China Gfuve CVT Tan-Delta Dielectric Loss Factor Tester, Find details about China Tan-Delta Tester, Dielectric Loss Tester from Gfuve CVT Tan-Delta Dielectric Loss Factor Tester
Dielectric loss tester can effectively find the overall damp, deterioration and partly defects of electrical equipment insulation, which are widely used in electrical manufacturing, electrical equipment installation, handover and preventive testing. The anti-interference precision dielectric loss tester is used for on-site anti-interference, dielectric loss measurement or laboratory dielectric loss measurement. The instrument is an integrated structure with built-in dielectric loss bridge, variable variable frequency power supply, test transformer and standard capacitor, etc.. The instrument adopts frequency conversion anti-interference and Fourier transform digital filtering technology, fully automatic and intelligent measurement, and the measurement data is very stable under strong interference. The result of measurement is displayed by large screen display, and the instrument comes with micro printer to print and print test results.
High voltage protection: Under condition of short circuit, breakdown or high voltage current fluctuation, it can cut off output at a high speed by short circuit mode
Power supply protection: incorrect connection of 380V, power supply fluctuation or sudden power failure, it will starti protection and avoid to cause over-voltage
Ground protection: it has the function of ground wiring detection and can not step up when it is not grounded. If the instrument is not grounded properly, the ground protection is started
CVT protection: four protection limits of voltage and current in high voltage, voltage and voltage and current in low voltage side to protect the equipment; the wrong menu will not output the exciting voltage. In CVT measurement without 10kV high voltage output
Anti misoperation: two level power switch; real-time monitoring of voltage and current; repeated key confirmation; distinctive terminal of high / low voltage; slow step-up; quick decompression; sound and light alarm
Anti - "Capacitance rise": when measuring large capacitance sample, the "rise" effect of voltage can occur. The instrument can automatically track the output voltage and keep the test voltage constant
High voltage cable: high voltage insulated wire can be used even connectting the floor
Anti-seismic performance: the instrument adopts unique anti-seismic design, and can withstand strong long-distance transportation, vibration and jolt without damage
Electrical parameters | ||
---|---|---|
Power supply | Single phase AC 220V±10% or 110V±10%, 50/60HzAC | |
Accuracy | Cx: + (reading * 1%+1pF)TG Delta: + (reading * 1%+0.00040) | |
Anti-interference index | frequency conversion anti-interference, can achieve the accuracy under 200% interference | |
Capacitance range | Internal applied high voltage: 3pF ~ 60000pF/10kV 60pF to 1 mu F/0.5kV | |
External applied high voltage: 3pF to 1.5 F/10kV 60pF to 30 mu F/0.5kV | ||
Resolution | maximum 0.001pF, 4 bit significant digits | |
TG delta range | no limit, resolution 0.001%, capacitance, inductance, resistance, three kinds of test products, automatic identification. | |
Test current range | 10 A to 5A | |
Internal Applied high voltage | set voltage range: 0.5 ~ 10kV | |
Maximum output current | 200mA | |
Lifting mode | continuous smooth adjustment | |
Voltage accuracy | + (1%× readings +10V) | |
Voltage resolution | 0.1V | |
Test frequency | 45, 50, 55, 60, 65Hz single frequency | |
45/55Hz, 55/65Hz, 47.5/52.5Hz automatic dual frequency conversion | ||
Frequency accuracy | 0.01Hz | |
External applied high voltage | positive and reverse wiring, the maximum test current 5A | |
CVT self excitation measurement | output voltage 3 ~ 50V, output current 3 ~ 30A | |
C1/C2 simultaneous measurements, high-voltage wiring can be mopping | ||
CVT ratio measurement | change ratio measurement accuracy: + reading×1% ratio, measuring range: 10~99999 | |
Phase measurement accuracy: + 0.02° | ||
phase measurement range: 0~ 359.99 ° | ||
High voltage dielectric loss | support frequency conversion and vibration supply, high voltage dielectric loss | |
Real time clock | time and date display in real time | |
Internal storage | 100 sets of measurement data can be stored inside the instrument | |
U disk | supports U disk storage | |
LCD | 5.7″black and white LCD displaye | |
Communication | RS232 and USB communication interface | |
Printer | internal installed 58mm wide thermal printer. | |
Standard | IEC61010-1, IEC61326-1 | |
Mechanical parameters | ||
Dimension (L×W×H) (mm) | 368x288x280 | |
Weight (kg) | 22 | |
Environmental conditions | ||
Operating temperature | -10°C to 50°C | |
Storage temperature | -20°C to 70°C | |
Relative humidity | ≤85%RH |