China GTM2L-630/3N 400A Earth Leakage Circuit Breaker ELCB with IEC60947-2, Find details about China RCCB, Earth Leakage Circuit Breaker from GTM2L-630/3N 400A Earth Leakage Circuit Breaker ELCB with IEC60947-2
Model | GTM2L-125 | GTM2L-250 | GTM2L-400 | GTM2L-630 | ||
IEC60947-2 | ||||||
Shell grade current Inm(A) | 125 | 250 | 400 | 630 | ||
Operating frequency (Hz) | 50 | 50 | 50 | 50 | ||
Number of poles | 3N | 3N | 3N | 3N | ||
Rated current In(A) | 16~125 | 100~250 | 250~400 | 400~630 | ||
Rated insulation voltage Ui(V) | 800 | 800 | 800 | 800 | ||
Rated impulse withstand voltage Uimp(KV) | 8 | 8 | 8 | 8 | ||
Rated working voltage Ue(V) | 400 | 400 | 400 | 400 | ||
Flashover distance (mm) | ≯50 | ≯80 | ≯100 | ≯100 | ||
Rated limit short circuit breaking capacity Icu(kA) | 35 | 35 | 50 | 50 | ||
Rated runningshort circuit breaking capacity Ics(kA) | 25 | 25 | 35 | 35 | ||
rated short-circuit turn on capacity Icm(kA)/1s | 25%Icu | 25%Icu | 25%Icu | 25%Icu | ||
Rated residual operating current IΔn(mA) | 30(Non delay type), 50, 100, 300, 500 | 30(Non delay type), 50, 100, 300, 500 | 100, 300, 500, 1000 | 100, 300, 500, 1000 | ||
Limit non driving time Δt(s) | 0.1, 0.3, 0.5, 1 | 0.1, 0.3, 0.5, 1 | 0.1, 0.3, 0.5, 1 | 0.1, 0.3, 0.5, 1 | ||
Rated residual non operating current IΔn(mA) | IΔno=IΔn/2 | IΔno=IΔn/2 | IΔno=IΔn/2 | IΔno=IΔn/2 | ||
Utilization category | A | A | A | A | ||
Service life | Mechanical life (times) | Maintenance free | 20000 | 20000 | 10000 | 10000 |
With maintenance | 40000 | 40000 | 20000 | 20000 | ||
Electrical life(times) | 400V | 8000 | 8000 | 7500 | 7500 | |
Outline dimension(mm) | Width | 120 | 140 | 198 | 280 | |
Length | 190 | 210 | 258 | 280 | ||
Height | 85 | 108 | 150 | 158 | ||
Optional Accessories | ||||||
Alarm contact | 08 | O | O | O | O | |
Shunt release | 10 | O | O | O | O | |
Auxiliary contact | 20 | O | O | O | O | |
Two sets of auxilisry contact | 60 | O | O | O | O |