27kv Pole Mounted Sectionalizer with Fault Monitoring System
27kv Pole Mounted Sectionalizer with Fault Monitoring System
 ITEM  1  : SECTIONALIZERS 1 POLE  15 KV PROGRAMMABLE   
ITEMSPECIFICATIONSUNITREQUIREDGUARANTEED
1GENERAL DATA   
1.01COUNTRY OF ORIGIN. INDICATECHINA
1.02MANUFACTURER INDICATEHEMG
1.03MODEL. INDICATEFDK-15KV
1.04STANDARD OF MANUFACTURE ANSI C37.63 or IECANSI C37.63/IEC
1.05TYPE    OUTDOOROUTDOOR
1.06SYSTEM 1 POLE ( SINGLE POLE)SINGLE POLE
1.07TYPE OF OPERATION AUTOMATYC AND MANUALAUTOMATIC AND MANUAL
1.08ALITUDE OF OPERATIONMOSLFROM 500 TO 4500UP TO 4500M
1.09TYPE OF PERFORMANCE ACCORDING TO CONFIGURATION (1 POLE, TWO POLE OR 3 POLE) AUTOMATYC AND MANUALAUTOMATIC AND MANUAL
2NOMINAL DATA BASE SUPPORT OF SECTIONALIZER   
2.01NOMINAL FRECUENCY. 60 HZ60HZ
2.02VOLTAGE CHARACTERISTICS.   
 NOMINAL VOLTAGE OF THE SYSTEM.KV10, 13.2, 13.810..13.2.13.8
 MAXIMUM VOLTAGE OF THE SYSTEM.KV1515
2.03INSULATION LEVEL.   
 NOMINAL VOLTAGE  KV1515
 WITHSTAND VOLTAGE INDUSTRIAL FREQUENCY  1 MINUTEKVp5050
 WITHSTAND VOLTAGE IMPULSE 1.2/50 usKVp125125
 LEAKAGE DISTANCEMM/KV2525
2.04CURRENT CHARACTERISTICS   
 NOMINAL CURRENTA100 OR MORE100A
 CURRENT OF NOMINAL SYMMETRICAL INTERRUPTION.KA4 OR MORE8
 PEAK VALUE OF FAULT CURRENT.KA10 OR MORE10
2.05MANUFACTURE  CHARACTERISTICS.   
 ISOLATING MATERIAL. PORCELAIN OR SILICON RUBBERPORCELAIN
 DRIVER SECTION RANGE.MM235 TO 12035 TO 120MM2
 CABLE MATERIAL ADMISSIBLE. Cu / AlCU/AL
3SECTIONALIZER CHARACTERISTICS.   
 RANGE OF CURRENT ACTION.AFROM 5 TO 2305A-230A
 STEP CURRENT GRADUATION.A11A
 PRE-LOAD CURRENT (ATTACH PRE-LOAD CURVE).A0.5 OR LESS0.3A
 NUMBER OF OPENING COUNTINGS. 1, 2, 3 AND 41, 2, 3 AND 4
 CURRENT BLOCKING OF INRUSH. YES 
 DETECTION OF DEADLINE.mamp300 OR LESS300mA
 DEADLINE VERIFICATION TIME.msecond100 or less100mS
 MAXIMUM MEMORY TIME WITH DEADLINE.sbetween 30 and 30030s-300s
 TOTAL OPENING TIME.s0.5 or less0.5S
 MEMORY RESET TIME (ACCOUNTS).sfrom 10 to 80 in steps og 1 secfrom 10 to 80 in steps of 1 sec
 ADMISSIBLE CURRENT OF SHORT DURATION.   
 1 secKA1010
 2 sec.KA44
3.11PEAK CURRENT VALUE ADMISSIBLE.KA1616
3.12PREPARED FOR DISTANCE ACCESS WITH DNP PROTOCOL.  YES
3.13PORT OF COMMUNICATION (FOR THE CONCENTRATOR).   
