China 11kv 12kv 15kv 24kv 25kv 33kv 35kv 36kv 40.5kv 42kv Medium Voltage Cold Applied Straight Through Joint for up to 42kv, Find details about China Cold Shrink, in Line from 11kv 12kv 15kv 24kv 25kv 33kv 35kv 36kv 40.5kv 42kv Medium Voltage Cold Applied Straight Through Joint for up to 42kv
Voltage | Cable cores | Cable conductor size (mm2) | Suitable insulation dia. range (mm) |
12/20(24)kV and below | 1-core or 3-core | 25-800 | 15-49 |
18/30(36)kV | 1-core or 3-core | 35-630 | 23-49 |
26/35(40.5)kV | 1-core or 3-core | 50-800 | 31-57 |
Test item | 12/20(24)kV | 18/30(36)kV | 26/35(40.5)kV |
A.C. voltage withstand test | No flashover, no breakdown at 54kV for 5min. | No flashover, no breakdown at 81kV for 5min. | No flashover, no breakdown at 117kV for 5min. |
Partial discharge test | 20kV, <10pC | 30kV, <10pC | 45kV, <10pC |
Heating cycles voltage test | 60 cycles at the temperature of 95-100°C, 30kV | 60 cycles at the temperature of 95-100°C, 45kV | 60 cycles at the temperature of 95-100°C, 65kV |
Impulse voltage withstand test at 95-100°C | No flashover, no breakdown at 10 positive and 10 negative impulses at 125kV | No flashover, no breakdown at 10 positive and 10 negative impulses at 170kV | No flashover, no breakdown at 10 positive and 10 negative impulses at 200kV |
15min, A.C. voltage withstand test | 30kV, 15min. no flashover, no breakdown | 45kV, 15min. no flashover, no breakdown | 65kV, 15min.no flashover, no breakdown |