12kv Intelligent Eco Friendly Magnetic Actuator Automatic Circuit Recloser

China 12kv Intelligent Eco Friendly Magnetic Actuator Automatic Circuit Recloser, Find details about China High Voltage Circuit Recloser, Auto Recloser from 12kv Intelligent Eco Friendly Magnetic Actuator Automatic Circuit Recloser

Model NO.
AB-3S-12
Trademark
New Concept Electric
Specification
80 kg
Origin
Yangzhou, Jiangsu, China
HS Code
8535210000
Model NO.
AB-3S-12
Trademark
New Concept Electric
Specification
80 kg
Origin
Yangzhou, Jiangsu, China
HS Code
8535210000
12kv Eco Friendly Magnetic Actuator Automatic Circuit Recloser

The AB-3S-12 series circuit reclosers are recently-developed pole-mounted intelligent vacuum circuit reclosers of a new generation, which absorb the advanced domestic and foreign technologies adopted by our company, embody the design concept of being "intelligent, energy-saving, environemntally-friendly and maintenance-free" and comply with the actual conditions of China's power distribution network and the construction requirements of smart grid. These products can be used as switches at the 10kV outgoing line of substation as well as pole-mounted switches for power distribution networks. This product integrates such functions as control, protection, measurement, fault positioning, online monitoring and synchronous closing. With full functions and high digitalized and intelligent degree, they are top choices for equipment of power distribution network automation and intellectualization process.
12kv Intelligent Eco Friendly Magnetic Actuator Automatic Circuit Recloser
12kv Intelligent Eco Friendly Magnetic Actuator Automatic Circuit Recloser

This product conforms to IEC62271, IEC60298, GB3906-2006, GB/T 11022-1999, DL/T 593-2006, GB 1984-2003 standards, etc.

Major Technical Parameters are Shown Below:
Rated voltage12 kV
Rated current630/1,250 A
Rated frequency50 Hz
Rated short-duration (1 min) power frequency withstand voltage42/48 kV
Rated short-circuit breaking current20/25 kA
Rated short-duration withstand current (4s)20/25 kA
Rated lightning impluse withstand voltage(to earth/break)75/85 kV
Rated short-circuit making current (peak value)50/63 kA
Rated peak withstand current50/63 kA
Rated short-circuit current breaking times30 times
Mechanical service life of vacuum circuit recloser10,000 times
CT transformation ratio600/1 or 1,250/1
Rated operating sequence of circuit recloserO-0.3s-CO-3s-CO-3s-CO-Lock
Total weight80+40 kg