Mv-105, Power Cable, 5 Kv, 3/C, Cu/Epr/Cts/CPE (ICEA S-93-639/NEMA WC71/UL 1072 )

China Mv-105, Power Cable, 5 Kv, 3/C, Cu/Epr/Cts/CPE (ICEA S-93-639/NEMA WC71/UL 1072), Find details about China Power Cable, XLPE Cable from Mv-105, Power Cable, 5 Kv, 3/C, Cu/Epr/Cts/CPE (ICEA S-93-639/NEMA WC71/UL 1072)

Model NO.
MV-105
Wire Core Material
Bare Copper Wire
Certification
ISO, CCC
Model
Mv-105
Brand
Boan
Rated Voltage
5 Kv
Number of Cores
3
Section
8 AWG-1000 Mcm
Class of Conductor
B
Type of Shield
Tinned Copper Tape
Trademark
DingAn
Transport Package
Heated Steel-Wooden Drum/Steel Drum
Specification
SGS
Origin
Jiangsu Yixing, China
HS Code
8544601200
Model NO.
MV-105
Wire Core Material
Bare Copper Wire
Certification
ISO, CCC
Model
Mv-105
Brand
Boan
Rated Voltage
5 Kv
Number of Cores
3
Section
8 AWG-1000 Mcm
Class of Conductor
B
Type of Shield
Tinned Copper Tape
Trademark
DingAn
Transport Package
Heated Steel-Wooden Drum/Steel Drum
Specification
SGS
Origin
Jiangsu Yixing, China
HS Code
8544601200
MV-105, Power Cable, 5 KV, 3/C, Cu/EPR/Cts/CPE (ICEA S-93-639/NEMA WC71/UL 1072)

Features
UL Listed as MV-105. True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends.

Application
Primary power and distribution circuits in industrial and commercial installations, power circuits in generating plants where line to ground fault current are within shield capabilities. May be used in wet or dry
locations, installed in raceways, duct, and open air, aerially or directly buried as permitted by NEC.

Standards
UL 1072: Medium Voltage Power Cables.
ICEA S-93-639/NEMA WC74: 5 kV - 46 kV Shielded Power Cables.
ICEA S-97-682: Standard for Utility Shielded Power Cables Rated 5 kV - 46 kV.
AEIC CS8: Specification for Extruded Dielectric, Shielded Power Cables Rated 5 kV- 46 kV.

Specifications
Maximum operating voltage: 5 kV to 25 kV 100% and 133% IL
Maximum conductor operation temperatures: Wet and dry locations, Normal: 105°C, Emergency: 140°C, Short Circuit: 250°C

Engineering Information
1. Conductor: Soft annealed uncoated copper compacted Class B per ASTM B496 or hard drawn Aluminum-1350 compacted Class B per ASTM B400.
2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).
3. Insulation: Thermoset ethylene propylene rubber (EPR). On request, Amorphous EPR.
4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).
5. Metallic Shield: Soft annealed tinned copper tape, 5 mil thick, 25% minimum overlap.
6. Grounding (Optional): One or three tinned copper or covered conductors cabled with phase conductors.
7. Assembly: Conductors cabled with non-hygroscopic fillers, as required and binder tape.
8. Jacket: Black sunlight resistance and flame retardant chlorinated polyethylene (CPE) compound.

100% and 133% Insulation Levels (90 mil)
SizeNumber of StrandsConductor NominalJacket ThicknessApproximate Outside DiameterApproximate Net Weight
CopperAluminum
AWG of kcmil inmilinlb/kft
870.13801.2810-
670.17801.27990816
470.21801.371218941
270.27801.4915561115
1190.3801.5518151260
1/0190.34801.6320941393
2/0190.381101.7925571674
3/0190.421101.8930171902
4/0190.48110235482144
250370.521102.1340722411
300370.571102.2346572665
350370.621102.3352432917
400370.661102.4258613205
500370.741102.6470913771
600610.811402.984624475
750610.911403.11101325155
1000611.061403.43129866352