China Hermetic Scroll Type Compressor Industry Water Chiller (KC-005), Find details about China Air Cooling Water Chiller, Air-Cooled Indutrial Water Chiller from Hermetic Scroll Type Compressor Industry Water Chiller (KC-005)
Model | KC-003 | KC-005 | KC-008 | KC-010 | KC-012 | KC-015 | KC-020 | |
Power Supply | 380V/50Hz/3ph (other motor voltage can special customize for the customer) | |||||||
Cooling capacity | kW | 9 | 15.2 | 21.2 | 27.5 | 34.8 | 42.6 | 56.5 |
kcal/h | 7,820 | 13,070 | 18,230 | 23,650 | 29,930 | 36,630 | 48,590 | |
Heating capacity | kW | 10.7 | 18.1 | 25.2 | 32.7 | 41.3 | 50.6 | 67.1 |
kcal/h | 9,200 | 15,530 | 21,650 | 28,120 | 35,500 | 43,510 | 57,720 | |
Power consumption | kW | 2.65 | 4.27 | 6.55 | 8.65 | 11.05 | 13.5 | 17.6 |
Chilled water volume | m3/h | 1.4 | 2.3 | 3.8 | 5 | 6.2 | 7..3 | 9.6 |
compressor | Type | Hermetic scroll / piston | ||||||
Start-up mode | Direct start | |||||||
Output Power | kW | 2.3 | 3.8 | 5.6 | 7.5 | 9.4 | 11.3 | 15 |
Refrigerant | Type | R-22 | ||||||
control method | Temperature-sensitive external pressure equalization expansion valve | |||||||
Filling amount | kg | 2 | 3.6 | 5.1 | 6.5 | 8.2 | 9.6 | 13.3 |
Water side heat exchanger | Type | Shell and tube | ||||||
Pipe diameter | B | PT 1" | PT 1-1/2" | PT 2" | ||||
Air heat exchanger | Type | Internal thread copper tube fin | ||||||
Surface area/row | M2 | 0.62/3R | 0.62/4R | 1.16/3R | 1.16/4R | 1.92/3R | 2.28/3R | 3.06/3R |
Axial fan | Type | Low noise axial flow | ||||||
Air volume | CMM | 65 | 110 | 150 | 195 | 220 | 265 | 390 |
Power | kW | 0.25 | 0.37 | 0.55 | 0.55 | 0.75 | 1.1 | 0.55x2 |
protective device | High and low voltage switch, antifreeze protection, soluble plug / safety valve, overload protection device, coil overheat protector, temperature automatic protection switch, etc. | |||||||
Dimension (mm) | L | 920 | 920 | 1200 | 1200 | 1500 | 1500 | 1860 |
W | 850 | 850 | 1050 | 1050 | 1100 | 1100 | 1220 | |
H | 1300 | 1300 | 1450 | 1450 | 1580 | 1580 | 1700 | |
Weight | kg | 160 | 190 | 300 | 330 | 390 | 430 | 600 |
Model | KCPH-25 | KCPH-30 | KCPH-35 | KCPH-40 | KCPH-45 | KCPH-50 | KCPH-5-60 | |
Power Supply | 380V/50Hz/3ph (other motor voltage can special customize for the customer) | |||||||
Cooling capacity | kW | 65.2 | 84.2 | 97.5 | 113.1 | 125.2 | 139.3 | 167.1 |
kcal/h | 56,070 | 72,410 | 83,850 | 97,260 | 107,660 | 119,790 | 143,700 | |
Heating capacity | kW | 77.5 | 99.6 | 115.2 | 134.3 | 148.5 | 164.9 | 197.2 |
kcal/h | 66,750 | 85,675 | 98,212 | 114,369 | 126,830 | 140,855 | 168,560 | |
Power consumption | kW | 21.7 | 26.8 | 30.5 | 35.2 | 40.9 | 43.3 | 52.9 |
Chilled water volume | m3/h | 12.1 | 14.3 | 16.8 | 19 | 21.5 | 23.8 | 28.5 |
compressor | Type | Fully enclosed scroll/piston | ||||||
Start-up mode | Direct start | |||||||
Output Power | kW | 18.8 | 22.5 | 26.3 | 30 | 33.8 | 37.5 | 45 |
Refrigerant | Type | R-22 | ||||||
control method | Temperature-sensitive external pressure equalization expansion valve | |||||||
Filling amount | kg | 15.8 | 20.4 | 23.6 | 27.8 | 30.3 | 33.6 | 40.2 |
Water side heat exchanger | Type | Shell and tube | ||||||
Pipe diameter | B | PT 2-1/2" | PT 3" | |||||
Air heat exchanger | Type | Internal thread copper tube fin | ||||||
Surface area/row | M2 | 3.80/3R | 4.52/3R | 5.36/3R | 6.08/3R | 6.82/3R | 7.54/3R | 9.02/3R |
Axial fan | Type | |||||||
Air volume | CMM | 440 | 530 | 620 | 760 | 820 | 880 | 1060 |
Power | kW | 0.75x2 | 1.1x2 | 1.1x2 | 1.5x2 | 2.2x2 | 0.75x4 | 1.1x4 |
Protective device | High and low voltage switch, antifreeze protection, soluble plug / safety valve, overload protection device, coil overheat protector, temperature automatic protection switch, etc. | |||||||
Dimension (mm) | L | 1860 | 2250 | 2400 | 2680 | 2800 | 2450 | 2560 |
W | 1220 | 1300 | 1300 | 1350 | 1350 | 2300 | 2300 | |
H | 1700 | 1850 | 1850 | 1900 | 1900 | 1900 | 1900 | |
Weight | kg | 680 | 950 | 1070 | 1150 | 1380 | 1510 | 1680 |
Note: 1. Measuring conditions of above specifications and parameters: inlet temperature of frozen water 12ºC, outlet temperature 7ºC, outdoor ambient temperature DB35 C/WB24ºC; | ||||||||
2. Scope of work: The temperature range of circulating water is from 5 to 35ºC, and the temperature difference between inlet and outlet water is from 3 to 8ºC. Use at Condensation Temperature not higher than 35ºC. 3. The specifications are subject to change without notice. If there are special requirements, please specify the specifications before ordering. | ||||||||
4. The main spare part of equipment Configurationt: Japan Panasonic compressor, USA LKE refrigeration accessories, France Schneider electronic controller, computer control panel; which equipped with high and low voltage switch. For the motor overload protection, lack of reverse phase protection, safety valve and other protective devices; stainless steel water tank coil evaporator and fin condenser . |