Container 800kw 1000kVA Black Start Emergency Diesel Generator Set

China Container 800kw 1000kVA Black Start Emergency Diesel Generator Set, Find details about China Emergency Diesel Generator, 800kw Diesel Genset from Container 800kw 1000kVA Black Start Emergency Diesel Generator Set

Model NO.
HGM1100
Conditions of Use
Land Use
Usage
Common Units
Landuse Type of Unit
Low Noise
Excitation Mode
AC Rotating Exciter
Engine Model
Googol Ptaa1780g7 Engine
Alternator Model
Meccalte Eco43-1ln/4
Controller Model
Deep Sea, Comp, Datakom , etc
Voltages
Low Voltage 380V , 400V ,Adjustable
Certificates
CE,ISO.BV,GOST,TUV,SGS,etc
Warranty
1 Year or 1000 Working Hours
Prime Power
800kw 1000kVA
Canopy Types
Silent ,Container,Trailer ,etc
Option
ATS,Circuit Breaker,Parallel, Remote Controlpanels
Lowest Fuel Consumption Ratio
198.40g/Kw.Hr
Trademark
HONNY
Transport Package
Poly Plastic Firm/ Wooden Package
Specification
ISO8528, CE, GOST, etc
Origin
Guangdong, China
HS Code
8502131000
Model NO.
HGM1100
Conditions of Use
Land Use
Usage
Common Units
Landuse Type of Unit
Low Noise
Excitation Mode
AC Rotating Exciter
Engine Model
Googol Ptaa1780g7 Engine
Alternator Model
Meccalte Eco43-1ln/4
Controller Model
Deep Sea, Comp, Datakom , etc
Voltages
Low Voltage 380V , 400V ,Adjustable
Certificates
CE,ISO.BV,GOST,TUV,SGS,etc
Warranty
1 Year or 1000 Working Hours
Prime Power
800kw 1000kVA
Canopy Types
Silent ,Container,Trailer ,etc
Option
ATS,Circuit Breaker,Parallel, Remote Controlpanels
Lowest Fuel Consumption Ratio
198.40g/Kw.Hr
Trademark
HONNY
Transport Package
Poly Plastic Firm/ Wooden Package
Specification
ISO8528, CE, GOST, etc
Origin
Guangdong, China
HS Code
8502131000

Container 800kw 1000kVA Black Start Emergency Diesel Generator Set

Container 800kW 1000kVA Black Start Emergency Diesel Generator set


Performance Feature
Engine and alternator shall be mounted on a same frame steel skid.
Built-in damper for anti-vibration.
World most famous brand diesel engine.
World famous brand AC alternator.
Advanced and reliable control module<o: P>
Full range protection function and alarm shutdown feature.

Alternator Feature
Brush-less, 4 poles, rotation magnet.
IP21-23(NEMA1) enclosure is standard for all industrial alternators.
The insulation system is Class H
Simple installation and maintenance, with easy access to terminals, rotating diodes and coupling bolts.
Wide range of flange adaptors and single bearing disc coupling.
Standard 2/3 pitch windings avoid excessive neutral currents
AVR auto voltage regulator, auto exciter, auto adjustment

Standard Accessory
Common steel base frame, Damper, Exhaust silencer, Flexible pipe, Battery and connecting wires, Operation manual and document.

Optional Accessory
Engine coolant and oil heater, Alternator space heater, Cooling for heat exchanger, Control system with RS232/485 communication interface, Battery charger by main supply, Fuel-water separator, Daily fuel tank, ATS & paralleling system, and Moving Trailer.

Silent Canopy Description
Standard Accessory:
Steel Weatherproof Canopy
Built In Fuel Tank For 8 Hours Running
Built In Control Panel
Built In Start Battery
Power Output Rapid Insert
Windows for Looking
Air Louver for Intake & Exhaust
Exhaust Gas Silencer
Soundproof Type

Quality Warranty Period:
All equipment is guaranteed for a period of 1000 hours running or 12 months from the date when the generator set has been delivered from the factory.

ATS SYSTEM
For emergency power usage in building, Auto transfer switch (ATS) is essential. ATS can automatic transfer load from Mains power supplying to Emergency power. In normal, when the Main power supplying failure or voltage drop below 80% of normal voltage, ATS will auto start Emergency generator set after a preset time of 0-10 sec (adjustable according to the users). Once generator reach at rated speed, the ATS will transfer the load to emergency generator sets automatically
Generator ModelHGM1100
Genset Prime Power800kW/1000kVA
 
Engine Ratings:
Engine Speed(RPM)1500
Generator set Frequency(Hz)50
Engine Standby Power (LTP)(kW)931 
Engine Prime Power (PRP)(kW)847 
Engine Continuous Power (COP)(kW)677 
Single Fan Power(kW)7.5
Single Fan Consumption(kW)7
Quantity of Fan(Sets)4
All Fan Consumption(kW)28
Engine Net Standby Output  (LTP)(kW)931 
Engine Net Prime Output  (PRP)(kW)847 
Engine Net Continuous Output  (COP)(kW)677 
BMEP for Standby Output(bar)25.48 
BMEP for Prime Output (bar)23.16 
BMEP for Continuous Output (bar)18.52 
Typical Generation Standby Output (kVA)1100
Typical Generation Standby Output (kW)880
Typical Generation Prime Output (kVA)1000
Typical Generation Prime Output (kW)800
Typical Generation Continuous Output (kVA)800
Typical Generation Continuous Output (kW)640
Typical  Alternator Efficiency 94.5%
Power Factor 0.8
Speed droop (static) elect. Gov. 0-5%
Governing standards to ISO 8528 Parts 1 and 5 G3
Max. step load acceptance, 1st step(% Prime Output) 55%
 
