China 35kw Water Cooled Cabinet Type Constant Temperature Precision Air Conditioner, Find details about China Air Conditioning, Packaged Air Conditioner from 35kw Water Cooled Cabinet Type Constant Temperature Precision Air Conditioner
Model SHKR- | 15WJH | 35WJH | 50WJH | 65WJH | 80WJH | |||||
Air flow direction | Top | Side | Top | Side | Top | Side | Top | Side | ||
Cooling Capacity | KW | 15 | 35 | 50 | 65 | 80 | ||||
Electric Heating Capacity | KW | 8 | 15 | 25 | 35 | 40 | ||||
Air flow | m³/h | 3000 | 5200 | 7800 | 105000 | 13000 | ||||
External static pressure | Pa | 150 | 0 | 150 | 0 | 200 | 0 | 200 | 250 | |
Running Noise | Db(A) | ≤64 | ≤62 | ≤68 | ≤66 | ≤70 | ≤68 | ≤72 | ≤72 | |
Capacity Control | % | 0,100 | 0,50,100 | 0,33,66,100 | 0,50,100 | 0,50,100 | ||||
Tempreture Control Range | ºC | Winter 18~23ºC±1ºC,Summer 22-23ºC±1ºC | ||||||||
Tempreture Control Range | % | 50~70±5 | ||||||||
Power Supply | 3Phase-380V-50Hz | |||||||||
Cooling power consumption | KW | 5.49 | 5.13 | 10.42 | 9.69 | 16.32 | 14.53 | 21.9 | 24.8 | |
Total consumption | KW | 16.33 | 16.21 | 31.1 | 60.68 | 52.61 | 80.87 | 68.24 | 75.89 | |
Refrigerant | R22 | |||||||||
Throttling | Externally balanced thermostatic expansion valve | |||||||||
Compressor | Type | Fully hermetic Scroll type | ||||||||
Evaprator | Type | Copper tube hydrophilic aluminum fin | ||||||||
Water-cooled condenser | Type | Shell and Tube type | ||||||||
Water Flow | m³/h | 3.9 | 7.6 | 10.7 | 14.6 | 17.5 | ||||
Water resistance | kPa | 22 | 29 | 31 | 34 | 35 | ||||
Pipe size | DN | 40 | 40 | 50 | 65 | 65 | ||||
Air-cooled condenser | Type | Copper tube hydrophilic aluminum fin | ||||||||
Fan Motor | KW | 0.24 | 0.6×2 | 0.6×2 | 0.8×2 | 0.8×2 | ||||
Fan | Type | Centrifugal,double inlet,Low noise | ||||||||
Drive | Belt Drive | |||||||||
Fan Motor | KW | 1.5 | 1.1 | 2.2 | 1.5 | 4 | 2.2 | 5.5 | 5.5 | |
Air Filter | Initial Effact(G4)+Medium effect(F8) | |||||||||
Humidifier | Type | Electrode steam | ||||||||
Humidification | KG/H | 4 | 8 | 15 | 15 | 15 |
Model SHKR/L- | 100WJH | 120WJH | 140WJH | 160WJH | 190WJH | 260WJH | ||
Air flow direction | Top | Top | Top | Top | Top | Top | ||
Cooling Capacity | KW | 100 | 120 | 140 | 160 | 190 | 260 | |
Electric Heating Capacity | KW | 45 | 50 | 55 | 60 | 70 | 80 | |
Air flow | m³/h | 16000 | 20000 | 22000 | 25000 | 30000 | 40000 | |
External static pressure | Pa | 300 | 350 | 350 | 350 | 400 | 450 | |
Running Noise | Db(A) | ≤75 | ≤76 | ≤77 | ≤79 | ≤80 | ≤82 | |
Capacity Control | % | 0,33,66,100 | 0,25,50,75,100 | Stepless control | ||||
Tempreture Control Range | ºC | Winter 18~23ºC±1ºC,Summer 22-23ºC±1ºC | ||||||
Tempreture Control Range | % | 50~70ºC±5ºC | ||||||
Power Supply | 3Phase-380V-50Hz | |||||||
Cooling power consumption | KW | 31.96 | 36 | 43.7 | 48.99 | 59.3 | 77 | |
Total consumption | KW | 88.32 | 103.4 | 116.2 | 163.6 | 163.7 | 191.8 | |
Refrigerant | R22 | |||||||
Throttling | Externally balanced thermostatic expansion valve | |||||||
Compressor | Type | Fully hermetic Scroll type | Screw Type | |||||
Evaprator | Type | Copper tube hydrophilic aluminum fin | ||||||
Water-cooled condenser | Type | Shell and Tube | ||||||
Water Flow | m³/h | 22.6 | 25.7 | 30.2 | 34 | 42.8 | 58.1 | |
Water resistance | kPa | 37 | 38 | 41 | 43 | 44 | 46 | |
Pipe size | DN | 65 | 80 | 80 | 80 | 100 | 100 | |
Air-cooled condenser | Type | Copper tube hydrophilic aluminum fin | ||||||
Fan Motor | KW | 0.8×3 | 0.8×3 | 0.8×4 | 0.8×4 | 0.8×6 | 0.8×6 | |
Fan | Type | Centrifugal,double inlet,Low noise | ||||||
Drive | Belt Drive | |||||||
Fan Motor | KW | 7.5 | 7.5 | 11 | 11 | 15 | 18.5 | |
Air Filter | Initial Effact(G4)+Medium effect(F8) | |||||||
Humidifier | Type | Electrode steam | ||||||
Humidification | KG/H | 15 | 23 | 23 | 32 | 45 | 45 | |
Note: | ||||||||
1. The norminal capacity is based on: Cooling: the temperature of the inlet dry/wet bulb is 23 °C/17 °C, and the temperature of the cooling water inlet and outlet is 30 °C/35 °C. Heating: The air inlet dry bulb temperature is 15 °C, and the steam pressure is 70Kpa. 2. The water-cooled unit is required to be equipped with a cooling tower. 3. The cooling power consumption does not include the auxiliary electric heating power. |