Chapter 1 Introduction
ZXB07.001 is a low duty power supply with AC/DC multiple outputs. Due to the latest circuit design, it is compact and of reliable performance. The whole system is of high regulation and output efficiency. The wide input voltage applicable to rural power network. The product is equipped with protection against output over-current, short circuit, protection, output over-voltage and over-temperature. The product is cooled by natural convection. It is designed according to the safety regulations, which strictly conforms to the safety standard of information technology.

Chapter 2 Technical Specification
2.1. Ambient Requirements
2.1.1
ItemUnitMinTyp.MaxRemark
Nominal operation temperatureºC-52555Safety approved.
Operation temperatureºC-252565The power system normally operates.
Relative humidity%5 93No condensing
Absolute humidityg/m30.26 25No condensing
Altitudem---Operation atmospheric pressure: 70kPa~106kPa
Cooling
      
Natural cooling. The heat generated by customized power shall be conducted to the enclosure through contact with max temperature of 65ºC and the conduction section shall be 28555mm2.
Operating duration24Hs continuous work.
2.1.2 Storage conditions
ItemUnitMinTyp.MaxRemark
Storage temperatureºC-40-80 
Relative humidity%0-95 
Absolute humidityg/m30.03 30 
Altitudem0 2000 
Temperation variationºC/min  1 

2.2. Input Properties
ItemUnitMinTypicalMax.Remark
Rated input voltageVac 220  
Input voltage rangeVac85220290Nominal input voltage: 100-240Vac
Input frequencyHz435067 
Inrush currentA  3025ºC cold startup 290V input, full load
Input power factor 0.95  Rated full load
2.3. Output Electrical Properties
      1. Basic Output Properties
Output voltageOutput voltage ratingOutput currentLoad RegulationLine regulationRegulationVp-p
-54V-53.5~-54.5V1.6A≤±2%≤±2%≤±3%≤±3%
3.4V3.3~3.5V7A≤±2%≤±2%≤±3%≤±3%

Remark:
  1. After operation under low temperature for 1 hour, the ripple (p-p) shall be measured with 1 10uF aluminum capacitor and 1 0.1uF filmy capacitor at output. The twisted pair is 20cm and within 20MHz bandwidth of oscillograph. There shall be no battery and backup power during the test.
  2. The system output current is 1.6A including the charge current (1A) under voltage of -54V. There shall be no battery and backup power during the test.
  3. -54V output shall be adjustable within -45~-54 under equalizing charge or discharge of battery.

  • Other Output Properties
ItemUnitMinTypicalMax.Testing Conditions
Output powerW-110.2  
110V Output efficiency%80  Test with load of 2.5A at -54V and 8A at 3.4V. The ambient temperature is 25ºC.There shall be no battery and backup power during the test.
220V Output efficiency%82   
Temperature coefficient/ºC  0.03% 
Over/under shoot @start up/shutdown   5% 
Transient response overshoot   5%Di/dt=10A/s, 25%~50%~75%Load variation with rate ≤0.1A/uS, calculated from the part out of the output line regulation range.
Transient response recovery durationμS  200
Turn on timeS  4Rated input/output
Output voltage boost durationmS  100Rated input/output, boost from 10% to 90%
Capacitive load capabilityuF  1000-54V
uF  40003.4V
3.4V power down delaymS10  The input voltage keeps to 3.4V/8A. There shall be no battery and backup power during the test.
 
  • Battery management
Dual outputs are provided at battery interface for battery operation and -48V backup power input (Battery/backup power -48V common power point: -48VRTN/BAT+, -48V backup power, BAT-). Connect only the battery if there is only 220Vac input and connect the backup power when fed by both 220Vac and backup power. Two diodes are employed for isolation of -48V backup and -48V voltage transferred from 220ac.

Note: There shall be only green LED on for normal power supply form AC input and -48V backup. Other parameters are measured without backup power.
Schematic diagrams for above two situations:
Power supplied by 220V only:

Power supplied by 220V and backup:


The -54V and 3.4V outputs will be powered by battery under situation of AC mains failure and the normal operation duration under full configuration shall be not less than 4 hours. 
The system is functioned with secondary shutdown, however, the battery load is controlled by main devices. 48V lead acid battery is adopted for backup and the discharge is managed by system. Current limiting shall be conducted during battery charge, the ultimate charge current shall be 1A.
ItemRequirementRemark
Float voltage54VRegulation: ±2%
Current limiting for equalizing/float chargeEqualize charge with voltage not more than -56V and then float charge.≤1A
U/V alarm set point46±1VAlarm through potential free contact
Power down protection set point43.5±0.5V 
Leakage currentNot supplied<0.35mA
Recovery set pointFrom battery shutdown till the re-power on of rectifier AC input 
Temp. compensation coefficientNot suppliedNot supplied
Battery capacity7AHDefault configuration (with charge capacity of 10-12AH)
Battery reversed polarity protectionSupplied 
Battery current limitingCurrent limiting circuit is supplied for battery dischargeThe fuse will be blown at over current.


