Recloser Control

China Recloser Control, Find details about China Control, Recloser from Recloser Control

Model NO.
CHK4
Condition
New
Customized
Customized
Material
Stainless Steel
Trademark
HEMG
Transport Package
Carton with Wooden
Specification
15KV/27KV/38KV, 50HZ/60HZ,
Origin
China
Model NO.
CHK4
Condition
New
Customized
Customized
Material
Stainless Steel
Trademark
HEMG
Transport Package
Carton with Wooden
Specification
15KV/27KV/38KV, 50HZ/60HZ,
Origin
China
7.Intelligent Controller Communications Cubicle
The product is supplied complete with an CHK4(T/S) series controller to achieve the various functions Including of measurement, protection, control and communication requirements. The controller can achieve the functions are as follows:
CHK4 CONTROLS FUNCTIONS AND CHARACTERISTICS
1.Control panel is operated by manual or PC
2.Remote control is by through SCADA
3.Total time maximum opening3 cycles/50ms for 60hz
4.Re-close time and programming stepProgrammable
5.Independent calibration groups, minimum
Automatic Protection Group Selection is used to change the protection, group depending on the direction of power flow. This allows the re-closer to be correctly graded with devices downstream regardless of the power flow direction.
3/4
each of which can be configured
with completely separate protection characteristics with different inverse time curves and setting currents. The number of protection groups available to the operator can be configured, thereby restricting or enabling access to protection settings as required
6Operation with dead line With battery bank if AC power is lost
  1. Back up battery bank power for 48hours without charging
  2. 100times operation within 48hours
  3. Battery bank is charged by intelligent charger in controller cabinet from outside PT
7.It is with Control and microprocessor protection
8.Selection of number of operations fast0-4 from IEC curve
9.Selection of number of slow operations0-4 from IEC curve
10.Selection of number of lock operations 1-4 IEC curve
11.Buttons with indicators (LED's). Applicable control with microprocessor relay
12.Modification of curves by time (dial) tap in current and adding time-definiteFOR IEC 5 Curve and IEEE 3 curve
13.Minimum programmable LED's. It applies to control with microprocessor relay.4 (u)
14.Automatic Re-closer locking
15.Remote operation lock
16.Levels of access codes to configuration
17.Fault recorder
18.FOR PROTECTION CURRENT TRANSFORMERS:
18.1Relation For Phases1000/600/400/200/100:1/5
18.1.1Precision for protection: +/- 5%
18.1.2Material of the bushingsPolymer
18.2Relation for Ground200/100/50:1/5(POTION)
18.2.1Precision for protection5P
18.2.2Material of the bushingPolymer
19.FEATURES OF THE ELECTRONIC CONTROL
19.1Type of installation: Outdoor for mounting substation or pole
19.2Degree of protection: IP65/IP54
19.3AccessFront
19.4Memory type: Non-volatile
20.THE CONTROL UNIT SHOULD INCLUDE:
20.1Liquid crystal displayLCD(3"x1"/77mmx27mm)
20.2Membrane keyboard
20.3LED's for indication of the State of the control, Re-closer (open/close) and the shooting conditions
21.OPERATION BUTTONS TO ENABLE / DISABLE THE FOLLOWING FUNCTIONS:
21.1Ground-fault trip
21.2Automatic Re-closer
21.3Remote control
21.4Buttons for closure and manual (local) tripping of the unit
21.5Function of hot line tag to configurable buttons for change of setting and activation of control logic or blocking local group.
22PROTECTION FUNCTIONS
22.1Instantaneous over current for phase, neutral and negative sequence50 relays PGQ/50N
22.2Timed over current for phase, neutral and negative sequence51 relays PGQ/51N
22.3Sequence Components
Negative, positive and zero phase sequence currents and voltages can be
monitored and logged.
In addition, the negative phase sequence current protection can be used for
detection of low-level phase-to-phase faults in the presence of high level three phase
loads. Inverse Time, Definite Time and Instantaneous operation is available.
Setting current range: 10 - 1260 A
22.4Sequence CoordinationSequence Coordination allows a recloser to coordinate it's trip sequence with
another recloser downstream
22.5Auto-re-closerRelay 79 (sequence 1,2,3,4)
Operating Sequence
Reclose times are individually selectable. The operating sequence is defined by:
O - 1st rt - CO - 2nd rt - CO - 3rd rt - CO
where rt = reclose time.
where O = open.
where C = close.
1st Reclose Time range: 0.2 - 180 sec
2nd Reclose Time range: 2.0 - 180 sec
3rd Reclose Time range: 2.0 - 180 sec
Timing resolution: 0.1 sec
Recovery/ Reset Time: 0.1 - 180 sec
Sequence Reset Timing resolution: 1 sec
22.6Trips to LockoutOvercurrent and fault trips to lockout are selectable between 1 and 4. A separate
setting is available for Sensitive Earth Fault and Negative Phase Sequence.
22.7Loss of phase
Loss of phase protection trips the re-closer if phase-earth voltage on one or two, phases falls below a set voltage threshold for a set length of time.
Threshold voltage range: 2 - 15kV
Voltage resolution: 1V
Time range: 0.1 - 100 sec
Time resolution: 0.1 sec
22.8Live load blocking
Live load blocking prevents a re-closer from closing if any of the load side terminals
are live.
Live Load Threshold Voltage range: 2 - 15kV
22.9Dead lockout
 
