China High Quality Wall Mounted Split Chilled Water Fan Coil Unit, Find details about China Fan Coil, Air Conditioner from High Quality Wall Mounted Split Chilled Water Fan Coil Unit
Model | HFP02 | HFP03 | HFP04 | HFP05 | HFP06 | HFP08 | |||
Power supply | 220V,50Hz,1Ph | ||||||||
Air volume | H | m³/h | 340 | 510 | 680 | 850 | 1020 | 1360 | |
M | 260 | 380 | 515 | 660 | 765 | 1010 | |||
L | 180 | 260 | 340 | 430 | 520 | 700 | |||
Static pressure | Pa | 0 | 0 | 0 | 0 | 0 | 0 | ||
Cooling capacity | TH | H | W | 2100 | 2700 | 4000 | 4500 | 5700 | 7200 |
SH | W | 1600 | 2025 | 3000 | 3375 | 4300 | 5400 | ||
TH | M | W | 1700 | 2214 | 3200 | 3690 | 4600 | 5904 | |
SH | W | 1399 | 1399 | 2200 | 2409 | 3200 | 3926 | ||
TH | L | W | 1300 | 1647 | 2400 | 2745 | 3500 | 4392 | |
SH | W | 700 | 960 | 1500 | 1715 | 2200 | 2710 | ||
Heating capacity | H | W | 3100 | 4050 | 5900 | 6750 | 8500 | 10800 | |
M | W | 2500 | 3219 | 4700 | 5366 | 6800 | 8586 | ||
L | W | 1700 | 2268 | 3300 | 3780 | 4800 | 6048 | ||
Noise | H | dB(A) | 39 | 41 | 42 | 45 | 46 | 47 | |
Power input | H | W | 35 | 40 | 75 | 90 | 125 | 130 | |
Water flow | H | m³/h | 0.36 | 0.46 | 0.71 | 0.77 | 0.98 | 0.93 | |
Pressure drop | kPa | 12 | 14 | 17 | 18 | 23 | 23.5 | ||
Water pipe in/out | ZG1/2'' | ZG1/2'' | ZG1/2'' | ZG1/2'' | ZG1/2'' | ZG1/2'' | |||
Condensing water pipe | ZG1/2'' | ZG1/2'' | ZG1/2'' | ZG1/2'' | ZG1/2'' | ZG1/2'' | |||
Coil | / | Hydrophilic aluminum fin and copper tube | |||||||
Max working pressure | MPa | 1.6 | 1.6 | 1.6 | 1.6 | 1.6 | 1.6 | ||
Dimension | L×W×H | mm | 780×276×202 | 780×276×202 | 950×313×240 | 950×313×240 | 1055×313×240 | 1055×313×240 | |
Net weight | kg | 10 | 10 | 14 | 14 | 16 | 16 |