3.14COMMUNICATION PROTOCOL.  IEC60870-5-101
3.15SOFTWARE AND ACCESSORIES FOR COMMUNICATION AND CONFIGURATION OF THE SECTIONALIZER THROUGH LAPTOP (FUNCTIONAL PARAMETERS AND STATISTICAL CONSULTATION STORED)  YES
3.16THE UNIT OF THE INTERFACE TOOL MUST BE CONSIDERED FOR EVERY 50 UNITS OF SECTIONALIZERS.  YES
     
     
 ITEM  2  : SECTIONALIZERS 1 POLE  27 KV PROGRAMMABLE   
ITEMSPECIFICATIONSUNITREQUIREDGUARANTEED
1GENERAL DATA   
1.01COUNTRY OF ORIGIN. INDICATECHINA
1.02MANUFACTURER INDICATEHEMG
1.03MODEL. INDICATEFDK-27KV
1.04STANDARD OF MANUFACTURE ANSI C37.63 or IECANSI C37.63 /IEC
1.05TYPE    OUTDOOROUTDOOR
1.06SYSTEM 1 POLE ( SINGLE POLE)SINGLE POLE
1.07TYPE OF OPERATION AUTOMATYC AND MANUALAUTOMATIC AND MANUAL
1.08ALITUDE OF OPERATIONMOSLFROM 500 TO 4500UP TO 4500
1.09TYPE OF PERFORMANCE ACCORDING TO CONFIGURATION (1 POLE, TWO POLE OR 3 POLE) AUTOMATYC AND MANUALAUTOMATIC AND MANUAL
2NOMINAL DATA BASE SUPPORT OF SECTIONALIZER   
2.01NOMINAL FRECUENCY. 60 HZ60HZ
2.02VOLTAGE CHARACTERISTICS.   
 NOMINAL VOLTAGE OF THE SYSTEM.KV22.922.9
 MAXIMUM VOLTAGE OF THE SYSTEM.KV2727
2.03  INSULATION LEVEL.   
 NOMINAL VOLTAGE  KV22727
 WITHSTAND VOLTAGE INDUSTRIAL FREQUENCY  1 MINUTEKVp6060
 WITHSTAND VOLTAGE IMPULSE 1.2/50 usKVp15050
 LEAKAGE DISTANCEMM/KV2525
2.04CURRENT CHARACTERISTICS   
 NOMINAL CURRENTA100 OR MORE100
 CURRENT OF NOMINAL SYMMETRICAL INTERRUPTION.KA4 OR MORE4
 PEAK VALUE OF FAULT CURRENT.KA10 OR MORE10
2.05MANUFACTURE  CHARACTERISTICS.   
 ISOLATING MATERIAL. PORCELAIN OR SILICON RUBBERPROCELAIN
 DRIVER SECTION RANGE.MM235 TO 12035-120MM2
 CABLE MATERIAL ADMISSIBLE. Cu / AlCU/AL
3SECTIONALIZER CHARACTERISTICS.   
 RANGE OF CURRENT ACTION.AFROM 5 TO 230FROM 5 TO 230A
 STEP CURRENT GRADUATION.A11
 PRE-LOAD CURRENT (ATTACH PRE-LOAD CURVE).A0.5 OR LESS0.3
 NUMBER OF OPENING COUNTINGS. 1, 2, 3 AND 41,2,3,4
 CURRENT BLOCKING OF INRUSH. YESYES
 DETECTION OF DEADLINE.mamp300 OR LESS300
 DEADLINE VERIFICATION TIME.msecond100 or less100
 MAXIMUM MEMORY TIME WITH DEADLINE.sbetween 30 and 30030-300
 TOTAL OPENING TIME.s0.5 or less0.5
 MEMORY RESET TIME (ACCOUNTS).sfrom 10 to 80 in steps oF 1 secFROM 10 TO 80 IN STEPS OF 1 SEC
 ADMISSIBLE CURRENT OF SHORT DURATION.   
