China High Precision Transformer Test Instruments Tangent Delta Tester Automatically Measurement, Find details about China Tangent Delta Tester, Power Transformer Capacitance Dissipation from High Precision Transformer Test Instruments Tangent Delta Tester Automatically Measurement
Tangent Delta Tester HYGS
Introduction
HYGS tangent delta tester is a high-precision instrument, which can be applied to automatically measure electrical loss tangent ( ) and capacitance of all kinds of high voltage electrical equipments on the spot of power plants, substations,laboratory, etc. The instrument is an integrated structure with a dielectric loss test bridge, a variable frequency power supply, a step-up transformer and a SF6 high stability standard capacitor.
Features
★Large LCD display
Simple operation, the instrument is equipped with a high-end full touch LCD screen, super touch interface, and each process is very clear. Operators can use it without additional professional training.
★Mass storage data
The instrument is equipped with a calendar chip and large capacity memory. The test results can be stored in chronological order. Users can view historical data at any time and print it out.
★Multiple test modes
The instrument can be tested by high pressure, high voltage, standard, positive connection method, reverse connection method, self excitation method and other methods.
★CVT test step in place
The instrument can also test the full sealed CVT (capacitor voltage transformer) C1, C2 dielectric loss and capacitance, to achieve the C1, C2 simultaneous test.
★Do not dismantle the high-voltage lead measurement CVT
The instrument can accurately measure the dielectric loss and capacitance of CVT without dismantling the CVT high voltage lead.
★CVT reverse shield method for measuring C0
The instrument can be used to measure the dielectric loss and capacitance value of C0 on the upper end of CVT.
★High speed sampling signal
The inverter and sampling circuit of the instrument are all controlled by digital, and the output voltage is adjustable continuously.
★Multi protection security
The instrument has many protection measures, such as input voltage fluctuation, output short circuit, over voltage, over current and temperature.
1 | Use conditions | -15ºC∽40ºC | RH<80% | |
2 | Anti-interference | Frequency conversion | ||
3 | Power | AC 220V±10% | Allowable generator | |
4 | High output | 0.5KV∽10KV(rated voltage:10KV) | Every 0.1kV | |
0.5KV∽12KV(rated voltage:12KV) | ||||
Precision | 2% | |||
Maximum current | 200mA (rated voltage:10KV) | |||
167mA (rated voltage:12KV) | ||||
Capacity | 2000VA | |||
5 | Self-excited power | AC 0V∽50V/15A | 45HZ/55HZ 47.5HZ/52.5HZ | |
6 | Resolving power | tgδ: 0.001% | Cx: 0.001pF | |
7 | Precision | △tgδ:±(Reading*1.0%+0.040%) | ||
△C x :±(Reading*1.0%+1.00PF) | ||||
8 | measuring range | tgδ | Unlimited | |
C x | 15pF < Cx < 300nF | |||
rated voltage:10KV | 10KV | Cx < 60 nF | ||
5KV | Cx < 150 nF | |||
1KV | Cx < 300 nF | |||
rated voltage:12KV | 12KV | Cx < 30 nF | ||
5KV | Cx < 150 nF | |||
1KV | Cx < 300 nF | |||
CVT test | Cx < 300 nF | |||
9 | CVT range | 10∽10000 | ||
accuracy | 0.1% | |||
Resolving power | 0.01 | |||
10 | Exterior dimension | 350(L)×270(W)×270(H) | ||
11 | Memory size | The 200 groups supports U disk data storage | ||
12 | Weight | 28 Kg |
Other products:
Circuit Breaker Analyzer / Contact Resistance Tester / On Load Tap Changer Tester / Circuit Breaker Vacuum Degree Tester / Insulating Oil Tester / CT PT Analyzer / Transformer Winding Resistance Tester / Sweep Frequency Response Analyzer / Transformer Load and No-load tester / Transformer Ratio Tester / Primary Current Injection Test Set / Frequency Adjustable Series Resonance Test Set / High Voltage Divider / High Voltage Generator / VLF tester / Wireless HV Phase Tester / MOA Metal Oxide Arrester MOA Tester / Hipot Tester / Relay Tester / Insulation Tester / Grounding Resistance Tester