Air puffer switch Auto recloser ZW32-12

China Air puffer switch  Auto recloser ZW32-12, Find details about China Switchgear Components, Outdoor VCB from Air puffer switch  Auto recloser ZW32-12

Poles Number
1-3
Type
Circuit Breaker
Function
Circuit-Breaker Failure Protection
Certification
ISO9001-2000
Poles Number
1-3
Type
Circuit Breaker
Function
Circuit-Breaker Failure Protection
Certification
ISO9001-2000

 Air puffer switch  Auto recloser ZW32-12 

             

l  ZW32 series high voltage out door circuit breaker can be used for 50HZ 40. 5kv outdoor high voltage electrical equipment.

l  Attached spring operating structure and electromagnet operating structure can manipulate electric opening and closing in a distance, or accumulate energy for manual operation.

l  The design performance strictly sticks to our national standard GB1984-89 for high voltage alternating current vacuum circuit breaker, and meet the requirements of International Electro technical Commission (IEC) IEC-56 for high voltage alternating current vacuum circuit breaker.

l  Mainly used in controlling and protection of outdoor power transmission and transformation system of 35kv, also in normal operation and short-circuit protection for all kinds of power grid and frequent operation place.

l  Highest system voltages Um related to the rated voltages are defined in IEC 60071-1.

l  These series of VCBs are ceramic pillar type.

l  Vacuum interrupter is installed in upper part of ceramic insulator.

l  It has characteristics of well tightness and high temperature endurance, non-combustion and non-exploration, easy mounting, anti-aging and long service life.  

 

Ambient condition

1. Altitude: up to 2500m

2. Ambient temperature: max +50°C min -35°C

3. Maximum daily average temperature °C 40

4. Wind pressure: ≤700Pa (equals to wind speed 37.5m/s)

5. Earthquake intensity: ≤8 degree (as per terms UBN-97: Zone 1)

6. Air contamination degree:  degree

7. Max daily temperature variation: ≤25°C

8. Maximum solar radiation: ≤1035 W/m²

9. Isokeraunic level: ≤70

10. Average rainfall annually: ≤1400 mm/a

 

Mechanical Data

Main Technical Data

 

 

Rated voltage                                                             

kv

36

Rated frequency                                                         

Hz

50

Rated lighting impulse withstand voltage

kv

185

Rated short-time power frequency withstand voltage(dry)    

kv

95

Rated short-time power frequency withstand voltage(humid)    

kv

80

Rated current                                                             

A

1250

1600

2000

Rated short-circuit breaking current                              

kA

20

25

31.5

Rated short-circuit making current                               

kA

50

63

80

Rated short-time withstand current                         

kA

20

25

31.5

Rated peak withstand current                               

kA

50

63

80

Rated operations of short-circuit breaking current interruption   

times

20

Full opening time

s

0.1

Rated operating sequence                                            

 

0-0.3s-CO-180s -CO

Rated duration of short-circuit                              

s

4

Rated single capacitor bank breaking current                  

A

400

Contact erosion limit                                       

mm

3

Mechanical life                                           

times

20000

Weight

kg

1100




Air puffer switch  Auto recloser ZW32-12
Air puffer switch  Auto recloser ZW32-12
Air puffer switch  Auto recloser ZW32-12
Air puffer switch  Auto recloser ZW32-12
Air puffer switch  Auto recloser ZW32-12
Air puffer switch  Auto recloser ZW32-12
Air puffer switch  Auto recloser ZW32-12
Air puffer switch  Auto recloser ZW32-12Air puffer switch  Auto recloser ZW32-12