Split Core Current Transformer with 250A/5A, 0.5class

China Split Core Current Transformer with 250A/5A, 0.5class, Find details about China Split Core CT, CT from Split Core Current Transformer with 250A/5A, 0.5class

Model NO.
H-CT005-24D
Insulating Medium
Epoxy Resin
Installation
Extension Type
Magnetic Circuit Structure
Single Stage Type
Voltage Transformation Principle
Electromagnetic Type
Model
H-CT005-24D
Current Ratio
250A/5A
Rate Primary Current
5A
Max Primary Current
300A AC
Secondary Turns
50
Wire Lead
AWG#22
DC Resistance
1.5ohms +/-20% at 20
Frequency
50/60Hz
Brand
E-Power
Manufacturer
Jiaxing Haihan Electron Co.,Ltd
Trademark
E-power
Specification
50x40x30cm
Origin
China
HS Code
85045000
Model NO.
H-CT005-24D
Insulating Medium
Epoxy Resin
Installation
Extension Type
Magnetic Circuit Structure
Single Stage Type
Voltage Transformation Principle
Electromagnetic Type
Model
H-CT005-24D
Current Ratio
250A/5A
Rate Primary Current
5A
Max Primary Current
300A AC
Secondary Turns
50
Wire Lead
AWG#22
DC Resistance
1.5ohms +/-20% at 20
Frequency
50/60Hz
Brand
E-Power
Manufacturer
Jiaxing Haihan Electron Co.,Ltd
Trademark
E-power
Specification
50x40x30cm
Origin
China
HS Code
85045000
The H-CT005 Series are split-core current transformers. The CT can be mounted to existing panels, such as control centers or load centers, to measure or monitor wattage. These current transformer's can be mounted without removing existing cables for easier installation.

1, Electrical Specifications

1), Rated Primary Current(AMP. ) 50/60Hz: 250nom(1~300A max)

2), Turn ratio: Np: Ns=1: 50

3), Current Ratio: 200A/5A

4), D. C. Resistance at 20 º C: 1.5Ω MAX

5), Accuracy @RL=1VA: 0.5%

6), Phase error at rated current range: ≤ 0.5°

7), Operating Temperature Range: -40~70º C

8), Storage Temperature Range: -45~85º C

9), Dielectric Withstanding Voltage(Hi-pot): 3.5KV/1mA/1min

10), Impulse Withstand Voltage: 5KV Peak

11), Insulation Resistance: DC500V/100MΩ Min

2, Applications.
A, Portable/Curret instruments.

B, Sub-metering.

C, Monitor Motor Loads

3, Feature
A, Small size.

B, Low cost

C, High secondary turns.

D, Secure locking hings

E, Full RoHS compliant

F, Mounting easy.
4, Material  List:
NOITEMDESCRIPTIONUL  CardMATERIALNOTE
1COREUU53/SILLICON  STEEL
 
2CASEPP3307E235269PP
 
3BOBBIND202G15@E107536PBT
 
4WIRE2UEWE164502UEW/U
 
5LEAD  WIREUL1007  16AWGE189674PVC80º C  300V
6SOLDER99.3%Sn0.7%Cu/Sn