China Promotional Three Phase Handheld Power Meter Smart Data Logger Flexible Rogowski Coil Current Sensor, Find details about China Smart Meter Quality Analyzer, Power Meter from Promotional Three Phase Handheld Power Meter Smart Data Logger Flexible Rogowski Coil Current Sensor
Connectivity advantages | |
Model | ME435 |
Support Extra sensor | BNC terminal 333mV CT BNC terminal Rogowski coil |
Storage | 1GB SD card(Max 4GB) (save intervals 1mins default) |
Power | 4*AA battery(wroking time: approx 7 hours) Or USB Type-C |
Specification | |||
Model | ME435 | ||
Product component type | Handhold poly-phase power meter | ||
Poles description | 3PH4W 3PH3W 1PH2W (L-N); 1PH2W(L-L);1PH3W(L-L-N) | ||
Device application | Power analysis Energy meter | ||
Input type | External Rogowski coil External CT(333mV only) | ||
Display | 3.5 inch TFT screen display | ||
Sampling rate | 8k samples per second | ||
Harmonic | 52th Max | ||
Mechanical characteristics | |||
Weight | 350g | ||
Dimension | L*W*D:21.5*10*3.5CM |
Characteristics | Description |
Current | Per phase, neutral, and average of 3 phases |
Voltage | L-L, L-N, and average of 3 phases |
Frequency | 45...65 Hz |
Active power | Total and per phase (signed) |
Reactive power | Total and per phase (signed) |
Apparent power | Total and per phase(signed) |
Power factor (True) | Total and per phase 0.000 to 1 (signed) |
Angle | Voltage angle,Current angle |
Current unbalance | Per phase, most unbalanced of 3 phases |
Voltage unbalance | most unbalanced of 3 phases |
Characteristics | Description |
Current | Per phase and average |
Voltage | per phase and average |
Active power | Per phase and total |
Reactive power | Per phase and total |
Apparent power | Per phase and total |
Characteristics | Description |
Current | Per phase and average |
Active, reactive, apparent power | Per phase and Total |
Peak Demand Values | |
Current | Per phase and average |
Active, reactive, apparent power | Per phase and Total |
Record | |
Record interval | 1s to 9999s(default 1min) |
Record format | csv |
Record capacity | Micro SD card 1GB(default) |
Store about 1K Bytes data each time | |
record 2 years (1min & 1GB) | |
Record data | Date&time, Voltage(V),UTHD(%),Current(A),ITHD (%), ITHD3(%),ITHD5(%), ITHD7(%), ITHD11(%), ITHD13(%), ITHD3(A), ITHD5(A), ITHD7(A), ITHD11(A), ITHD13(A) Frequency(Hz), PF(power factor), Active Power(W),Reactive Power(Var),Apparent Power(Va), Active Energy(Wh),Reactive Energy(Varh),Apparent Energy(Vah) Current Demand(A),Current Peak Demand(A)&Date Total Active Power Deamnd(W) Total Active Power Peak Deamnd(W)&Date Total Reactive Power Deamnd(W) Total Reactive Power Peak Deamnd(W)&Date Total Apparent Power Deamnd(W) Total Apparent Power Peak Deamnd(W)&Date |
Characteristics | Description |
Reset | |
Minimum and maximum values | - |
Peak demand values | - |
Current demand calculation method | 1 to 60 minutes |
Power demand calculation method | 1 to 60 minut |
Environmental conditions | ||
Operating temperature | -25ºC to +55ºC | |
Storage temperature | -40ºC to +85ºC | |
Humidity rating | 5 to 95% RH at 50ºC(non-condensing) | |
Pullution degree | 2 | |
Overvoltage category | III,for distribution systems up to 277/480VAC | |
Dielectric withstand | As per IEC61010-1, Doubled insulated front panel display | |
Altitude | 3000m Max | |
IP degree of protection | IP20 conforming to IEC 60629 | |
Colour | White | |
Contractual warranty | 12months | |
EMC | ||
Electrostatic discharge | Level IV(IEC61000-4-2) | |
Immunity to radiated fields | Level III (IEC61000-4-3) | |
Immunity to fast transients | Level IV (IEC61000-4-4) | |
Immunity to surge | Level IV (IEC61000-4-5) | |
Conducted immunity | Level III (IEC61000-4-6) | |
Immunity to power frequency magnetic fields | 0.5mT (IEC61000-4-8) | |
Conducted and radiated emissions | Class B (EN55022 ) | |
Standard compliance | ||
EN 62052-11,EN61557-12,EN 62053-21,EN 62053-22,EN 62053-23,EN 50470-1,EN 50470-3, EN 61010-1,EN 61010-2,EN 61010-031 |
Measurement accuracy | ||
Rated current (5 level selectable) | 100A(0.5% from 10A to 120A) 600A(0.5% from 10A to 720A) 1000A(0.5% from 10A to 1200A) 3000A(0.5% from 30A to 3600A) 6000A(0.5% from 60A to 7200A) | |
Rogwoski coil connect setting | 100A | MRC-16 |
600A | MRC-36 | |
1000A | Y-FCT-200 or Y-FCT-350 or NRC-100 | |
3000A | NRC-150 or Y-FCT-510 | |
6000A | NRC-200 or Y-FCT-800 | |
CTs connect setting | Primary setting: | from 1A to 999999A |
Secondary setting: | from 0.001mV to 333mV | |
Voltage | 0.2% from 60V to 500V | |
Power factor | ±0.005 | |
Active/Apparent Power | IEC62053-22 Class 0.5 | |
Reactive power | IEC62053-21 Class 2 | |
Frequency | 0.01% from 45 to 65Hz | |
Active energy | IEC62053-22 Class 0.5s | |
Reactive energy | IEC62053-21 Class 2 | |
Input-current characteristics | ||
Primary current range | 100A 0.5A to 120A 600A 0.5A to 720A 1kA 1A to 1200A 3kA 3A to 3600A 6kA 6A to 7200A | |
Measurement input range | 1/225mV-333mV | |
Permissible overload | 600mV for 10s/hours | |
Power Supply | ||
Power | 4*AA battery(working time: approx. 7hours) | |
USB Type-C | ||
power consumption | ||
Screen Backlight On | 1100mW | |
Screen Backlight Off | 900mW | |
Wire diameter for terminals | ||
Current input | BNC connector | |
Voltage input | Banana plug | |
DC power supply | DC 5.5*2.1 plug |
Port number | Port name | Port function | Remarks |
1 | IA | A-phase current input | Current input |
2 | IB | B-phase current input | |
3 | IC | C-phase current input | |
4 | UN | N-phase voltage input | Voltage input |
5 | UC | C-phase voltage input | |
6 | UB | B-phase voltage input | |
7 | UA | A-phase voltage input | |
8 | Power | USB Type-C | USB Type-C |
9 | Micro SD | SD card | Take out(in) SD card |
Accessories | |
Voltage wires | 4pcs voltage clamp wires with banana plug (2 meters,1.5mm²) |
Adaptor | 85-265 AC to 9V DC adaptor |
SD card | 1GB |
Remark | Rogowski coil and AA battery not included |
Function | Factory settings |
Wiring | 3PH4W; VT Direction connection; 3 Rcoils on I1, I2, and I3 50Hz |
Ratio | Rcoil FSA=1000A VT ratio=NA |
SD Card | Switch=ENABLE Period=60s |
Harmonic | H1=3 H2=5 H3=7 H4=9 H5=11 |
Password(Low) | 1000 |
Date/Time | - |
BackLight | Switch=ON Period=60s Backlight=5 |
Demand | Method: sliding block; Interval: 15 minutes |