40.5kv Three Phase Magnetic Actuator Automatic Auto Recloser ACR

China 40.5kv Three Phase Magnetic Actuator Automatic Auto Recloser ACR, Find details about China Three Phase Auto Recloser, Automatic Circuit Recloser from 40.5kv Three Phase Magnetic Actuator Automatic Auto Recloser ACR

Model NO.
AR-3S-40.5
Trademark
New Concept
Specification
200Kg
Origin
Yangzhou
HS Code
8535210000
Model NO.
AR-3S-40.5
Trademark
New Concept
Specification
200Kg
Origin
Yangzhou
HS Code
8535210000
40.5kv THREE PHASE Magnetic Actuator Automatic Auto Recloser ACR

The AB-3S-40.5 series circuit reclosers are recently-developed pole-mounted intelligent vacuum circuit reclosers of a new generation, which absorb the advanced domestic and foreign technologies adopted by our company, embody the design concept of being "intelligent, energy-saving, environemntally-friendly and maintenance-free" and comply with the actual conditions of China's power distribution network and the construction requirements of smart grid. These products can be used as switches at the 10kV outgoing line of substation as well as pole-mounted switches for power distribution networks. This product integrates such functions as control, protection, measurement, fault positioning, online monitoring and synchronous closing. With full functions and high digitalized and intelligent degree, they are top choices for equipment of power distribution network automation and intellectualization process.

This product conforms to IEC62271-111, IEC60298, GB3906-2006, GB/T 11022-1999, DL/T 593-2006, GB 1984-2003 standards, etc.

 Major Technical Parameters are shown below:
 
Rated voltagekV40.5
Rated currentA1250/1600
Rated frequencyHz50
1min power frequency withstand voltage (to earth/open contacts)kV95
Rated lightning impulse withstand voltage (to earth/open contacts)kV185
Rated short circuit break currentkA25/31.5
Rated short circuit making current (peak)kA63/80
Thermal stable current(4s)kA25/31.5
Dynamic stable current(peak)kA63/80
Rated short circuit current break timeTime20
Closing timems≤100
Opening timems≤70
Average open speedm/s1.3~1.8
Average close speedm/s1.0~1.7
Mechanical timeTime10000
Rated operation sequence of circuit breaker O-0.3s-CO-3s-CO-3s-CO-lockout
Current transformer ratio Optional
Accuracy degree Optional
Shell protection degree IP64
Weightkg300

Our advantages:
1. Most parts are manufactured ourselves, like: frame, cabinet, permanent magnet mechanism, insulation part, control panel, etc. That means the process quality control is effectively controlled.
2. Adopt fast algorithm with national patent technology (patent number: ZL200720037710.7) so as to obtain fast breaking capacity of circuit breaker. As a result, it can isolate fault circuit rapidly. It takes less than 25ms from inspecting fault to cut fault circuit by separate circuit breaker. It can avoid the problem of override trip effectively.
3. Adopt single phase earthing protection system with national patent technology (patent number: ZL201020178325.6). It can realize on-line judgment to single phase earthing fault of low current earthing system without adding device. Releases warning or tripping action according to setting value


Our service:
1. Pre-sale technical support, training;
2. On-site factory inspection is accepted;
3. Open atitude for cooperation;
4. Punctual goods delivery;
5. After-sale technical support and service.

40.5kv Three Phase Magnetic Actuator Automatic Auto Recloser ACR
40.5kv Three Phase Magnetic Actuator Automatic Auto Recloser ACR
40.5kv Three Phase Magnetic Actuator Automatic Auto Recloser ACR
40.5kv Three Phase Magnetic Actuator Automatic Auto Recloser ACR