Dead lockout prevents a reclose unless one or more of the source side or load side
terminals are live. If all terminals are dead, then the controller goes to lockout
22.10Envelope and low frequency
This feature trips the re-closer when the system frequency exceeds the under and
over frequency trip threshold values. Frequency tripping range: 45 - 65 Hz
Relay 81
Frequency calculation: Once per cycle over a two-cycle period
Number of under/over frequency cycles before tripping: 2 - 1000
Accuracy: ±0.05Hz
22.11Over voltageRelay 59
22.12Low voltageRelay 27
22.13DistanceRelay 21
22.14Directional blocking
Directional protection
 
67 relay PGQ/67N
a protection feature that restricts tripping on faults to a
designated side of the re-closer. It prevents nuisance tripping if network
conditions are causing "false" earth faults. In radial systems, Directional Blocking
prevents nuisance tripping by blocking faults in the source direction and only responding to faults in the load direction.
Distinct protection for faults in the forward and reverse direction. A forward fault may
use a different time-current curve and settings to a reverse fault (i.e. these are
individually selectable). Both the forward protection and reverse protection are
operating at the same time. This is an additional protection feature
22.15Cold load picks up(OPTIONAL)
Cold load pick-up allows for a loss of diversity when a load has been without supply
for a period.
Multiplier range: 1 - 5
Multiplier resolution: 0.1
Time Constant range: 1 - 480 min
Time constant resolution: 1 min
22.16High impedance/conductor broken failureOptional
22.17harmonicoptional
22.18Protection time-current curves: 1. IEC/IEEE ,2.ANSI(OPETIONAL)
3.(optional Non Standard Inverse Time Curves)
IEC 60255 CURVESInverse,Very Inverse and Extremely Inverse.
IEEE C37.122Moderately Inverse,Very Inverse and Extremely Inverse.
22.19Instantaneous protection
Instantaneous protection works by tripping the re-closer if the line current exceeds
the Instantaneous Multiplier x Setting Current.
Multiplier range: 1 - 30
Resolution of setting: 0.1
Max effective setting: 12.5kA
22.20Definite time protection
Definite Time is an alternative to Inverse Time protection. It works by tripping the
Re-closer at a fixed time after pick-up.
Setting current range: 10 - 1260A
Definite time resolution: 0.1 sec
Definite time range: 0.01 - 100 sec
Setting current resolution: 1A
22.21Sensitive Earth Fault (SEF)SEF trip Current Range:         5A-25A
MIN 5A(to Ground)/MIN25A(to phases)
SEF operating time range:         0.1-999sec
SEF trip current setting resolution:         1A
SEF operating time resolution:         0.1S
22.22Under / Over Voltage Protection
When selected, and a nominal Phase to Earth System operating voltage is set, the UOV Protection works within a defined threshold above and below the specified
voltage.
Under Voltage Lower Threshold Range:
50% - 88%
Over Voltage Upper Threshold Range: 112% - 150%
