630A, Switchgear Vessel Gas Filled in Load Switch Breaker Solution Rmu

China 630A, Switchgear Vessel Gas Filled in Load Switch Breaker Solution Rmu, Find details about China Ring Main Unit, Rmu from 630A, Switchgear Vessel Gas Filled in Load Switch Breaker Solution Rmu

Application Range
High-rise Buildings
Shell Material
Stainless Steel
Shell Protection Grade
IP42 or Cutomized
Brand
Sanhe
Transport Package
Plywood or Solid Wood
HS Code
8536200000
Application Range
High-rise Buildings
Shell Material
Stainless Steel
Shell Protection Grade
IP42 or Cutomized
Brand
Sanhe
Transport Package
Plywood or Solid Wood
HS Code
8536200000
    The Ring Main Unit 8MRMU was developed under Germany technology by the engineers of over ten years switchgear production and application experience. We designed it on the concept of self-contained and totally insulated switchgear for secondary power distribution network. The products conform to China national GB and IEC standards      
   The Ring Main Unit 8MRMU is insensible to the environment and it is maintenance free. All the live parts are integrated well in the gas tank which SF6 is filled at 0.03 MPa gauge pressure(relative). These parts cover bus bar system, load break switch, disconnector, circuit breaker, earthing switch , fuse holders etc. The compact system,of which up to 6 loops could be accommodated in a single gas tank, is ideal solution for the installation site with a harsh climatic condition or environmental restrictions, We have gave models for the standard specification like 12kV and 24kV. Meanwhile,we can accept OEM or ODM business.

Feature:
Compact design
Maximum 6 loops could be accommodated in a single gas tank, space-saving, maintenance free
Environment-friendly structure
Hermetically tight gas tank make the parts of the primary circuit insensitive to certain aggressive ambient conditions, such as: Saline air,Air humidity, Dust And free from foreign objects etc
Maintenance-free design
Sealed pressure systems brings high reliability and safety.Finally,It is cost-saving.  
Innovation system
Clear integration of secondary systems and combined protection and control  units is well adapted to new system conditions.  
Service life
The expected service life of gas-insulated switchgear is over 30 years. The product lifespan is 45 years

8MRMU-C Incoming Panel with Load-Break Switch

Voltage(kV) 

Rated current

Short time withstand current(3s)

Switch Type 

Insulation type

Structure 

Remark 

12/24

630A

20kA

DES(LBS) 

SF6 

Max.6 loops

standard 


Specification 
Rated VoltagekV1224
Rated FrequencyHz50/60
Power Frequency Withstand Voltage (1min)(Phase to Phase, Phase to Earth)kV4250
Power Frequency Withstand Voltage (1min)(Isolation Gap)kV4860
Lightning Impulse Withstand Voltage(Phase to Phase, Phase to Earth)kV75125
Lightning Impulse Withstand Voltage(Isolation Gap)kV85/95(optional)145
Rated CurrentA630630
Rated Active Load Breaking CurrentA630630
Closed Loop Breaking CurrentA630630
Rated Breaking Current for Cable ChargingA1010
Rated Earthing Fault Breaking CurrentA31.531.5
Rated Short Circuit Making Current(Peak)kA5050
Short Time Withstand Current (4s)kA2020
Rated Peak Withstand Current (Peak)kA5050
Mechanical EnduranceOperating Cycles50005000
Rated SF6 Filling Pressure (Relative)MPa0.030.035
Protection DegreeIP67 for Gas Tank, IP4X for Enclosure

outdoor enclosure IP54(optional)
Overall Dimensions(Width*Height*Depth)mm340*1450*780

Note: *.Depends on the rating value of the fuse.

630A, Switchgear Vessel Gas Filled in Load Switch Breaker Solution Rmu