China 132kv Outdoor Porcelain Post Insulator for Substation, Find details about China Post Insulator, Substation Insulator from 132kv Outdoor Porcelain Post Insulator for Substation
Produce name | Rod type post insulator | Type | ZSW-132/6-4 |
Manufacturer | HEMG | Test type | Sampling test |
Sample number | 3 | Sample data | 2008/06/23 |
Sampling cardinal number | 21 | Lot number | 2008/6 |
Standard | IEC168 and product drawing | ||
Test item |
| ||
Test result | The test item of this lot product is 6, all the test result meeting the IEC168 standard and drawing requirement, and qualified. | ||
Remarks |
Sample serial number | Height | Creepage distance | Top part installation dimension | Bottom part installation dimension |
1 | 1200 | 3922 | 4*M12-¢140 | 4-¢18 - ¢225 |
2 | 1201 | 3918 | 4*M12-¢140 | 4-¢18 - ¢225 |
3 | 1200 | 3932 | 4*M12-¢140 | 4-¢18 - ¢225 |
Required value | 1200±2 | 3910 | 4*M12-¢140 | 4-¢18 - ¢225 |
Serial number | Min value of one sample | Min value of one sample | Average value | |||
Upper accessory | Lower accessory | Upper accessory | Lower accessory | Upper accessory | Lower accessory | |
1 | 72 | 78 | 90 | 89 | 89 | 88 |
2 | 74 | 75 | 89 | 88 | ||
3 | 72 | 76 | 88 | 87 | ||
Required value | ≮60 | ≮72 | ≮86 |
Serial number | Failing load value kN | Failing status |
1 | 7.8 | Porcelain fracture |
2 | 7.5 | Porcelain fracture |
Required value | ≥6 | / |
Serial number | Failing load value kN.m | Failing status |
3 | 3 | Porcelain not fracture |
Required value | ≥2 | / |