10kv/12kv Tangent Delta Power Transformer Capacitance Dissipation Dielectric Loss Capacitance Dissipation Test Device

China 10kv/12kv Tangent Delta Power Transformer Capacitance Dissipation Dielectric Loss Capacitance Dissipation Test Device, Find details about China Tangent Delta Testing, Transformer Capacitance Dissipation Test from 10kv/12kv Tangent Delta Power Transformer Capacitance Dissipation Dielectric Loss Capacitance Dissipation Test Device

Model NO.
HYGS
Trademark
Huaying
Origin
China (Mainland)
HS Code
903084900
Model NO.
HYGS
Trademark
Huaying
Origin
China (Mainland)
HS Code
903084900

Tangent Delta Tester HYGS


Introduction

HYGS tangent delta tester is a high-precision instrument, which can be applied to automatically measure electrical loss tangent ( ) and capacitance of all kinds of high voltage electrical equipments on the spot of power plants, substations,laboratory, etc. The instrument is an integrated structure with a dielectric loss test bridge, a variable frequency power supply, a step-up transformer and a SF6 high stability standard capacitor.   

Features
★Large LCD display
Simple operation, the instrument is equipped with a high-end full touch LCD screen, super touch interface, and each process is very clear. Operators can use it without additional professional training.
★Mass storage data
The instrument is equipped with a calendar chip and large capacity memory. The test results can be stored in chronological order. Users can view historical data at any time and print it out.
★Multiple test modes
The instrument can be tested by high pressure, high voltage, standard, positive connection method, reverse connection method, self excitation method and other methods.
★CVT test step in place
The instrument can also test the full sealed CVT (capacitor voltage transformer) C1, C2 dielectric loss and capacitance, to achieve the C1, C2 simultaneous test. 
★Do not dismantle the high-voltage lead measurement CVT
The instrument can accurately measure the dielectric loss and capacitance of CVT without dismantling the CVT high voltage lead.
★CVT reverse shield method for measuring C0
The instrument can be used to measure the dielectric loss and capacitance value of C0 on the upper end of CVT.
★High speed sampling signal
The inverter and sampling circuit of the instrument are all controlled by digital, and the output voltage is adjustable continuously.
★Multi protection security
The instrument has many protection measures, such as input voltage fluctuation, output short circuit, over voltage, over current and temperature.

Technical index

1

Use conditions

-15ºC∽40ºC

RH<80%

2

Anti-interference

Frequency conversion

3

Power

AC 220V±10%

Allowable generator

4

High output

0.5KV∽10KV(rated voltage:10KV)

Every 0.1kV

0.5KV∽12KV(rated voltage:12KV)

Precision

2%

Maximum current 

200mA (rated voltage:10KV)

167mA (rated voltage:12KV)

Capacity

2000VA

5

Self-excited power

AC 0V∽50V/15A

45HZ/55HZ   47.5HZ/52.5HZ
55HZ/65HZ   57.5HZ/62.5HZ
Automatic double frequency

6

Resolving power

tgδ: 0.001%

Cx: 0.001pF

7

Precision

△tgδ:±(Reading*1.0%+0.040%)

△C x :±(Reading*1.0%+1.00PF)

8

measuring range

tgδ

Unlimited

C x

15pF < Cx < 300nF

rated voltage:10KV

10KV

Cx   < 60  nF

5KV

Cx < 150 nF

1KV

Cx < 300 nF

rated voltage:12KV

12KV

Cx < 30  nF

5KV

Cx < 150 nF

1KV

Cx < 300 nF

CVT test

Cx < 300 nF

9

CVT range

10∽10000

accuracy

0.1%

Resolving power

0.01

10

Exterior dimension

350(L)×270(W)×270(H)

11

Memory size

The 200 groups supports U disk data storage

12

Weight

28 Kg


10kv/12kv Tangent Delta Power Transformer Capacitance Dissipation Dielectric Loss Capacitance Dissipation Test Device

Other products:
Circuit Breaker Analyzer / Contact Resistance Tester / On Load Tap Changer Tester / Circuit Breaker Vacuum Degree Tester / Insulating Oil Tester / CT PT Analyzer / Transformer Winding Resistance Tester / Sweep Frequency Response Analyzer / Transformer Load and No-load tester / Transformer Ratio Tester / Primary Current Injection Test Set / Frequency Adjustable Series Resonance Test Set / High Voltage Divider / High Voltage Generator / VLF tester / Wireless HV Phase Tester / MOA Metal Oxide Arrester MOA Tester / Hipot Tester / Relay Tester / Insulation Tester / Grounding Resistance Tester



logistics
10kv/12kv Tangent Delta Power Transformer Capacitance Dissipation Dielectric Loss Capacitance Dissipation Test Device

Certification Show
10kv/12kv Tangent Delta Power Transformer Capacitance Dissipation Dielectric Loss Capacitance Dissipation Test Device

Company Profile
10kv/12kv Tangent Delta Power Transformer Capacitance Dissipation Dielectric Loss Capacitance Dissipation Test Device


Customers Visiting
10kv/12kv Tangent Delta Power Transformer Capacitance Dissipation Dielectric Loss Capacitance Dissipation Test Device


Exhibition
10kv/12kv Tangent Delta Power Transformer Capacitance Dissipation Dielectric Loss Capacitance Dissipation Test Device

Technical Support
10kv/12kv Tangent Delta Power Transformer Capacitance Dissipation Dielectric Loss Capacitance Dissipation Test Device
10kv/12kv Tangent Delta Power Transformer Capacitance Dissipation Dielectric Loss Capacitance Dissipation Test Device

10kv/12kv Tangent Delta Power Transformer Capacitance Dissipation Dielectric Loss Capacitance Dissipation Test Device


Partners
10kv/12kv Tangent Delta Power Transformer Capacitance Dissipation Dielectric Loss Capacitance Dissipation Test Device



Contact Us