ITEM 1 : SECTIONALIZERS 1 POLE 15 KV PROGRAMMABLE | ||||
ITEM | SPECIFICATIONS | UNIT | REQUIRED | GUARANTEED |
1 | GENERAL DATA | |||
1.01 | COUNTRY OF ORIGIN. | INDICATE | CHINA | |
1.02 | MANUFACTURER | INDICATE | HEMG | |
1.03 | MODEL. | INDICATE | FDK-15KV | |
1.04 | STANDARD OF MANUFACTURE | ANSI C37.63 or IEC | ANSI C37.63/IEC | |
1.05 | TYPE | OUTDOOR | OUTDOOR | |
1.06 | SYSTEM | 1 POLE ( SINGLE POLE) | SINGLE POLE | |
1.07 | TYPE OF OPERATION | AUTOMATYC AND MANUAL | AUTOMATIC AND MANUAL | |
1.08 | ALITUDE OF OPERATION | MOSL | FROM 500 TO 4500 | UP TO 4500M |
1.09 | TYPE OF PERFORMANCE ACCORDING TO CONFIGURATION (1 POLE, TWO POLE OR 3 POLE) | AUTOMATYC AND MANUAL | AUTOMATIC AND MANUAL | |
2 | NOMINAL DATA BASE SUPPORT OF SECTIONALIZER | |||
2.01 | NOMINAL FRECUENCY. | 60 HZ | 60HZ | |
2.02 | VOLTAGE CHARACTERISTICS. | |||
NOMINAL VOLTAGE OF THE SYSTEM. | KV | 10, 13.2, 13.8 | 10..13.2.13.8 | |
MAXIMUM VOLTAGE OF THE SYSTEM. | KV | 15 | 15 | |
2.03 | INSULATION LEVEL. | |||
NOMINAL VOLTAGE | KV | 15 | 15 | |
WITHSTAND VOLTAGE INDUSTRIAL FREQUENCY 1 MINUTE | KVp | 50 | 50 | |
WITHSTAND VOLTAGE IMPULSE 1.2/50 us | KVp | 125 | 125 | |
LEAKAGE DISTANCE | MM/KV | 25 | 25 | |
2.04 | CURRENT CHARACTERISTICS | |||
NOMINAL CURRENT | A | 100 OR MORE | 100A | |
CURRENT OF NOMINAL SYMMETRICAL INTERRUPTION. | KA | 4 OR MORE | 8 | |
PEAK VALUE OF FAULT CURRENT. | KA | 10 OR MORE | 10 | |
2.05 | MANUFACTURE CHARACTERISTICS. | |||
ISOLATING MATERIAL. | PORCELAIN OR SILICON RUBBER | PORCELAIN | ||
DRIVER SECTION RANGE. | MM2 | 35 TO 120 | 35 TO 120MM2 | |
CABLE MATERIAL ADMISSIBLE. | Cu / Al | CU/AL | ||
3 | SECTIONALIZER CHARACTERISTICS. | |||
RANGE OF CURRENT ACTION. | A | FROM 5 TO 230 | 5A-230A | |
STEP CURRENT GRADUATION. | A | 1 | 1A | |
PRE-LOAD CURRENT (ATTACH PRE-LOAD CURVE). | A | 0.5 OR LESS | 0.3A | |
NUMBER OF OPENING COUNTINGS. | 1, 2, 3 AND 4 | 1, 2, 3 AND 4 | ||
CURRENT BLOCKING OF INRUSH. | YES | |||
DETECTION OF DEADLINE. | mamp | 300 OR LESS | 300mA | |
DEADLINE VERIFICATION TIME. | msecond | 100 or less | 100mS | |
MAXIMUM MEMORY TIME WITH DEADLINE. | s | between 30 and 300 | 30s-300s | |
TOTAL OPENING TIME. | s | 0.5 or less | 0.5S | |
MEMORY RESET TIME (ACCOUNTS). | s | from 10 to 80 in steps og 1 sec | from 10 to 80 in steps of 1 sec | |
ADMISSIBLE CURRENT OF SHORT DURATION. | ||||
1 sec | KA | 10 | 10 | |
2 sec. | KA | 4 | 4 | |
3.11 | PEAK CURRENT VALUE ADMISSIBLE. | KA | 16 | 16 |
3.12 | PREPARED FOR DISTANCE ACCESS WITH DNP PROTOCOL. | YES | ||
3.13 | PORT OF COMMUNICATION (FOR THE CONCENTRATOR). | |||
3.14 | COMMUNICATION PROTOCOL. | IEC60870-5-101 | ||
3.15 | SOFTWARE AND ACCESSORIES FOR COMMUNICATION AND CONFIGURATION OF THE SECTIONALIZER THROUGH LAPTOP (FUNCTIONAL PARAMETERS AND STATISTICAL CONSULTATION STORED) | YES | ||
