China Environment-Friendly Nitrogen Insulated Rmu, Find details about China Ring Main Unit, Rmu from Environment-Friendly Nitrogen Insulated Rmu
10 , The product technical plan is complete, which can be implemented according to the technical requirements of various places and even countries Current upper isolation or lower isolation, top expansion or side expansion, co-box type or expandable type, spring actuator Structure or permanent magnet operating mechanism.
Load switch cabinet | Breaker Cabinet | |
Rated voltage kV | 12 | 95 |
Rated frequency Hz | 50/60 | |
1 min power frequency withstand voltage (phase to phase, to ground) kV | 42 | |
1 min power frequency withstand voltage (fracture) kV | 48 | |
Lightning impulse withstand voltage kV | 75 | |
Rated current A | 630 | 630/1250(*) |
Rated active load breaking current A | 630 | |
Rated closed loop breaking current A | 630 | |
Rated cable charging breaking current A | 10 | 25 |
Ground fault breaking current A | 31.5 | |
Cable charging breaking current A during ground fault | 17.3 | |
Rated short-circuit breaking current | 20 | |
Rated short-circuit making current | 50 | |
Rated short-time withstand current (4s) | 20 | |
Rated peak withstand current | 50 | |
Mechanical life | 20000 | |
3-position isolator Mechanical life | 10000 | |
Ambient temperature (Celsius) | -40---+40 | |
SF6 gas pressure (gauge pressure at 20 ºC ) MPa | 0.02 | |
Arc withstand capability kA/1s | 20 | |
Protection level | Tank IP67/cabinet IP4X |
Note:* The rated current value of circuit breaker unit and bus can be up to 1250A, which can be negotiated with the manufacturer according to the customer's demand.
Testing Area
Temperature rise test and partial discharging test