MODEL | CAPACITY(M3/h) | FAN | WATER SPRAYING PUMP | INLET/OUTLET DN(MM) | WEIGHT | DIMENSION | |||||
QTY&POWER (KW) | AIR VOLUME PER SET (M3/h) | QTY | WATER VOLUME PER SET (M3/h) | DN(mm) | SHIPPING(KG) | OPERATIONG(KG) | LENGTH(MM) | WIDTH(MM) | HEIGHT(MM) | ||
ZHX-320 | 320 | 1*3 | 35000 | 1*1.1 | 36 | DN80 | 2390 | 3790 | 1925 | 2380 | 4220 |
ZHX-430 | 430 | 1*4 | 45000 | 1*1.1 | 45 | DN100 | 2510 | 3910 | 1925 | 2380 | 4220 |
ZHX-525 | 525 | 1*5.5 | 65000 | 1*1.1 | 45 | DN100 | 2760 | 4340 | 1925 | 2580 | 4220 |
ZHX-595 | 595 | 1*5.5 | 75000 | 1*1.5 | 65 | DN100 | 3290 | 5140 | 1925 | 2900 | 4220 |
ZHX-700 | 700 | 1*7.5 | 87000 | 1*1.5 | 65 | DN100 | 3680 | 5530 | 1925 | 2900 | 4965 |
ZHX-800 | 800 | 2*4 | 45000 | 1*2.2 | 84 | DN100 | 4230 | 7650 | 3770 | 2200 | 4220 |
ZHX-870 | 870 | 2*4 | 45000 | 1*2.2 | 84 | DN125 | 4510 | 7930 | 3770 | 2200 | 4720 |
ZHX-980 | 980 | 2*4 | 45000 | 1*2.2 | 84 | DN125 | 4620 | 8040 | 3770 | 2200 | 4965 |
ZHX-1100 | 1100 | 3*3 | 40000 | 1*3 | 120 | DN125 | 6170 | 10170 | 4240 | 2200 | 4720 |
ZHX-1250 | 1250 | 3*4 | 45000 | 1*3 | 120 | 2-DN100 | 6510 | 10510 | 4240 | 2200 | 4965 |
ZHX-1380 | 1380 | 4*3 | 45000 | 1*3 | 120 | 2-DN100 | 7100 | 11950 | 5610 | 2200 | 4220 |
ZHX-1520 | 1520 | 4*3 | 40000 | 1*3 | 120 | 2-DN100 | 7310 | 12160 | 5610 | 2200 | 4730 |
ZHX-1680 | 1680 | 4*4 | 45000 | 1*3 | 120 | 2-DN100 | 7590 | 12440 | 5610 | 2200 | 4965 |
ZHX-1840 | 1840 | 4*4 | 45000 | 1*4 | 170 | 2-DN125 | 8920 | 15580 | 7450 | 2200 | 4220 |
ZHX-2010 | 2010 | 4*4 | 45000 | 1*5.5 | 230 | 2-DN125 | 9330 | 15990 | 7450 | 2200 | 4720 |
ZHX-2245 | 2245 | 4*4 | 45000 | 1*5.5 | 230 | 2-DN125 | 9550 | 16210 | 7450 | 2200 | 4965 |
ZHX-2450 | 2450 | 5*4 | 45000 | 1*5.5 | 230 | 4-DN100 | 11650 | 19090 | 9300 | 2200 | 4720 |
ZHX-2600 | 2680 | 5*4 | 45000 | 1*5.5 | 230 | 4-DN100 | 12350 | 19790 | 9300 | 2200 | 4965 |
ZHX-2820 | 2820 | 6*4 | 45000 | 1*5.5 | 230 | 4-DN100 | 12490 | 19930 | 9300 | 2200 | 4965 |
MODEL | CAPACITY(M3/h) | FAN | WATER SPRAYING PUMP | INLET/OUTLET DN(MM) | DIMENSION | |||||
QTY and Power (KW) | AIR VOLUME PER SET (M3/h) | QTY and Power(KW) | WATER VOLUME PER SET (M3/h) | OPERATIONG(KG) | LENGTH(MM) | WIDTH(MM) | HEIGHT(MM) | |||