3.16 | THE UNIT OF THE INTERFACE TOOL MUST BE CONSIDERED FOR EVERY 50 UNITS OF SECTIONALIZERS. | YES | ||
ITEM 2 : SECTIONALIZERS 1 POLE 27 KV PROGRAMMABLE | ||||
ITEM | SPECIFICATIONS | UNIT | REQUIRED | GUARANTEED |
1 | GENERAL DATA | |||
1.01 | COUNTRY OF ORIGIN. | INDICATE | CHINA | |
1.02 | MANUFACTURER | INDICATE | HEMG | |
1.03 | MODEL. | INDICATE | FDK-27KV | |
1.04 | STANDARD OF MANUFACTURE | ANSI C37.63 or IEC | ANSI C37.63 /IEC | |
1.05 | TYPE | OUTDOOR | OUTDOOR | |
1.06 | SYSTEM | 1 POLE ( SINGLE POLE) | SINGLE POLE | |
1.07 | TYPE OF OPERATION | AUTOMATYC AND MANUAL | AUTOMATIC AND MANUAL | |
1.08 | ALITUDE OF OPERATION | MOSL | FROM 500 TO 4500 | UP TO 4500 |
1.09 | TYPE OF PERFORMANCE ACCORDING TO CONFIGURATION (1 POLE, TWO POLE OR 3 POLE) | AUTOMATYC AND MANUAL | AUTOMATIC AND MANUAL | |
2 | NOMINAL DATA BASE SUPPORT OF SECTIONALIZER | |||
2.01 | NOMINAL FRECUENCY. | 60 HZ | 60HZ | |
2.02 | VOLTAGE CHARACTERISTICS. | |||
NOMINAL VOLTAGE OF THE SYSTEM. | KV | 22.9 | 22.9 | |
MAXIMUM VOLTAGE OF THE SYSTEM. | KV | 27 | 27 | |
2.03 | INSULATION LEVEL. | |||
NOMINAL VOLTAGE | KV | 227 | 27 | |
WITHSTAND VOLTAGE INDUSTRIAL FREQUENCY 1 MINUTE | KVp | 60 | 60 | |
WITHSTAND VOLTAGE IMPULSE 1.2/50 us | KVp | 150 | 50 | |
LEAKAGE DISTANCE | MM/KV | 25 | 25 | |
2.04 | CURRENT CHARACTERISTICS | |||
NOMINAL CURRENT | A | 100 OR MORE | 100 | |
CURRENT OF NOMINAL SYMMETRICAL INTERRUPTION. | KA | 4 OR MORE | 4 | |
PEAK VALUE OF FAULT CURRENT. | KA | 10 OR MORE | 10 | |
2.05 | MANUFACTURE CHARACTERISTICS. | |||
ISOLATING MATERIAL. | PORCELAIN OR SILICON RUBBER | PROCELAIN | ||
DRIVER SECTION RANGE. | MM2 | 35 TO 120 | 35-120MM2 | |
CABLE MATERIAL ADMISSIBLE. | Cu / Al | CU/AL | ||
3 | SECTIONALIZER CHARACTERISTICS. | |||
RANGE OF CURRENT ACTION. | A | FROM 5 TO 230 | FROM 5 TO 230A | |
STEP CURRENT GRADUATION. | A | 1 | 1 | |
PRE-LOAD CURRENT (ATTACH PRE-LOAD CURVE). | A | 0.5 OR LESS | 0.3 | |
NUMBER OF OPENING COUNTINGS. | 1, 2, 3 AND 4 | 1,2,3,4 | ||
CURRENT BLOCKING OF INRUSH. | YES | YES | ||
DETECTION OF DEADLINE. | mamp | 300 OR LESS | 300 | |
DEADLINE VERIFICATION TIME. | msecond | 100 or less | 100 | |
MAXIMUM MEMORY TIME WITH DEADLINE. | s | between 30 and 300 | 30-300 | |
TOTAL OPENING TIME. | s | 0.5 or less | 0.5 | |
MEMORY RESET TIME (ACCOUNTS). | s | from 10 to 80 in steps oF 1 sec | FROM 10 TO 80 IN STEPS OF 1 SEC | |
ADMISSIBLE CURRENT OF SHORT DURATION. | ||||
1 sec | KA | 8 | 8 | |
2 sec. | KA | 3 | 3 | |
3.11 | PEAK CURRENT VALUE ADMISSIBLE. | KA | 20 | 20 |
3.12 | PREPARED FOR DISTANCE ACCESS WITH DNP PROTOCOL. | YES | YES | |
3.13 | PORT OF COMMUNICATION (FOR THE CONCENTRATOR). | RS-485 OR ETHERNET | RS-485 | |
3.14 | COMMUNICATION PROTOCOL. | IEC 60870-5-101 ( IEC104) OR DNP | IEC 60870-5-101 | |
