China CT/PT Transformer Comprehensive Tester/Polarity Test/Transformation Ratio Test, Find details about China Turns Ratio Meter, Transformer Turn Ratio from CT/PT Transformer Comprehensive Tester/Polarity Test/Transformation Ratio Test
Introduction
TPVA-402 transformer tester is a fully automatic transformer comprehensive tester. The tester can finish: CT/PT volt-ampere characteristic curve test, CT/PT Polarity test, CT/PT Transformation ratio test, automatically calculating error curve of any CT point.
Features
1 This TPVA-402 transformer tester is easy to operate. Complete computerize device and high performance CPU,no need manual work,it finishes test automatically,which prevent person from high voltage circuit.
2 Large output. Maximum output voltage of volt-ampere characteristic test reaches to 1000V,Maximum output current of transformation ratio test is 600A,output capacity of internal voltage regulating machine is 5KVA.
3 Optional accessory includes external join to voltage raising machine ,current raising machine and voltage regulating machine.Maximum voltage of external voltage raising machine is 2000V,3A;Maximum current of external current raising machine is 1000A;Maximum output of external voltage regulating machine is 1500V,20A.You can have a CT test of reach up to 500KV,1A when using external voltage raising machine.
4 320*240 Large screen,it can display volt-ampere characteristic curve directly when the test is finished.It can print curve and result anytime with micro-printers of the tester.
5 Adapt rotating mouth,easy operation and durable use.
6 Flash Ram inside,prevent data losing from power off.
7 RS232 communication interface,make sure connection of the instrument and PC,triers can control the test and unload the test data through PC.
8 AC220V and AC380V power supply
Parameters
Input voltage | Output scope | Measuring scope | Measuring degree | |||
Device body | 220V | 0~600V,0~20A | 0~600V,0~20A | 0.5% | ||
380V | 0~1000V,0~20A | 0~1000V,0~20A | 0.5% | |||
220V | 0~600A | 0~600A | Ratio measuring precision 1% | |||
Voltage raising machine | 220V | 0~1650V,0~3A | 0~1650V,0~3A | 0.5% | ||
380V | 0~2000V,0~3A | 0~2000V,0~3A | 0.5% | |||
Current raising machine | 220V | 0~1000A | 0~1000A | Ratio measuring precision 1% | ||
Voltage adjustment machine |
|
| 0~1000V,0~30A | 0.5% | ||
Power | AC 220V/380V 50HZ | Size: | 420×330×320mm | Weight: | 24kg |