2.4. Protection
 
ItemUnitMinTypicalMax.Recovery Property
Input O/V protection set pointV290310320Without battery and backup power
Input O/V recovery  set pointV290300320
Input O/V protection hysteresisV8  
Input U/V protection set pointV606585Without battery and backup power
Input U/V recovery set pointV607585
Input U/V protection hysteresis V8  
-54V output O/V protectionV-59-62-65Lock up, without battery and backup power
3.4V output O/V protectionV3.73.954.2
-54V output over-current protectionA2.7533.75Auto-recoverable, without battery and backup power, 3.4V, with 8A full load
3.4V output over-current protectionA111315Auto-recoverable, without battery and backup power
Thermal protectionºC   Auto-recoverable, without battery and backup power
Short circuit protectionA Damage free under long-term short circuit, auto-recoverable, without battery and backup power
Input power failure alarm 
Auto-recoverable, without battery and backup power
Output protection requirement Output protection at 3.3V shall not affect the output at -54V.




2.5. Safety and insulation rating
 
ItemRatingStandard(or Testing condition)
Insulation voltage(output-GND)500Vac500Vac/1Min / Leakage current≤10mA, no breakdown or flashover
Insulation voltage (input -GND)1500Vac1500Vac/1Min / Leakage current≤10mA, no breakdown or flashover
Insulation voltage (input to output)3000Vac3000Vac/1Min / Leakage current≤10mA, no breakdown or flashover
Insulation resistance10MΩRH:<90%, DC 500V, the insulation resistance of input to output, input to ground, and output to ground is not less than 10MΩ.
Leakage current<3.5mAMax input operation voltage, 50Hz input

2.6. EMC

 
ItemRequirementStandard
CECLASS B for integrated and CLASS A for single equipmentEN55022
RECLASS B for integrated and CLASS A for single equipmentEN55022
Harmonic currentCLASS DIEC 61000-3-2[6]
CSTesting frequency: 0.15MHZ-80MHZ; Electric strength: 3V; AM: 80% (1KHZ) IEC61000-4-3 (Criterion A)
RSTesting frequency: 80MHZ-1000MHZ; Electric strength: 10V; AM: 80% (1KHZ) IEC 61000-4-6 (Criterion A)
ESDAir discharge: ±8KVIEC 61000-4-2 (Criterion A)
Contact discharge: ±6KV
Voltage ripple & flickerPST≤1.0;PLT≤0.65;dC≤3%;dmax≤4%;Vd(t) is 3% or less when the voltage ripple duration is more than 200msIEC61000-3-3
 EFT/B±2KVIEC61000-4-4 (Criterion B)
SURGEBasic: Wire-wire: 2Ω IR, ±1KV Wire-GND: 12Ω IR,±2KV (Criterion B)
Strengthening: Wire-wire: ±4KV, 2Ω IR, Wire-GND: ±6KV, 12Ω IR, (Criterion R)
EN61000-4-5
DIPThe voltage derates to 70%Ut and the duration is 100ms (5 periods), conforms to criterion B at 0°,45°,90°,135°,180°,225°, 270°, 315°.EN61000-4-11
Ut=264Vac:Criterion A
Ut=220Vac:Criterion A
Ut=90Vac:Criterion A
The voltage derates to 70%Ut and the duration is 20ms(1 period),conforms to criterion B at 0°,45°,90°,135°,180°,225°, 270°,315°.EN61000-4-11(Criterion B)
The voltage derates to 0%Ut and the duration is 10ms(Half a period)EN61000-4-11(Criterion B)
OthersEN61000-4-11(Criterion B)

2.7. Other requirements
ItemRequirementsProperty
Acoustic noise<50dB(A)Pass
MTBF≥80,000H 
Annual repair rate≤0.2% 
Operation vibration5-9Hz,3.5mm;9-200Hz: 1g; 3 axes, SF for 5 times per axisPass
Random vibrationAcceleration spectral density, 5~20Hz: 1.0;20~200Hz: -3dB; RMS acceleration: 0.781Grms
3 axes
Testing duration: 30min per axis
Pass
ImpactImpact waveform: Half-sine wave;
Acceleration Vp: 300m/s2
Pulse width: 6ms;
6 axes
3 times per axis
Pass
BumpBump waveform: Half-sine wave;
Acceleration Vp: 180m/s2
Pulse width: 6ms;
6 axes
100 times per axis
 
DropWeight: ≤15kg
Height: 100cm
Drop test for 1 angle, 3 prisms and 6 surfaces:
Angle:
Choose the frailest one for test, if unavailable, the angel 2-3-5 shall be applied.
3 pcs of prisms: prism that joint at the base angle
6 pcs of faces: surfaces of tested unit
Drop time: once per surface
 
Damp proof24~45ºC,95%RH,48hGB/T 2423.4-1993
Mildew proofMildew test  Class BGB/T 2423.16-1999
Smog proofSmog test, 96HGB/T 2423.17-1999
DustproofDust with diameter more than 5um shall be not more than 3×104 particles/m3,the dust particles shall be non-conducting and non-corrosive.Pass
Static pressureTL=Wt×(S-1)×F×9.8(N)
TL: pressure applied, unit: N; Wt: weight of packaged piece, unit: kg;
S: stack available, adopt the maximum value;
F: safety coefficient, usually specified as 5;
S=3/h;
h--height of packaged piece, unit: m
The pressure shall be imposed for 2H.
 
Low voltageTested at 4000m altitudeRefer to GB2423