 1 secKA88
 2 sec.KA33
3.11PEAK CURRENT VALUE ADMISSIBLE.KA2020
3.12PREPARED FOR DISTANCE ACCESS WITH DNP PROTOCOL. YESYES
3.13PORT OF COMMUNICATION (FOR THE CONCENTRATOR). RS-485 OR ETHERNETRS-485
3.14COMMUNICATION PROTOCOL. IEC 60870-5-101 ( IEC104) OR DNPIEC 60870-5-101
3.15SOFTWARE AND ACCESSORIES FOR COMMUNICATION AND CONFIGURATION OF THE SECTIONALIZER THROUGH LAPTOP (FUNCTIONAL PARAMETERS AND STATISTICAL CONSULTATION STORED) YESYES
3.16THE UNIT OF THE INTERFACE TOOL MUST BE CONSIDERED FOR EVERY 50 UNITS OF SECTIONALIZERS. YESYES
     
      
     
     
 ITEM 3  :  DATA CONCENTRATOR FOR PROGRAMMABLE SECTIONALIZERS 15 KV AND 27 KV, BIL 150 KV   
ITEMSPECIFICATIONSUNITREQUIREDGUARANTEED
1CONCENTRATOR   
 MANUFACTURER. INDICATEHEMG
 COUNTRY INDICATECHINA
 MODEL. INDICATEAPT-309
 DISTANCE OF COMMUNICATION VIA RADIO FRECEUNCIA FOR THE COLLECTION OF EVENTS (PERMANENT FAILURES, TEMPORARY FAILURES) FOR THE SECTIONALIZERS NEAR THE CONCENTRATOR. 50 MTS OR MORE50MTS
 NUMBER OF AIR CIRCULAR SECTIONALISTS FOR RADIO COMMUNICATION WITH THE CONCENTRATOR. 9 OR MORE9
 COMMUNICATION BETWEEN THE CONCENTRATOR AND THE MANAGEMENT SOFTWARE (FOR CONFIGURATION AND MODIFICATION OF PARAMETERS). YESYES
 COMMUNICATION BETWEEN THE CONCENTRATOR AND A SCADA SYSTEM (WITHOUT INTERMEDIATE SOFTWARE) THROUGH DNP3 COMMUNICATION PROTOCOL ON TCP / IP, USING GPRS COMMUNICATION INTERFACE THE ANTENNA MUST BE EXTERNAL OMNIDIRETIONAL, TYPE BOND WITH COAXIAL CABLE AND BNC / SMA CONNECTOR OR SIMILAR WITH GAIN OF 14 DBI OR MORE. YESBY IE80670-5-101.104/DNP IS ARAIABLE ,PRICE WILL BE EXTRA ADDING
 EMBOSSED GPRS MODEM. YESYES
 INTERNAL POWER SUPPLY BATTERY (MAINTENANCE FREE AND REPLACEABLE). 5 YEARS OR MORE5
 WITH MEMORY TO STORE LAST FAILURES, EVENTS AND DOWNLOAD THE INFORMATION OF THE SAME EQUIPMENT). YESYES
 TYPE OF FAILURE WITH TIME STAMP, CURRENT MEASURES, PRESENCE / ABSENCE OF VOLTAGE OF THE BATTERY, PARAMETERS OF THE MANAGED EQUIPMENT AND STATE OF THE SAME CONCENTRATOR. YESYES
 THE INFORMATION STORED IN THE CONCENTRATOR CAN BE MANAGED FROM THE MANAGEMENT SOFTWARE IN A LOCAL AND REMOTE WAY. YESYES
 PORT  RJ45 10/100 FOR LOCAL CONFIGURATION YESYES
2SOFTWARE FOR CONFIGURATION AND MANAGEMENT OF THE CONCENTRATOR AND SECTIONALIZER.   
 MANUFACTURER. INDICATEHEMG
 COUNTRY INDICATECHINA
 MODEL.   
 NAME OF THE SOFTWARE. INDICATEFAULT MONITORIG SOFTWARE
 EXECUTION UNDER WINDOWS OPERATING SYSTEM. YESYES
 DIRECT CONNECTION INTERFACE TO THE EQUIPMENT. YESYES
 HANDLING OF USERS, LEVELS AND ACCESS PERMITS. YESYES
 MANUFACTURING AND CONFIGURATION MODULE. YESYES
 PARAMETERIZATION MODULE OF THE CONCENTRATOR. YESYES
 EVENTS DISPLAY MODULE. YESYES
 MODULE OF HISTORICAL AND STATISTICAL REPORT. YESYES
 EXPORT OF REPORTS TO A CALCULATION SHEET FORMAT. YESYES