Basic Performance Datasheet
Aspiration Type Turbocharger, air-air after-cooler
Injection Type Direct Injection
Configuration Vee
No. of Cylinders 16
Displacement(liters)19.2
Bore(mm)128
Stroke(mm)142
Compression Ratio 14.6:1
Piston Speed(m/s)7.10
Rotation Direction (from flywheel) Counter Clockwise
Number of Flywheel Teeth 204
Flywheel House Size SAE0-18
 
Lubrication System
Lube Oil Specification AFI-CF4
Oil Capacity( Liters)72
Max. Permissible Oil Temperature (°C)110
Low Oil Pressure Warning (kPa)200
Low Oil Pressure Shutdown (kPa)160
Oil consumption (as % of fuel consumption) ≤0.5
 
Cooling System
Coolant Capacity for Engine( Liters)26
Max. Permissible Temperature (°C)90
Max. Coolant Warning Temperature (°C)95
Max. Coolant Shutdown Temperature (°C)105
Thermostat Open Temperature (°C)71
Radiator Cooling Flow(m³/min)1320
Flow of Coolant pump(m³/h)51.96 
Heat dissipation (engine radiator)(kW)446 
Heat dissipation (convection)(kW)68 
Radiator Model PSCN7002
 
Fuel System
Governor Type Electrical Control
Engine Output at generator set prime output(kW)847 
Fuel Consumption at 25% of generator set prime output(l/h)56.76 
Fuel Consumption at 50% of generator set prime output(l/h)102.32 
Fuel Consumption at 75% of generator set prime output(l/h)150.74 
Fuel Consumption at 100% of generator set prime output(l/h)201.67 
Lowest Fuel Consumption Ratiog/kW.hr198.40 
 
Intake & Exhaust System(On Standby Output)
Combustion Air Consumption(m³/min)69.84 
Max. Intake Restriction(Kpa)5
Max. Exhaust Temperature(Before Turbo)(°C)696
Max. Exhaust Temperature(After Turbo)(°C)505
Max. Exhaust Back Pressure(Kpa)5
Exhaust Gas Flow(m³/min)85.36 
Exhaust Flange Diameter(mm)2*150
 
Electrical System
Charging Alternator Voltage(V)28
Charging Alternator Capacity(A)55
Starting Voltage(V)24
Starting Motor Capacity(kW)1*9
Minimum Battery Capacity(Ah)2*200
Minimum Temperature for Unaided Cold Start(C)10
 
Engine Dimension
Length(mm)1950
Width(mm)1389
Height(mm)1162
Engine Dry Weight w/o Cooling System(kg)2250
Note:
1,All engine parameters are in accordance with ISO3046, ISO8528
2,All engine parameters are based on 25°C / 100kPa environment condition
3,No power decrease with below 40ºC environment temperature and 1500 meter altitude
4,More than 40ºCand 1500m above sea level , decrease 2% per 10ºC , and 4% per 300m
5,At calorific value 42700 kJ/kg + 5%, density 0,835 kg/dm3 , temperature 280 K
6,Above data is only the testing data in our laboratory, it can't used to be the data on all contract
 
 
AlternatorAlternator modelMGA400-800-4SF
Rating Voltage(V)400/230V,380/220V adjustable
Rating Capacity(KW/KVA)800/1000
Eff.%95.1%
Power Factor0.8
Exciting typeBrushless self-exciter AVR
Voltage regulation±1%
No. of  Phase3 phase 4 wire
Enclosure ClassIP21
Class of InsulationH
 
Standard Accessory Battery4X150AH 12V
Battery Wires1 set
Flexible Pipe2*6 inch
Industry Silencer2*6 inch
Optional AccessoryVCB Breaker Panel1600A
Fuel Tank1000 Liter
Fuel-water Separator  
HeaterCoolant & Oil Heater

For more products, please visit our showroom honnydg.en.made-in-china.com

Container 800kw 1000kVA Black Start Emergency Diesel Generator Set
Container 800kw 1000kVA Black Start Emergency Diesel Generator Set
Container 800kw 1000kVA Black Start Emergency Diesel Generator Set
Container 800kw 1000kVA Black Start Emergency Diesel Generator Set
Container 800kw 1000kVA Black Start Emergency Diesel Generator Set
Container 800kw 1000kVA Black Start Emergency Diesel Generator Set
Container 800kw 1000kVA Black Start Emergency Diesel Generator Set
Container 800kw 1000kVA Black Start Emergency Diesel Generator Set
Container 800kw 1000kVA Black Start Emergency Diesel Generator Set
Container 800kw 1000kVA Black Start Emergency Diesel Generator Set
Container 800kw 1000kVA Black Start Emergency Diesel Generator Set
For more details, please visit our website honnydg.en.made-in-china.com