China Switching Power Supply 30A 1800W Telecom Rectifier, Find details about China AC DC Telecom Rectifier, 48 VDC Telegram Power Rectifier from Switching Power Supply 30A 1800W Telecom Rectifier
1U 48V 30A Telegram power Switch DC power system
30A/48VDC/1800W Rectifier System
SPS series systems are compact and intelligent power system with capacity from 30A to 250A, containing rectifier modules, controller module, AC connection and DC connection. In addtion, easy installation to compact size add to the success of the system
Product features:
1. 19" 1U, 3U, 4U, 5U, 6U sub-rack, easy to be embedded into all standard kinds of telecom equipment;
2. System capacity from 30A to 250A;
3. PFC technique features the system high efficiency, energy-saving and up to 0.99 power factor;
4. Intelligent fan-cooling technique brings good cooling performance, low failure rate and high reliablity;
5. Fast on-line expansion of rectifier modules enabled by hot-swap;
6. N+1 rectifier module redundancy.
Product picture
Model | SPS30-48 /MR4815 | SPS60-48 /CR4830 | SPS90-48 /CR4830 | SPS120-48 /CR4830 | SPS200-48 /SR4850 | SPS250-48 /SR4850 | WPS30-48 /MR4815 | WPS60-48 /MR4815 |
Output Current | 30A | 60A | 90A | 120A | 200A | 250A | 30A | 60A |
Rated Output Power | 1740W | 3600W | 5400W | 7200W | 11600W | 14500W | 1740W | 3600W |
Rated Output Voltage | 53.5Vdc (42-58 Vdc) | |||||||
AC Input | ||||||||
AC Input Voltage Range | 176~300Vac, 1phase/3wire (@ full load) | |||||||
AC Input Frequency | 45Hz ~65Hz | |||||||
AC input Power Factor | ≥0.99 | |||||||
AC transfer Efficiency | ≥91% | ≥92% | ||||||
AC Input Lightening protection | NA | 1pc*50A/2P ClassC SPD | 1pc*63A/2P ClassC SPD | 1pc*100A/2P ClassC SPD | 1pc*100A/2P ClassC SPD | 1pc*30A/2P ClassC SPD | 1pc*30A/2P ClassC SPD | |
DC Output | ||||||||
Output Voltage Range | 42~58 Vdc | |||||||
Current Share | ±5% | |||||||
Load Regulation | ≤0.5% | |||||||
Voltage Regulation | ≤0.1% | |||||||
Environment | ||||||||
Operating Temperature | (-20 to 50°C) (Rectifier Temp Range: -45°C to 75°C) | |||||||
Relative Humidity | 5%~95% RH, No Condensation | |||||||
Configuration | ||||||||
Rectifier Module | 2*MR4815 | 2*CR4830 | 3*CR4830 | 4*CR4830 | 4*SR4850 | 5*SR4850 | 2*MR4815 | 4*MR4815 |
Controller | 1*CAS-03 | 1*CAS-03 | 1*CAS-03 | 1*CAS-03 | 1*CAS-03 | 1*CAS-03 | 1*CAS-03 | 1*CAS-03 |
DC Distribution | 1pc*30A | 1pc*60A | 4pcs*32A/1P 4pcs*16A/1P (customizable) | 2pcs*63A/1P 4pcs*32A/1P 4pcs*16A/1P (customizable) | 1st LVD: 1pc* 63A /1P 5pcs*32A/1P 2nd LVD: 2pcs*16A /1P 2pcs*32A/1P (customizable) | 4pcs*6A/1P 1pcs*16A/1P2pcs*20A/1P 2pcs*80A /1P (customizable) | 5pcs*16A /1P 1pcs*32A/1P (customizable) | 5pcs*16A /1P 1pcs*32A/1P (customizable) |
Battery Breaker | 1pc*30A | / | 2pcs*63A/1P or 1pc*100A/1P | 2pcs*100A/1P | 2pcs*100A/1P | 2pcs*125A/1P | 1pcs*32A/2P | 1pcs*32A/2P |
Alarm Relay | 4pcs | 4pcs | 4pcs | 4pcs | 4pcs | 4pcs | 4pcs | 4pcs |
Others | ||||||||
Standard | UL60950/EN60950, EN55022, RoHS | |||||||
Communication | LAN, RS232/RS485, Dry contact | |||||||
Dimension (mm) | 482*290*44 (Subrack) | 482*290*44 (Subrack) | 482*330*132 (Subrack) | 482*300*176 (Subrack) | 482*300*264 (Subrack) | 482*300*264 (Subrack) | 650*550*300 (wall-mount) IP45 | 650*550*320 (wall-mount) IP45 |
Optional | 2nd LVD, DC Lightning Protection at DC output | 2nd LVD, DC Lightning Protection | 2nd LVD, DC Lightning Protection | 2nd LVD, DC Lightning Protection | 2nd LVD, Teperature Compensation Cable, Lead-acid Battery 40Ah, Lithium Iron 40Ah |