Online UPS Double Conversion 6kVA, 10kVA, 15kVA, 20kVA UPS by China UPS Power Supplier, Find details about China Uninterruptible Power Source, Battery Backup from Online UPS Double Conversion 6kVA, 10kVA, 15kVA, 20kVA UPS by China UPS Power Supplier
True double-conversion
Real-time digital signal processor (DSP) control
N+X parallel redundancy
Selectable quantity of battery for each group:for long run unit
Adjustable charging current via LCD
3-stage charging design optimizes battery performance
ECO mode operation for energy saving
Self-diagnosis at startup
Emergency power off function(EPO)
Maintenance bypass is convenient for maintenance
Generator compatible
Communications:RS-232,USB,SNMP card(Optional), Relay card (Optional)
Cold start
MODEL | UCR60L | UCR100L | ||||
Capacity (VA/Watts) | 6K / 5.4K | 10K / 9K | ||||
INPUT | ||||||
Nominal Voltage | 380/400/415Vac(3Ph+N+PE) or 220/230/240Vac(L+N+PE) | |||||
Operating Voltage Range | 208~478Vac or 120VAC-276Vac | |||||
Operating Frequency Range | 50Hz:45~55Hz,60Hz:54~66Hz | |||||
Power Factor | ≥0.99 | |||||
Bypass Voltage Range | Max.voltage: 220V:+25%(Optional +10%,+15%,+20% ) | |||||
230V:+20%(Optional +10%,+15%) | ||||||
240V:+15%(Optional +10% ) | ||||||
Min. voltage: -45% (Optional -20%,-30%) | ||||||
ECO Range | Same as bypass | |||||
Harmonic Distortion (THDi) | ≤5%(100% non-linear load) | |||||
OUTPUT | ||||||
Output Voltage | 220/230/240Vac | |||||
Power Factor | 0.9 | |||||
Voltage Regulation | ±1% | |||||
Frequency | Line Mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(Optional) | ||||
Bat.Mode | (50/60±0.1)Hz | |||||
Crest Factor | 3:1 | |||||
Harmonic Distortion (THD) | ≤2% with linear load | |||||
≤5% with non-linear load | ||||||
Waveform | Pure Sinewave | |||||
Transfer Time | Utility to Battery : 0ms; Utility to Bypass: 0ms | |||||
EFFICIENCY | ||||||
Efficiency | Up to 94% | |||||
BATTERY | ||||||
Battery Voltage | Selectable Voltage: ±96/108/120Vdc | |||||
Typical Recharge Time | 6-8 hours (To 90% capacity) | |||||
Charging Current | Maximum current 10A | |||||
PROTECTION | ||||||
Overload | Line Mode | Load≤125%: last 5min;≤150%: last 1min;>150% 200ms turn to bypass mode | ||||
Bypass Mode | 40A(Input breaker) | 63A(Input breaker) | ||||
Short Circuit | Hold Whole System | |||||
Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately | |||||
Battery Low | Alarm and Switch off | |||||
INDICATORS | ||||||
Audible &Visual Alarms | Line Failure, Battery Low, Overload, System Fault | |||||
Status LED &LCD Display | Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault | |||||
Parameters On The LCD Panel | Input/Output Voltage, Input/Output Frequency, Load Level, Battery Level, Inner Temperature & Remaining Battery Backup Time | |||||
MANAGEMENT | ||||||
Communication Interface | RS-232,USB,Parallel card, SNMP card(Optional), Relay card (Optional) | |||||
ENVIRONMENT | ||||||
Operating Temperature | 0ºC~40ºC | |||||
Storage Temperature | -25ºC~55ºC | |||||
Humidity Range | 0~95% (Non-condensing) | |||||
Altitude | < 1500m | |||||
Noise Level | <55dB | |||||
PHYSICAL | ||||||
Dimension W×H×D (mm) | 443×131×580(3U) | |||||
Net Weight (kg) | 30 | 31 | ||||
STANDARDS | ||||||
Noise Suppression | Complies with EN62040-2 | |||||
Safety | IEC/EN62040-1,IEC/EN60950-1 | |||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, | |||||
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | ||||||
BATTERY PACK | ||||||
Model | EXBR±120V | |||||
Battery type& Max.quantity | 7Ah×20/9Ah×20 | |||||
Dimensions W×H×D (mm) | 443×131×720(3U) | |||||
Net Weight (kg) | 67 |