ZNX-100 | 100 | 1*1.5 | 18000 | 1*0.55 | 23 | DN50 | 1660 | 1230 | 1150 | 3440 |
ZNX-200 | 200 | 1*2.2 | 30000 | 1*0.75 | 28 | DN50 | 2480 | 1925 | 1150 | 3650 |
ZNX-320 | 320 | 1*3 | 45000 | 1*0.75 | 28 | DN50 | 3620 | 1925 | 1840 | 3840 |
ZNX-430 | 430 | 1*4 | 60000 | 1*1.1 | 45 | DN80 | 3790 | 1925 | 1840 | 4220 |
ZNX-525 | 525 | 1*5.5 | 75000 | 1*1.5 | 65 | DN80 | 4490 | 2470 | 1840 | 4220 |
ZNX-595 | 595 | 1*7.5 | 87000 | 1*1.5 | 65 | DN80 | 4760 | 2470 | 1840 | 4450 |
ZNX-700 | 700 | 1*7.5 | 100000 | 1*2.2 | 84 | DN100 | 6080 | 2790 | 1840 | 4450 |
ZNX-800 | 800 | 2*4 | 65000 | 1*2.2 | 84 | DN100 | 7480 | 3770 | 1840 | 4220 |
ZNX-870 | 870 | 2*4 | 65000 | 1*2.2 | 84 | DN100 | 8010 | 3770 | 1840 | 4450 |
ZNX-980 | 980 | 2*4 | 65000 | 1*2.2 | 84 | DN125 | 8450 | 3770 | 1840 | 4450 |
ZNX-1100 | 1100 | 2*5.5 | 75000 | 1*3 | 120 | DN125 | 9430 | 3770 | 2200 | 4220 |
ZNX-1250 | 1250 | 2*5.5 | 75000 | 1*3 | 120 | 2-DN100 | 10050 | 3770 | 2200 | 4450 |
ZNX-1380 | 1380 | 2*5.5 | 87000 | 1*4 | 170 | 2-DN100 | 11270 | 4846 | 2200 | 4350 |
ZNX-1520 | 1520 | 2*7.5 | 100000 | 1*4 | 170 | 2-DN100 | 11590 | 4846 | 2200 | 4650 |
ZNX-1680 | 1680 | 3*4 | 65000 | 1*4 | 170 | 2-DN100 | 13730 | 5610 | 2200 | 4350 |
ZNX-1840 | 1840 | 3*5.5 | 75000 | 1*4 | 170 | 2-DN125 | 14330 | 5610 | 2200 | 4650 |
ZNX-2010 | 2010 | 3*5.5 | 75000 | 1*4 | 170 | 4-DN80 | 15380 | 6046 | 2200 | 4650 |
ZNX-2245 | 2245 | 3*7.5 | 87000 | 1*5.5 | 230 | 4-DN80 | 17340 | 7230 | 2200 | 4650 |
ZNX-2450 | 2450 | 4*5.5 | 75000 | 2*3 | 120 | 4-DN100 | 18520 | 7450 | 2200 | 4650 |
ZNX-2600 | 2600 | 4*5.5 | 75000 | 2*4 | 170 | 4-DN100 | 20880 | 9030 | 2200 | 4965 |
ZNX-2820 | 2820 | 4*5.5 | 75000 | 2*4 | 170 | 4-DN100 | 21120 | 9030 | 2200 | 4965 |
VII. To offer you quotation promptly, please kindy contact us with answers regarding below :
1. Condensing temperature ?
2. wet bulb temperature ?
3. heat rejection (KW) ?
4.R717 or R22 or 134A ?
If replace others brand Ammonia Evaporative condenser, Just send the brand and model to us first ,we can make the design basic on brand and model information .