Trip After X Secs Range: 0 - 300 Seconds
Phase Logic
1.When ALL phases deviate beyond thresholds
2.When ANY phase voltage deviates beyond the thresholds
3.When the numerical AVERAGE of all phase Voltages deviates beyond the threshold.
22.23Inrush restraint
Inrush restraint raises the phase and earth threshold currents for a short period of
time to allow for short duration inrush currents when closing onto a load.
Multiplier range: 1 - 30
Multiplier resolution: 0.1
Time range: 0.05 - 30 sec
Time resolution: 0.05 sec
23MEASUREMENT FUNCTIONS 
23.1Voltage By phase,line and neutral
23.2Current (0-1250A)By phase ,line and neutral
23.3Power (Active and reactive)By phase and line
23.4Energy (Active and reactive)By phase and line
23.5Power factor By phase and line
22.6Load profile registry (Amperage, voltage, power,energy  power factor)1.registry Every 15 minutes
2.Optional adjustable (0-60MIN)
24ADDITIONAL  FUNCTIONS:
24.1Events Registrar
  1. 216 records of events
  2. 216 records of remote control
  3. 216 records of events of failure
  4. 45 records for fault waveform(15before and 30 after)
  5. 216 records of history events
24.2The battery status monitor
24.3Inputs and outputs programmable by the user
24.4Native protocol Mod-bus/DNP3.0 profile
25COMMUNICATION PORTS:
25.1RS232 for Setting of communication protocols and Maintain of the control by PC
25.2RJ45 for Setting, Program and Receiving of control BY PC(OPTIONA)
25.3RS-232 for communicationWith DNP 3.0 /Mod-bus interface
25.4RS-485 for communicationWith DNP 3.0 /Mod-bus interface
25.5RJ45 for remote communicationWith DNP 3.0/IEC61850 standard interface
25.6GRPS or Bluetooth or WI-FI or radio to connect with laptop
25.7Unit with 1 or 2 Fiber optic port and 3 RJ45 Ethernet communication (option)
25.8Protocol IEC60870-5-104/IEC60870-5-101 /DNP3.0/MODBUS/IEC61850(option)
25.9COMMUNICATION BETWEEN RELAYS(OPTIONAL)
26Supply voltage: 110/125/220/220VAC/DC(OPTIONAL)
27Frequency: 50Hz/60 Hz(OPTIONAL)
28Back-up batteries: sealed free maintance ,rechargeable in control box ,monitor of power on diagnostic and continuous self monitoring 1.2AH/7AH/17AH/24AH(OPTIONAL)
2.2x12V=24VDC or 4x12v=48VDC
3.48hours with 20w if loss of power
29Life years of recloser 10years
Life years of battery 5 years
30Integrated battery charger/monitor is included
3112VDC integrated auxiliary output to power a radio or moden another device for remote or local data transmission
32Included of Heating resistors
33Included of Control cable  15M and power cable from PT (option)
34Included of Setting ,Programming and Receiving software
35Including of ac lamps and heaters of moisture contol
36Including of electricnic magnetic lock for control box
37Microprocessor realy in the front will be with IP20 to avoid of dust ,insert ,air contaminats ,high humidity and vibration.
38Main Protection Function Schematic
  
 
 
     
 
Main protection function schematic diagram
Recloser Control
 
 MANIN MENU AS FOLLOWING:
Recloser Control