China Low Temp Industrial Cooling Machine Bitzer Screw Compressor Water Cooled Chiller, Find details about China Cooling System, Condensing Units from Low Temp Industrial Cooling Machine Bitzer Screw Compressor Water Cooled Chiller
Screw Water Cooling Chiller(Single Unit)Series | |||||||||
Model | MG-350W | MG-390W | MG-460W | MG-480W | MG-540W | MG-580W | MG-600W | MG-700W | |
Capacity | USRT | 100.1 | 109.5 | 136.5 | 136.5 | 153.0 | 180.3 | 172.3 | 180.3 |
Kcal/h | 302720 | 331100 | 397320 | 412800 | 462680 | 502240 | 521160 | 607160 | |
KW | 352 | 385 | 462 | 480 | 538 | 584 | 606 | 706 | |
Power | 3PH-380V-50Hz | ||||||||
Refrigerant | Type | R22 | |||||||
Control | Thermostatic expansion valve | ||||||||
Comperssor | Type | Semi-closed screw type | |||||||
kw Power | 78 | 87 | 104 | 106 | 119 | 128 | 134 | 152 | |
Start | Y-△ | ||||||||
Capacity | 25-50-75-100(%)or25-100(%) | ||||||||
Evaporator | Type | High efficiency copper tube shell and tube type | |||||||
m³/h Flow | 60.3 | 66.0 | 79.2 | 82.3 | 92.2 | 100.1 | 103.9 | 121.0 | |
Inlet/Outlet | DN125 | DN125 | DN125 | DN125 | DN125 | DN150 | DN150 | DN150 | |
Condenser | Type | High efficiency threaded copper tube shell and tube type | |||||||
m³/h Flow | 81.1 | 89.0 | 106.7 | 110.5 | 123.9 | 134.3 | 139.5 | 161.8 | |
Inlet/Outlet | DN125 | DN125 | DN125 | DN125 | DN125 | DN150 | DN150 | DN150 | |
Protection System | Compressor overheat protection, high/low pressure protection,phase missing/sequence protection, flow rate protection, anti-frozen protection. | ||||||||
Dimension | L | 3500 | 3500 | 3500 | 3500 | 3500 | 3800 | 3800 | 3800 |
W | 1200 | 1200 | 1200 | 1200 | 1300 | 1300 | 1300 | 1300 | |
H | 1500 | 1750 | 1750 | 1800 | 1800 | 1800 | 1800 | 1800 | |
Weight | kg | 1500 | 1600 | 1700 | 1750 | 1800 | 1900 | 2000 | 2100 |
Water cooled chillers offer a constant steam of chilled water year around .
Water Cooled Chiller:It is a little complicated to assemble the cooling tower and water pump, need much more water sources, but it supply the better cooling efficiency in the higher ambient working condition compare to air cooled one.Working with water cooling tower, buffer tank, water pumps.
Application