (Kg) | 21 | 26 | 30 | 35 | ||||||
Control | Thermostatic Expansion Valve | |||||||||
Evaporator | Type | Shell and Tube Type High Efficiency Heat Exchange | ||||||||
Qty | 1 | |||||||||
Freezing Fluid Flow (m3/h) Based on Cryogenic Tem. -8ºC | 9 | 12 | 13 | 16 | ||||||
Freezing Fluid Flow (m3/h) Based on Cryogenic Tem. -10ºC | 9 | 11 | 12 | 15 | ||||||
Freezing Water Flow (m3/h) | 23 | 28 | 33 | 38 | ||||||
Head Loss (m3/h) | 54 | 54 | 57 | 59 | ||||||
Pipe Dia. (m3/h) | 2-1/2" | 2-1/2" | 2-1/2" | 2-1/2" | ||||||
Condenser | Type | Shell and Tube Type High Efficiency Heat Exchange | ||||||||
Qty | 1 | |||||||||
Cooling Water Flow (m3/h) Based on Cryogenic Tem. -8ºC | 16 | 20 | 22 | 26 | ||||||
Freezing Water Flow (m3/h) Based on Cryogenic Tem. -10ºC | 15 | 19 | 21 | 25 | ||||||
Freezing Water Flow (m3/h) | 28 | 35 | 41 | 47 | ||||||
Head Loss (m3/h) | 51 | 51 | 54 | 54 | ||||||
Pipe Dia. (m3/h) | 2" | 2" | 2" | 2" | ||||||
Protection Devices | built in high pressure protector, low pressure protector, overload protector, over-voltage or under-voltage, anti-phase and phase sequence protector, frost-preventive switch | |||||||||
Size | L(mm) | 2175 | 2195 | 2245 | 2860 | |||||
W(mm) | 935 | 935 | 935 | 1015 | ||||||
H(mm) | 1430 | 1500 | 1655 | 1710 | ||||||
Unit Weight | Kg | 1020 | 1060 | 1270 | 1370 | |||||
Operation Weight | Kg | 1120 | 1180 | 1420 | 1550 | |||||
Operation Noise | Db (A) | 72 | 72 | 76 | 76 |
Applications
1. Medical Processing - supply reliable cooling for certain medical fabrication processes and storage to guarantee safety and effectiveness.
2. Food Processing - Supply low-temperature cooling day in and day out for food processing companies to guarantee the safety and consistent quality for frozen foods.
3. Product and Material Testing - Supply -40°F temperatures to make many types of clothing, materials and equipment could be tested.
Package & Shipping
Use standard export plywood case with forklift truck feet, easy to load and unload
5-7 days to finish the production after receiving the deposit
Shipping by LCL or FCL
After-sales service