7.10 Technical Particulars & Guarantees of
110V DC Sub-Station Battery
 
SL. No.DescriptionUnitBPDB's RequirementManufacturers Guaranteed Particulars
1Manufacturers name & country -To be mentionedHEMG/CHINA
2Manufacturers model no.-To be mentionedGNZ100
3Type-Nickel Cadmium Alkaline (enclosed type)Nickel cadmium Alkaline(open type)
4Operating VoltageV DC110110
5Continuous Discharge Current at rate of 10 hour & Final Cell Voltage 1.1 VoltAmp1010A
6Short Time Discharge Current at rate of 2 hour & Final Cell Voltage 1.1 VoltAmp5050A
7Electrolyte type-To be mentionedAlkaline solutions
8Capacity at 10 hour rateAH100100Ah
9Discharge VoltageVolt1.3 Per Cell1.3 Per Cell
10Charging Voltage (Normal) Volt1.6 Per Cell1.6 Per Cell
11Number of cellsNos.92 nos. +5nos. Spare92 nos.+5 nos. Spare
12Voltage per cellV1.21.2V
13Charging Voltage (Maximum)Volt1.75 Per Cell1.75 Per cell
14Normal float charge rateATo be mentioned0.2A-0.3A
15Maximum boost charge rateATo be mentioned30A
16Amp hour efficiency at:
a)     10 hour rate
b)     1 hour rate
 
%
%
 
To be mentioned
To be mentioned
108%
60%
17Size of cellMmTo be mentioned165*105*345mm(ABS or PP container)
18Weight of cell and electrolyteKgTo be mentioned9.3Kg/1.70Kg
19Standard-As per Latest Edition of applicable IEC-60623IEC-60623
20Specific gravity of electrolyte To be mentioned1.20±0.02g/cm3
21Release pressure for valve regulated typeKg/m2To be mentioned0.005×10-4Kg/m2
22Volume of electrolyte per cellMlTo be mentioned1.8L
23Volume of reserve electrolyte per cellMlTo be mentioned0.78L
24No of electrode plates per cellNos.To be mentionedPositive 12 pcs
Negative 11 pcs
25Type of racks
a)     Height
b)     Width
c)     Depth
  
 
To be mentioned
Steel
3360
640
626
26Cell dimension:
a)     Height
b)     Width
c)     Depth
  
To be mentioned
 
165
105
345
27Rack Dimensions
a)     Height
b)     Width
c)     Depth
   
3360
640
626
28Recycling facilities for unserviceable batteries available or notY/NTo be mentionedNo
 
Seal & Signature of the Manufacturer                                Seal & Signature of the Bidder

7.11 Technical Particulars & Guarantees of Sub-Station
110V DC Battery Charger
 
SL. No.DescriptionUnitBPDB's RequirementManufacturers Guaranteed Particulars
1Manufacturers name & country -To be mentionedHEMG
2Manufacturers model no.-To be mentionedGZDT-110V/50A
3Rating-To be mentioned10KVA
4Rated Input voltage rangeV AC415 V ± 10%415V±10%
5Rated FrequencyHz50 Hz (±3%)50Hz±3%
6No of Phase-0303
7Control Shall be mentionedPLC+Touch screen
8Communication module for station automation Shall be provided485
9Rectifier type SiliconSilicon
10Nominal output voltageV DC110110V
11Charging operating control Boost and floating charge, automatic with manual operationmanual operation
12Output currentA DC≥ 4050A
13Continuous current rating 110% of rated current110% of rated current
14Efficiency%≥ 85≥85%
15Voltage regulation%± 0.5≤±0.5%
16Ripple voltagemV≤ 150≤150
17Boost charging voltageV/cell1.6 to 1.75 (programmable)programmble
18Boost charging timeHourProgrammableprogrammable
19Operating temperature°C0 to 500~50
20Humidity%9595%
21Audible noisedB≤ 65≤65
22Facilities for paralleling with another charger Shall be providedOne charger
23Protection against surge voltage Shall be providedSurge arrester
24Protection against reverse polarity  Isolation diodes
25Provision for current limiting  110%
26Provision of constant voltage charge 90V -130V  80-160V
27Provision of showing earth leakage current by analog meter  20mA
28Battery Temperature compensation Shall be incorporated.-2~3mv/ºC(20ºC)
29Alarm annunciator independent of the microprocessor Shall be providedPLC
30Analog meters for voltage and current measurement of input output and battery power   
Shall be mentioned
Dc voltmeter
Dc current meter
31Dimension Shall be mentioned800×600×2260mm
32Output voltage range
a)     Normal charge
b)     Float charge
c)     Boost charge
 
V DC
V DC
V DC
 
110 V ± 1%
120 V ± 1%
150 V ± 1%
 
110 V ± 1%
120 V ± 1%
150 V ± 1%
33Normal/boost charge independent units?Yes/NoTo be mentionedNo
34Output currentA5050
35Rated Battery CurrentA2020
36Efficiency%To be mentioned80%
37Ripple Voltage%3%3%
38Type of AVR-Static20V
39Installation Break Down VoltageKV2KV for 1 Minute2KV for 1 Minute
40Type of rectifierThyristorTo be mentionedThyristor
41MCCB   
 a)     QuantityNos.MCB will be provided near AC input & DC OutputMeet customer needs
 b)     RatingAAC input MCB-50A DC Output MCB-63AAC input MCB-50A DC Output MCB-63A
42Standard-As per Latest Edition of Applicable IEC-60146IEC-60146