Line Ageing Resistance Tensile FRP Silicone Composite Station Post Insulator 66kv

China Line Ageing Resistance Tensile FRP Silicone Composite Station Post Insulator 66kv, Find details about China Composite Insulator, Polymer Insulator from Line Ageing Resistance Tensile FRP Silicone Composite Station Post Insulator 66kv

Model NO.
FXBW-66
Size of Bearing Capacity
70KN
Certification
ISO9001
Color
Gray or Brown
Brand
Wortai or Custom Brand
Name
Dead End Polymer/Composite Insulator
Voltage Class
10kv- 750kv
Specified Mechanical Load
70kn 120kn 300kn
End Fittings
Forged Steel
Core
Electrical Grade Fiberglass Rod (E-Glass + Epoxy)
Standard
ANSI C29.13 IEC61109
Trademark
WORTAI or OEM
Transport Package
12PC in 1 Carton and Then Pallet
Specification
Pallet dimension 110x110x210
Origin
Wenzhou, China
HS Code
8546900000
Model NO.
FXBW-66
Size of Bearing Capacity
70KN
Certification
ISO9001
Color
Gray or Brown
Brand
Wortai or Custom Brand
Name
Dead End Polymer/Composite Insulator
Voltage Class
10kv- 750kv
Specified Mechanical Load
70kn 120kn 300kn
End Fittings
Forged Steel
Core
Electrical Grade Fiberglass Rod (E-Glass + Epoxy)
Standard
ANSI C29.13 IEC61109
Trademark
WORTAI or OEM
Transport Package
12PC in 1 Carton and Then Pallet
Specification
Pallet dimension 110x110x210
Origin
Wenzhou, China
HS Code
8546900000

Line Ageing Resistance Tensile FRP Silicone Composite Station Post Insulator 66kv
Line Ageing Resistance Tensile FRP Silicone Composite Station Post Insulator 66kv
Production Process of Composite Insulators
Line Ageing Resistance Tensile FRP Silicone Composite Station Post Insulator 66kv
Production Description

The housing and sheds of the insulator are made of silicone rubber, one shot injection moulding; this ensures 
   that the interface between the rubber and rod is impenetrable against moisture ingress.

The core rod of insulator is made of a fiberglass that has excellent electrical and mechanical strength.
Leakage current surge suppression due to high level of hydrophobicity of silicone rubber.
Better performance in polluted areas.
Light weight for handling and installation.
The silicone insulators are manufactured and tested according to the standards ANSI C29.13 and IEC 1109


La carcasa y los cobertizos del aislante están hechos de caucho de silicona, moldeado por inyección de un solo disparo; esto asegura que la interfaz entre el caucho y la varilla es impenetrable contra la entrada de humedad.
 La varilla del núcleo del aislante está hecha de fibra de vidrio que tiene una excelente resistencia eléctrica y mecánica.
• Supresión de picos de corriente de fuga debido al alto nivel de hidrofobicidad del caucho de silicona.
 Mejor desempeño en áreas contaminadas.
 Ligero para manipulación e instalación.
 Los aisladores de silicona están fabricados y probados según las normas ANSI C29.13 e IEC 1109


 
Product Paramenters
Ca. NoRated Voltage
(kV)
Rated
Mechanical Tensile Strength
(kN)
Joint Structure MarkSection Length (mm)Insulation
Distance
(mm)
Min. Nominal Creepage Distance
(mm)
Lighting Impulse Withstand Voltage
(peak)
(kV)
1min power frequency wet withstand voltage
(virtual value)
(kV)
FXBW4-10/70107016380±1520048011545
FXBW4-10/1001010016400±1520048011545
FXBW4-15/70157016420±1526055013060
FXBW4-15/1001510016420±1526055013060
FXBW4-24/70247016450±1532071216570
FXBW4-24/1002410016470±1532071216570
FXBW4-35/70357016650±15450101523095
FXBW4-35/1003510016670±15450101523095
FXBW4-66/70667016870±157001900410185
FXBW4-66/1006610016940±157001900410185
FXBW4-110/7011070161180±1510003150550230
FXBW4-110/100110100161240±1510003150550230
FXBW4-220/100220120162240±15195063001000395
FXBW4-220/160220160202240±15195063001000395
FXBW4-330/100330100162990±40260090751425570
FXBW4-330/120330120162990±40260090751425570
FXBW4-330/160330160202990±40260090751425570
FXBW4-330/180330180202990±40260090751425570
FXBW4-330/210330210202990±40260090751425570
FXBW4-500/100500100164450±504000137502250740
FXBW4-500/120500120164450±504000137502250740
FXBW4-500/180500180204450±504000137502250740
FXBW4-500/210500210204450±504000137502250740
FXBW4-500/24050024020/244450±504000137502250740
FXBW4-500/300500300244450±504000137502250740
FXBW-750/160750160206550±5060002200027001125
FXBW-750/210750210206550±5060002200027001125
FXBW-750/300750300246550±5060002200027001125
*We propose to use corona ring at 110kV and above.
*Corona ring is necessary at 220kV and above.
*For Different end fitting types are available on request.
*For Specification or application beyond the range listed here,please contact us for detail.
 
Test and Inspection Equipments
Line Ageing Resistance Tensile FRP Silicone Composite Station Post Insulator 66kv
Packing and Delivery
Line Ageing Resistance Tensile FRP Silicone Composite Station Post Insulator 66kv
Certifications
Line Ageing Resistance Tensile FRP Silicone Composite Station Post Insulator 66kv
WORTAI Album
Line Ageing Resistance Tensile FRP Silicone Composite Station Post Insulator 66kv
Why Choose WORTAI

* More than 20 years manufacturing experience in electric power industry
* Top quality products, ISO9001, ISO14001, KEMA, CNAS certificates
* Custom tailored products, OEM & ODM are welcome
* Challenging prices for giving customers the greatest benefits
* Fast response time, we promise to reply customer's email within 24 hours
* Attractive lead times, plenty of equipments and workers to ensure the delivery on time
* Top skilled technicians
* Flexibility


WORTAI have been sold to over 20 countries and regions, spread all over Asia, Africa, Middle & South America, Middle East and Europe, we also has done OEM service for some world famous brands.Choosing WORTAI means being one step ahead of the general development. We look forward to a closer relationship and mutually beneficial cooperation with any prospective customers in the near future. WORTAI will work with you shoulder-to-shoulder to satisfy your needs.With competitive price, good quality and best service, WORTAI will be your most wise choice. Together we're winners! Let's do it right now!