Company founded in 2010. The company's headquarters is located in Jinhe community of Zhangmutou town in Dongguan. The practical area of the factory is about 10 thousand square meters. It sets up distribution outlets in East China, North China, northwest and other places. It is a high-tech enterprise in Dongguan. The company has more than 20 patents.
Electric Characteristics | |||||
No. | Parameter | Tested Terminal | Value | Test Condition | Standard Test Instrument |
1 | Non-load Output Voltage | a-b-c | 800V+/-3% | Input: A-B-C 800V, 50Hz Output: no load | Transformer comprehensive tester |
2 | Load Output Voltage | a-b-c | 800V+/-5% | Input: A-B-C 800V, 50Hz, a-b-c outout end with a 350KW rated resistive load | |
3 | Rated Apparent Power | 350KVA | |||
4 | Working Frequency | 47.5-55Hz | |||
5 | Rated Load Current | a-b-c | 252.5 A | ||
6 | Connection method | YNyn0 | |||
7 | Non-load Current | a-b-c | <15A | Input:A-B-C, 800V, 50Hz, Output: no load | |
8 | Short Circuit Impedance | Average Voltage between A-B-C /800V*100% | (4+/-1%) | Short-circuit a-b-c phase output line current reaches 252.5A | |
9 | Temperature Rise | The hottest spot in the coil | <110K | Rated full load, air cooling | |
10 | Full Load Efficiency | >97.5% (25+/-5 degree centigrade) | Input: A-B-C 800V, 50Hz, a-b-c outout end with a 350KW rated resistive load | ||
11 | Insulation Grade | H | |||
12 | Input Voltage Range | 1.1 times the rated input voltage, the iron core not saturated | |||
13 | Insulation Resistance | Winding - core, primary - secondary, temperature relay - winding, core | >100MΩ | 500V DC, temperature 40ºC or less, humidity 80% or less | ohm gaugae |
14 | Dielectric Strength | Winding - core, primary - secondary, temperature relay - winding, core | <35mA, no arcing breakdown | 2500V/50Hz/60S | Power Frequency Voltage Tester |
15 | Noise | one meter distance | <75dB | The rated conditions | |
16 | Work Environment | Operating Temperature | -25~50 degree centigrade | ||
Altitude | <2000m |