China Hdbc, Stranded Bare Copper Conductor (AS 1746), Find details about China Bare Copper Conductor, Copper Ground Wire from Hdbc, Stranded Bare Copper Conductor (AS 1746)
Stranding and wire diameter | Approx. overall diameter | Cross-sectional area | Mass per | Calculated breaking laod (CBL) | Equivalent aluminium area | D.C. resistance per km at 20°C |
mm | mm | mm2 | kg | kN | mm2 | Ω |
7/1.00 | 3.00 | 5.498 | 49.3 | 2.32 | 8.68 | 3.25 |
7/1.25 | 3.75 | 8.589 | 76.9 | 3.59 | 13.6 | 2.09 |
7/1.75 | 5.25 | 16.84 | 151 | 6.89 | 26.6 | 1.06 |
7/2.00 | 6.00 | 21.99 | 197 | 8.89 | 34.7 | 0.815 |
7/2.75 | 8.25 | 41.58 | 375 | 16.2 | 65.3 | 0.433 |
19/1.75 | 8.75 | 45.70 | 413 | 18.3 | 71.7 | 0.395 |
19/2.00 | 10.0 | 59.70 | 538 | 23.6 | 93.6 | 0.303 |
7/3.50 | 10.5 | 67.35 | 607 | 25.4 | 106 | 0.268 |
7/3.75 | 11.3 | 77.28 | 696 | 28.8 | 121 | 0.233 |
37/1.75 | 12.3 | 88.99 | 806 | 35.6 | 139 | 0.203 |
19/2.75 | 13.8 | 112.9 | 1020 | 43.1 | 177 | 0.160 |
19/3.00 | 15.0 | 134.3 | 1210 | 50.8 | 211 | 0.134 |
37/2.50 | 17.5 | 181.6 | 1640 | 70.3 | 284 | 0.099 6 |
37/2.75 | 19.3 | 219.8 | 1990 | 83.9 | 344 | 0.082 3 |
37/3.00 | 21.0 | 261.6 | 2370 | 98.9 | 409 | 0.069 1 |
61/2.75 | 24.8 | 362.3 | 3290 | 138.0 | 566 | 0.050 0 |