China Three Phase UPS High Frequency Modular UPS Power 20kVA to 600kVA for Data Center, Find details about China UPS, Modular UPS from Three Phase UPS High Frequency Modular UPS Power 20kVA to 600kVA for Data Center
Module Model | M25(M20/M30 for optional) |
Module Capacity | 25KVA |
Input/Output Way | three phase in three phase out,three phase in single phase out,single phase in three phase out,single phase in single phase out |
Module Dimension(H×W×D)mm | 133×482×465 |
Weight(kg) | About 21 kg |
Charging module specification | Each module can supply 6 kw charging power |
Input PF | ≥0.99 |
Overload | 135% |
Max Cooling Power | 1187W |
Input Total Harmonic Distortion THDI(%) | ≤3% |
Model | 3RW-150 | 3RW-250 | 3RW-500 | ||
Max Capacity | 150KW | 250KVA | 500KVA | ||
Power Module | Type of power module | M25(M20 for optional) | |||
Mains Input | Input mode | Three Phase Four Wire+ Ground/Single Phase Two Wire+ Ground | |||
Input voltage | 380V/220V±20%,400V/230V±20%,415V/240V±20% | ||||
Input Frequency | 50Hz±10%,60Hz±10% | ||||
Soft Start(Sec.) | 60sec | ||||
Input Total Harmonic Distortion THD(%) | <3% | ||||
Input PF | ≥0.99 | ||||
Input Bypass | Input Voltage | 380V/220V±20%,400V/230V±20%,415V/240V±20% | |||
Input Frequency | 50Hz±4%,60Hz±4% | ||||
Input frequency tracking range | 50Hz±4%,60Hz±4% | ||||
DC Input | Rated Input Voltage | ±384VDC | |||
Input voltage range | ±345V~±440V DC | ||||
Charge Characteristic | Charging current limited | yes | |||
Charging Time | 10 hours(2 hours backup battery capacity) | ||||
Charging Voltage Stability | ±1% | ||||
Output | UPS Power Factor | 0.9 | |||
Output Voltage | 380V/220V AC,400V/230V AC,415V/240V AC | ||||
Output Frequency | 50Hz±4%;Mains overrun or battery mode output is 50Hz±0.2% 60Hz±4%;Mains overrun or battery mode output is 60Hz±0.2% | ||||
Output voltage Stability | 380V/220V±1%(Static);380V/220V±2%(Load change from 0 ~ 100% ) 400V/230V±1%(Static);400V/230V±2%(Load change from 0 ~ 100% ) 415V/240V±1%(Static);415V/240V±2%(Load change from 0 ~ 100% ) | ||||
Output voltage recovery time | <20ms(Load change from 0 - 100% ) | ||||
Overload | Rated Load 125% ,Runs 10min | ||||
Mains to Battery Transfer Time | 0ms | ||||
Bypass to Inverter Transfer Time | <1ms | ||||
Crest Factor | 3 :1 | ||||
Output Total Harmonic Distortion THD(%) | ≤1%(Linear load ) ≤3%(Non Linear Load) | ||||
Efficiency | ≥95%(AC Power Supply) ≥98%(Battery Power Supply) | ||||
Flow Accuracy | ≤5% | ||||
Working Environment | Storage Environment Temperature | -25ºC~60ºC | |||
Working Environment Temperature | -5ºC~40ºC | ||||
Elevation Allowed | ≤1500 Meters | ||||
Humidity | ≤95% (no condensing) | ||||
IP Class | IP31 | ||||
Cooling | Air | ||||
Safety Standard | EN62040-1-1:2003 IEC60950-1:2001 | ||||
Electromagnetic Compatibility Characteristics | EN62040-2:2006 | ||||
Noise | ≤55dB | ||||
Others | Dimension(H×W×D)mm Weight Kg | 600*800*1600 about 180KG | 800*800*2000 about 250KG | 2000*800*2000 about 450KG | |
Structure | 19 inch Standard | ||||
Monitor Management System | UP Supervisor | ||||
RS232,RS485/422 and configure 8pcs dry contacts | Standard | ||||
TCP/IP Expansion CARDS | Standard | ||||
Display | LCD/LED |