China High Efficiency Inverter Charger 3000va Inverex, Find details about China High Efficiency Inverter, Inverter Charger from High Efficiency Inverter Charger 3000va Inverex
MODEL | PSC3K-24 |
Input Voltage Waveform | Sinusoidal (utility or generator) |
Nominal Input Voltage | 230Vac |
Low Line Disconnect | 170Vac±4%(NOR) 90Vac±4%(GEN/WID) |
Low Line Re-connect | 180Vac±4% (NOR) 100Vac±4% (GEN/WID) Note: 1.NOR setting can be used for general electrical appliance 2. WID setting can be used only for some special load, such as lamp, fan. |
High Line Disconnect | 280Vac±4% |
High Line Re-connect | 270Vac±4% |
Max AC Input Voltage | 300Vac rms |
Nominal Input Frequency | 50Hz / 60Hz (Auto detection) |
Low Line Frequency Disconnect | 40±1Hz |
Low Line Frequency Re-connect | 42±1Hz |
High Line Frequency Disconnect | 65±1Hz |
High Line Frequency Re-connect | 63±1Hz |
Output Voltage Waveform | As same as Input Waveform |
Output Short Circuit Protection | 30ACircuit Breaker |
Efficiency (Line Mode) | >95% ( Rated R load, battery full charged ) |
Transfer Switch Rating | 30A |
Transfer Time | 10ms (typical) 15ms max(NOR) 20ms (typical) 40ms max(GEN/WID) |
Bypass charger enable in off mode | Yes |
Power Limitation |
MODEL | PSC3K-24 |
Output Voltage Waveform | Pure Sine Wave |
Rated Output Power | 3000VA |
Power Factor | 0.8 |
Nominal Output voltage | 230Vac |
Minimum Peak Output Voltage at Rated Power | >200V |
Output Frequency(Hz) | 50Hz / 60Hz ± 1Hz (follow first connect to grid) |
Output Voltage Regulation | ±10% Vrms |
Nominal Efficiency | >90% (@Normal DC Input; >60% R load) |
Over-Load Protection | fault after 5s@≥150% load,<=200% load fault after 10s@110%~150% load, |
Surge rating | 6000VA |
Capable of starting electric motor | 1.5HP |
Output Short Circuit Protection | Current limit (Fault after 4 cycles max) |
Nominal DC Input Voltage | 24V |
Min DC start voltage | 20V |
Low DC Alarm | 21.0 ± 0.6Vdc |
Low DC Alarm Recovery | 21.6 ± 0.6Vdc |
Low DC Shut-down | 20.0 ± 0.6Vdc |
Low DC Shut-down Recovery | 22.0 ± 0.6Vdc |
High DC Shut-down | 30.0 ± 0.6Vdc |
High DC Shut-down Recovery | 29.0 ± 0.6Vdc |
DC component of output | <100mV |
Power Limitation |
Nominal Input Voltage | 230Vac | |||||||||||||
Input Voltage Range | 180V - 270Vac(NOR) 100V - 270Vac(GEN/WID) | |||||||||||||
High Voltage Disconnect | 280Vac±4% | |||||||||||||
High Line Re-connect | 270Vac±4% | |||||||||||||
Low Voltage Disconnect | 170Vac(NOR) 90Vac(GEN/WID) | |||||||||||||
Low Line Re-connect | 180Vac±4% (NOR) 100Vac±4% (GEN/WID) | |||||||||||||
Nominal Output Voltage | Refer to Charge Algorithm/ Battery Type Setting | |||||||||||||
Nominal Charge Current | 10A@Vi/p<170Vac 20A@Vi/p=230Vac 10A@Vi/p>280Vac | |||||||||||||
Charge current tolerance | ±10% | |||||||||||||
Over Charge Protection | Bat. V ≥30Vdc, Fault, Buzzer alarm | |||||||||||||
Charge Algorithm | Three stage: Boost CC (constant current stage) → Boost CV (constant voltage stage) → Float (constant voltage stage) | |||||||||||||
Battery Type Setting(+/-0.3v/bat) |
| |||||||||||||
Charger current (+/-10%) |
Load(VA) | 100Ah 24VDC(min) | 200AH 24VDC(min) |
300 | 457.5 | 972.2 |
600 | 208.1 | 499.5 |
900 | 140.6 | 262.3 |
1200 | 103 | 178.1 |
1500 | 77.8 | 138.3 |
1800 | 57.6 | 113.2 |
2100 | 49.5 | 100.5 |
2400 | 41.4 | 87.9 |
2700 | 33.2 | 75.3 |
3000 | 28.4 | 62.6 |
Safety Standard | EN60950-1:2006+A1: 2010 EN62040-1-1: 2008 |
EMC Standard | EN62040-2 : 2006C2 |
Operating Temperature Range | 0°Cto 45°C |
Storage temperature | -15°C~ 60°C |
Altitude, operational | Elevation: 0 - 1500 Meters |
Relative humidity | 5% to 95% non-condensing |
Audible Noise | 60dB max |
Cooling | Forced air |
Dimension (L*W*H) | 330mm*268mm*76mm |
Net Weight | 4.9KG |
DC wiring | Double 6 AWG cable for each polarity |
AC input/output | L/N/G:12AWG |