China Vacuum Contactor, Find details about China Vacuum Contactor, Jcz5-12kv from Vacuum Contactor
By summarizing the user's experience for many years and combining with the company's rich design experience, the company redesigned the original product, which greatly improved the appearance, performance index, reliability and ease of use and maintenance of the product. It can be reliably used for the switching of capacitive load (ac-6a for transformer and ac-6b for capacitor bank).
Users are welcome to choose to use.
Product features
Main circuit
The integral frame structure is adopted to ensure the insulation and provide sufficient mechanical strength at the same time.
Vacuum switch tube is made by domestic famous manufacturers. Mature technology, reliable quality and good market reputation
The 630A current level adopts double moving end connection of end face and conductive clamp, which makes it more reliable with low resistance and low temperature rise.
The conducting bar is beautiful and durable, and the upper end has two modes of horizontal connection or vertical connection, which is convenient for users.
Electromagnetic system
The unique built-in large capacity sealed auxiliary switch in similar products greatly improves the reliability and safety of auxiliary switch.
It adopts double coil electromagnetic system, and the matching characteristic with action force is better than that of single coil.
The operation structure is optimized to reduce the starting power and holding power of the coil, so the temperature rise is low, the service life is long and the reliability is more.
The limiting buffer is set at the opening limit position of the movable armature to eliminate the hidden trouble caused by the excessive rebound amplitude of the opening. At the same time, the auxiliary switch head also uses buffer to reduce the action impact force and improve the reliability of the auxiliary switch.
Action structure
The flexible support of the rotating shaft, no clamping force and small axial movement improve the action performance and consistency.
The reasonable action mechanism ensures the axial movement coaxiality of the vacuum tube moving conducting rod, and improves the performance and reliability of the contactor.
The contact pressure of the main contact is enhanced to improve the electrical performance and action characteristics. The index is better than similar products.
The mechanical retaining device is self-contained, with reasonable structure and more reliable use.
Easy to use and maintain
The control circuit terminal has function mark to prevent wiring error. According to the needs of users, the terminal can be installed on the two sides or front of the machine to facilitate wiring. The number of auxiliary contacts can be combined according to the use require.
Description | Unit | 12/160 | 12/250 | 12/400 | 12/630 | ||||||
Rated voltage(Ur) | kV | 12 | |||||||||
Rated current(Ie) | A | 160 | 250 | 400 | 630 | ||||||
Rated switch-in cap.(Im) | kA | 1.6 | 2.5 | 4 | 6.3 | ||||||
Rated switch-off cap.(Ic) | kA | 1.28 | 2 | 3.2 | 5.04 | ||||||
Rated overload withstand period and current | kA/s | 2.4/1 | 3.75/1 | 6/1 | 9.45/1 | ||||||
Rated short-time withstand current(Ik) | kA | 1.6 | 2.5 | 4 | 6.3 | ||||||
Rated peak value withstand current(Ip) | kA | 4 | 6.25 | 10 | 16 | ||||||
Rated short-circuit retaining period(tk) | s | 4 | |||||||||
Rated insulation level | Rated WF Withstand Voltage | Fracture | kV | 42 | |||||||
Between phases | kV | 42 | |||||||||
To earth | kV | 42 | |||||||||
Rated lightning withstand voltge (Peak vvalue) | Fracture | kV | 75 | ||||||||
Between phases | kV | 75 | |||||||||
To earth | kV | 75 | |||||||||
Master circuit contact resistance | μΩ | ≤200 | ≤200 | ≤200 | ≤150 | ||||||
Rated operation frequency | time/h | 300 | |||||||||
Mechanical locking operation frequency | time/h | 60 | |||||||||
Mechanical withstand life(mechanical life) | 10000 times | 100(For mechanical locking model. Exchange locking device per 300,000 times) | |||||||||
Electric withstand life (Electric life) | AC3 | 10000 times | 25(Close current 6Ie Open current 1Ie) | ||||||||
AC4 | 10000 times | 6(Close current 6Ie open current6Ie) |