3.15 | SOFTWARE AND ACCESSORIES FOR COMMUNICATION AND CONFIGURATION OF THE SECTIONALIZER THROUGH LAPTOP (FUNCTIONAL PARAMETERS AND STATISTICAL CONSULTATION STORED) | YES | YES | |
3.16 | THE UNIT OF THE INTERFACE TOOL MUST BE CONSIDERED FOR EVERY 50 UNITS OF SECTIONALIZERS. | YES | YES | |
ITEM 3 : DATA CONCENTRATOR FOR PROGRAMMABLE SECTIONALIZERS 15 KV AND 27 KV, BIL 150 KV | ||||
ITEM | SPECIFICATIONS | UNIT | REQUIRED | GUARANTEED |
1 | CONCENTRATOR | |||
MANUFACTURER. | INDICATE | HEMG | ||
COUNTRY | INDICATE | CHINA | ||
MODEL. | INDICATE | APT-309 | ||
DISTANCE OF COMMUNICATION VIA RADIO FRECEUNCIA FOR THE COLLECTION OF EVENTS (PERMANENT FAILURES, TEMPORARY FAILURES) FOR THE SECTIONALIZERS NEAR THE CONCENTRATOR. | 50 MTS OR MORE | 50MTS | ||
NUMBER OF AIR CIRCULAR SECTIONALISTS FOR RADIO COMMUNICATION WITH THE CONCENTRATOR. | 9 OR MORE | 9 | ||
COMMUNICATION BETWEEN THE CONCENTRATOR AND THE MANAGEMENT SOFTWARE (FOR CONFIGURATION AND MODIFICATION OF PARAMETERS). | YES | YES | ||
COMMUNICATION BETWEEN THE CONCENTRATOR AND A SCADA SYSTEM (WITHOUT INTERMEDIATE SOFTWARE) THROUGH DNP3 COMMUNICATION PROTOCOL ON TCP / IP, USING GPRS COMMUNICATION INTERFACE THE ANTENNA MUST BE EXTERNAL OMNIDIRETIONAL, TYPE BOND WITH COAXIAL CABLE AND BNC / SMA CONNECTOR OR SIMILAR WITH GAIN OF 14 DBI OR MORE. | YES | BY IE80670-5-101.104/DNP IS ARAIABLE ,PRICE WILL BE EXTRA ADDING | ||
EMBOSSED GPRS MODEM. | YES | YES | ||
INTERNAL POWER SUPPLY BATTERY (MAINTENANCE FREE AND REPLACEABLE). | 5 YEARS OR MORE | 5 | ||
WITH MEMORY TO STORE LAST FAILURES, EVENTS AND DOWNLOAD THE INFORMATION OF THE SAME EQUIPMENT). | YES | YES | ||
TYPE OF FAILURE WITH TIME STAMP, CURRENT MEASURES, PRESENCE / ABSENCE OF VOLTAGE OF THE BATTERY, PARAMETERS OF THE MANAGED EQUIPMENT AND STATE OF THE SAME CONCENTRATOR. | YES | YES | ||
THE INFORMATION STORED IN THE CONCENTRATOR CAN BE MANAGED FROM THE MANAGEMENT SOFTWARE IN A LOCAL AND REMOTE WAY. | YES | YES | ||
PORT RJ45 10/100 FOR LOCAL CONFIGURATION | YES | YES | ||
2 | SOFTWARE FOR CONFIGURATION AND MANAGEMENT OF THE CONCENTRATOR AND SECTIONALIZER. | |||
MANUFACTURER. | INDICATE | HEMG | ||
COUNTRY | INDICATE | CHINA | ||
MODEL. | ||||
NAME OF THE SOFTWARE. | INDICATE | FAULT MONITORIG SOFTWARE | ||
EXECUTION UNDER WINDOWS OPERATING SYSTEM. | YES | YES | ||
DIRECT CONNECTION INTERFACE TO THE EQUIPMENT. | YES | YES | ||
HANDLING OF USERS, LEVELS AND ACCESS PERMITS. | YES | YES | ||
MANUFACTURING AND CONFIGURATION MODULE. | YES | YES | ||
PARAMETERIZATION MODULE OF THE CONCENTRATOR. | YES | YES | ||
EVENTS DISPLAY MODULE. | YES | YES | ||
MODULE OF HISTORICAL AND STATISTICAL REPORT. | YES | YES | ||
EXPORT OF REPORTS TO A CALCULATION SHEET FORMAT. | YES | YES | ||