Multi-Function Portable Transformer CT/ PT Analyzer Test Set CT Analyser

China Multi-Function Portable Transformer CT/PT Analyzer Test Set CT Analyser, Find details about China CT/PT Analyzer Test Set, CT PT Analyzer from Multi-Function Portable Transformer CT/PT Analyzer Test Set CT Analyser

Model NO.
CT-300
Model NO.
CT-300
Brief introduction
This device uses high-performance DSP and ARM, advanced manufacturing process to ensure that the product is stable and reliable, full-featured, high degree of automation, high test efficiency, is the professional testing equipment for the CT/PT industry.
Products features
  1. Full-featured , meet all kinds of CT (e.g.: protection, measuring, TP) excitation characteristics ( i.e. voltage characteristics ), ratio, polarity , secondary winding resistance, secondary load, ratio error and phase angle error and other testing requirements , also for various types of PT electromagnetic unit excitation characteristics, ratio, polarity , secondary winding resistance , ratio error and phase angle error and other testing requirements.
  2. Automatically gives the knee voltage / current, 10% ( 5% ) error curve , accuracy limit factor (ALF), instrument security factor (FS), secondary time constant (Ts), remanence coefficient (Kr), saturated and unsaturated inductors and others CT, PT parameters.
  3. Meet IEC60044-1, IEC60044-6 CT/PT standard.
  4. Based on an advanced low-frequency testing theory, able to test knee point of the CT test up to 30KV.
  5. Device can store 2000 groups of test data, non-volatile. After the test is completed with U disk to the PC, data analysis software, and generate reports in WORD file.
  6. Testing is simple and convenient, one button complete CT resistance, excitation, ratio and polarity tests, except load test , CT various other tests are using the same wiring.
  7. Easy to carry, instrument weight<9KG.
Product parameters
Testing purposesProtective CT
Output 0~180Vrms, 12Arms,36A(peak value)
Voltage measurement accuracy±0.2%
CT ratio measurement Range: 1~30000
Accuracy: ±0.2%
PT ratio measurementRange: 1~10000
Accuracy: ±0.2%
Phase measurementResolution: 0.5min
Accuracy: ±5min
Secondary winding resistance measurementRange: 0~300Ω
Accuracy: 2%±2mΩ
AC load measurementRange:  0~300VA
Accuracy:  2%±0.2VA
Input supply voltageAC220V±10%, 50Hz
Work EnvironmentTemperature:-10ºC ~ 50ºC, humidity≤90%
Dimension & weight Dimension: 340×300×150mm3, weight≤9Kg