ASTM Standard Bare Aluminium Conductor Aluminium Alloy Reinforced Acar Conductor

China ASTM Standard Bare Aluminium Conductor Aluminium Alloy Reinforced Acar Conductor, Find details about China Acar, Aluminum Alloy Conductor from ASTM Standard Bare Aluminium Conductor Aluminium Alloy Reinforced Acar Conductor

Model NO.
400MCM,500MCM,550MCM,700MCM,800MCM,850MCM,950MCM
Certification
ISO9001, CCC, BV
Code Name
Aluminum Conductor Alloy Reinforced
Model Number
15+4/18+19/12+7/30+7/24+13/54+7/42+19
OEM or ODM
Yes
Customized
Yes
Usage
Power Transimision
Voltage
0.6-240kv
Standard
ASTM IEC BS En
Trademark
RMJT
Transport Package
Wooden Drum
Specification
1200MCM,1250MCM,1300MCM,1400MCM,1500MCM,1750MCM
Origin
China
HS Code
7614900000
Model NO.
400MCM,500MCM,550MCM,700MCM,800MCM,850MCM,950MCM
Certification
ISO9001, CCC, BV
Code Name
Aluminum Conductor Alloy Reinforced
Model Number
15+4/18+19/12+7/30+7/24+13/54+7/42+19
OEM or ODM
Yes
Customized
Yes
Usage
Power Transimision
Voltage
0.6-240kv
Standard
ASTM IEC BS En
Trademark
RMJT
Transport Package
Wooden Drum
Specification
1200MCM,1250MCM,1300MCM,1400MCM,1500MCM,1750MCM
Origin
China
HS Code
7614900000
ACAR--Aluminum Conductor Aluminum Alloy Reinforced

ASTM Standard Bare Aluminium Conductor Aluminium Alloy Reinforced Acar Conductor


 
APPLICATIONS

Used as bare overhead transmission cable and as primary and secondary distribution cable. A good strength-to-weight ratio makes ACAR applicable where both ampacity and strength are prime considerations in line design; for equal weight, ACAR offers higher strength and ampacity than ACSR.
 
SPECIFICATIONS

ACAR bare conductor meets or exceeds the following ASTM specifications:
• B230 Aluminum 1350-H19 Wire for Electrical Purposes.
• B398 Aluminum-Alloy 6201-T81 Wire for Electrical Purposes.
• B524 Concentric-Lay-Stranded Aluminum Conductors, Aluminum-Alloy Reinforced (ACAR, 1350/6201).
 
CONSTRUCTION

Aluminum 1350-H19 wires, concentrically stranded around aluminum-alloy 6201-T81 core. Although the alloy strands generally comprise the core of the conductor, in some constructions they are distributed in layers throughout the aluminum 1350-H19 strands.

Aluminum Conductors Aluminum Alloy Reinforced                      ASTM  B524
Size 
(kcmil)
StrandingDiameter (ins.)Weight 
Per 1000 ft.
(lbs.)
Rated 
Strength
 (lbs.)
Resistance 
OHMS/1000 ft.
Allowable 
Ampacity
+ (Amps)
Individual WiresComp.
 Cable
DC 
@ 20°C
AC 
@ 75°C
EC620162011350
355.01270.13670.13670.683332.185000.05140.0624519
465.91270.15660.15660.783435.8110000.03920.0477616
503.61270.16280.16280.814471.1119000.03620.0441646
653.11270.18540.18540.927611.0154000.02790.0342760
739.83070.14140.14140.990692.7153000.02400.0296831
739.818190.14140.14140.990691.6188000.02520.0308814
853.73070.15190.15191.063799.3175000.02080.0257907
853.718190.15190.15191.063798.0215000.02180.0268890
927.23070.15830.15831.108868.2190000.01920.0238955
927.218190.15830.15831.108866.7234000.02010.0247936
1024.53070.16640.16641.165959.3209000.01730.02161015
1024.518190.16640.16641.165957.7258000.01820.0225995
1081.03070.17090.17091.1961012.1221000.01640.02051048
1081.018190.17090.17091.1961010.5272000.01720.02131028
1109.03070.17310.17311.2121038.4227000.01600.02001065
1109.018190.17310.17311.2121036.6279000.01680.02081044
1172.03070.17800.17801.2461097.3240000.01520.01901101
1172.018190.17800.17801.2461095.5295000.01590.01981080
1197.03070.17990.17991.2591120.8245000.01480.01871115
1197.018190.17990.17991.2591118.9302000.01560.01941094
1280.03070.18600.18601.3021198.5262000.01390.01751160
1280.01870.18600.18601.3021196.5322000.01460.01821139
1361.042190.14940.14941.3441273.6303000.01330.01681196
1527.042190.15820.15821.4241428.8336000.01180.01511314
1703.042190.16710.16711.5041593.5375000.01060.01371363
1933.042190.17800.17801.6021808.8425000.009360.01231465
2267.042190.19280.19281.7352142.0499000.008060.01081594
2493.072190.16550.16551.8212356.9504000.007220.00991687
2493.054370.16550.16551.8212354.5576000.007430.01011670
+Ampacity based on 75°C conductor temperature, 25°C ambient temperature,with 2 ft./sec. wind in the sun.

Aluminum Conductors Aluminum Alloy Reinforced           IEC 61089
Code 
number
DiameterNo. of 
wires
AreasLinear 
mass
Rated 
strength
D.C 
resistance
WireCond.A1A2A1A2Total
 mmmm  mm2mm2mm2kg/kmkNOhm/km
161.765.28439.737.31746.6 3.851.7896
252.26.64315.211.426.672.8 5.931.1453
402.788.354324.318.342.6116.5 9.250.7158
633.4910.54338.328.767.1183.5 14.380.4545
1004.413.24360.845.6106291.2 22.520.2863
1252.9714.912783.348.6132362.7 27.790.2302
1603.3616.812710762.2169464.2 35.040.1798
2003.7618.812713377.8211580.3 43.130.1439
2504.212112716797.2264725.3 53.920.1151
2503.0421.31819131138269742.2 60.390.1154
3153.3423.430726361.3324892.6 60.520.0916
3153.4223.91819165174339935.1 76.090.0916
4003.7626.330733477.84111133.5 75.190.0721
4003.852718192102214311187.5 95.580.0721
4503.9927.930737587.64631275.2 84.590.0641
4504.0828.618192362494851335.9 107.520.0641
5004.2129.430741797.35141416.9 93.980.0577
5004.3130.118192622775391484.3 119.470.0577
5604.4531.23074671095761586.9 105.260.0515
5603.453154750465.45701571.9 101.540.0516
6303.7133.442194542056601820.0 130.250.0458
6303.7934.124372714176881897.5 160.190.0458
7103.9435.542195122327432051.2 146.780.0407
7104.0236.224373054707752138.4 180.530.0407
8004.1837.642195772618382311.2 165.390.0361
8004.2738.424373445308732409.5 203.410.0361
9004.4339.942196492949422600.1 186.060.0321
9003.6640.254375673889552638.4 199.540.0321
10003.841.8721981621510322849.1 190.940.0289
10003.8542.4543763043210612931.6 221.710.0289
11204.0244.2721991424111553191.0 213.850.0258
11204.0844.9543770548311893283.4 248.320.0258
12504.2546.77219102026912893561.4 238.680.0231
12504.3147.4543778753913273664.5 277.140.0231
14004.549.47219114330214443988.8 267.320.0207