22kv Medium Voltage Switchgear

China 22kv Medium Voltage Switchgear, Find details about China Switchgear, Mv Switchgear from 22kv Medium Voltage Switchgear

Model NO.
KYN28-24
Warranty
1 Year
Protection Level
IP3X
Voltage
11kv
Rated Load
2500A
Application
Electric Power
Customized
Customized
Surface Treatment
Powder Coating
Trademark
ROCKWILL
Transport Package
Wooden
Specification
IEC, ANS
Origin
China
HS Code
85352100
Model NO.
KYN28-24
Warranty
1 Year
Protection Level
IP3X
Voltage
11kv
Rated Load
2500A
Application
Electric Power
Customized
Customized
Surface Treatment
Powder Coating
Trademark
ROCKWILL
Transport Package
Wooden
Specification
IEC, ANS
Origin
China
HS Code
85352100
This switchgear mainly applies in the power system of AC 3~36KV three phase 50/60Hz in the construction of city power network and reconstruction project, factory and mineral enterprise, high building and public facility to receive and distribute power.

Rated voltage: 12 kV/24kV/36kV
Rated frequency: 50Hz
Mechanical life: 10000 times
Protection degree: IP3X
Main busbar rated current: 630A up to 4000A
Load break switch full capacity breaking time: 100 times
Fuse breaking current: 31.5-50 kA
  
22kv Medium Voltage Switchgear

Feature

1. Indoor or outdoor electrical switchgear, factory-assembled, for primary and secondary distribution systems protection.

2. Up to 40kV, 3150A, 50 / 60Hz

3. Modular space-saving design, metal-enclosed, removable or fixed type

4. IEC standards compliant

5. Parts from ABB, SCHNEIDER, GE, etc., are available

6. Improved safety for personnel and operations

7. Quality is assured by extensive design and production tests, coupled with manufacturing in facility that  has been certified in compliance with ISO 9001.


8.  One year warranty

Standard Service Condition

1. The ambient air temperature does not exceed 40°C and its average value, measured over a period of  24h, does not exceed 35°C.

2. The minimum ambient air temperature is -5°C.

3. The altitude does not exceed 1000m.

4. he ambient air is not significantly polluted by dust, smoke, corrosive and/or flammable gases, vapours

or salt.

5. The conditions of humidity are as follows:

-   The average value of the relative humidity, measured over a period of 24h, does not exceed 95%;

-   The average value of the water vapour pressure, over a period of 24h, does not exceed 2.2kPa;

-   The average value of the relative humidity, over a period of one month, does not exceed 90%;

-   The average value of the water vapour pressure, over a period of one month, does not exceed 1.8kPa.

Application

1.  Substations

2.  Public utilities

3.  Industrial plants

4.  Public buildings: high-rise buildings, railway stations, hospitals

Specification

 Item

Units

Data

 Rated frequency

Hz

50/60

 Rated voltage 

kV

22,24

 1min power frequency withstand voltage

kV

(50)65

 Rated impulse withstand voltage(peak)

kV

125

 Rated current

A

630,1250,1600,2500,3150

 Rated current of branch bus

A

630,1250,1600,2500

 Rated short time withstand current

kA

16 ,20,25,31.5

 Rated peak withstand current

kA

40,50,63,80

 Rated short circuit continuous time

s

4

 Protection level

  Shell:IP4X,IP2X When CPT and CB door are open

 Weight

      Kg                        800,1000 (Rated current>1600)

More pls contact with us.
22kv Medium Voltage Switchgear
22kv Medium Voltage Switchgear
22kv Medium Voltage Switchgear
22kv Medium Voltage Switchgear




22kv Medium Voltage Switchgear
22kv Medium Voltage Switchgear

22kv Medium Voltage Switchgear
22kv Medium Voltage Switchgear
22kv Medium Voltage Switchgear