China Honny Power 3000kw Generator Diesel with Good Price, Find details about China 3000kw Generator, Generator 3000kw from Honny Power 3000kw Generator Diesel with Good Price
Genset Model | HGM3025E | |
Genset Prime Output | kW/kVA | 2200/2750 |
Genset Standby Output | kW/kVA | 2420/3025 |
Rating Power Factor | 0.8 | |
Rating Speed | rpm | 1500 |
Rating Frequency | Hz | 50 |
Rating Voltage | V | 400 |
Engine Model | QTA89E-G3 | |
Displacement | l | 88.5 |
Configuration | 20V | |
Genset Size-Open Type (LxWxH) | mm | 8000x2900x3500 |
Genset Weight | kg | 25000 |
Engine Model | QTA89E-G3 | |
Engine Standby Output (LTP) | kW | 2686 |
Engine Prime Output (PRP) | kW | 2442 |
Engine Continuous Power (COP) | kW | 2085 |
Typical Alternator Efficiency | 96% | |
Speed droop (static) elect. Gov. | 0-5% | |
Governing standards to ISO 8528 | G3 | |
Max. step load acceptance, 1st step(% PRP) | 45% | |
Engine Data in General | ||
Aspiration Type | Turbocharger, air-water aftercooler | |
Injection Type | Common Rail | |
Configuration | Vee | |
No. of Cylinders | 20 | |
Bore | mm | 170 |
Stroke | mm | 195 |
Compression Ratio | 13.5:1 | |
Piston Speed | m/s | 9.75 |
Rotation Direction (from flywheel) | Counter Clockwise | |
Number of Flywheel Teeth | 218 | |
Flywheel House Size | SAE00-21 | |
Lubrication System | ||
Lube Oil Specification | AFI-CG4 | |
Oil Capacity | l | 300 |
Max. Permissible Oil Temperature | °C | 110 |
Oil Pressure Warning | kPa | 300 |
Oil Pressure Shutdown | kPa | 200 |
Oil Consumption (as % of fuel consumption ) | % | ≤0.5 |
Cooling System | ||
Coolant Capacity for Engine | l | 200 |
Max. Permissible Temperature | °C | 90 |
Max. Coolant Warning Temperature | °C | 95 |
Max. Coolant Shutdown Temperature | °C | 98 |
Thermostat Open Temperature | °C | 71 |
Radiator Cooling Flow | m³/min | 3800 |
Flow of Cylinder Liner Coolant Pump | m³/h | 75 |
Flow of aftercooler Coolant pump | m³/h | 90 |
Heat dissipation (engine radiator) | kW | 916 |
Heat dissipaton (CAC) | kW | 550 |
Heat dissipation (convection) | kW | 147 |
Fuel System | ||
Governor Type | Common Rail | |
Fuel Consumption at 25% of genset prime output | l/h | 171 |
Fuel Consumption at 50% of genset prime output | l/h | 199 |
Fuel Consumption at 75% of genset prime output | l/h | 427 |
Fuel Consumption at 100% of genset prime output | l/h | 562 |
Lowest Fuel Consumption Ratio | g/kW.hr | 192 |
Intake & Exhaust System (On Standby Output) | ||
Combustion Air Consumption | m³/min | 275 |
Max. Intake Restriction | KPa | 5 |
Exhaust Temperature (Before Turbo) | °C | 660 |
Exhaust Temperature (After Turbo) | °C | 540 |
Max. Exhaust Back Pressure | Kpa | 5 |
Exhaust Gas Flow | m³/min | 685 |
Turbo Bellows Diameter | mm | DN250 |
Exhaust Flange Diameter | mm | DN250 |
Electrical System | ||
Charging Alternator Voltage | V | 28 |
Charging Alternator Capacity | A | 55 |
Starting Voltage | V | 24 |
Starting Motor Capacity | kW | 2*13 |
Minimum Battery Capacity | Ah | 4*200 |
Emission Data | ||
CO | g/kW.h | 0.738 |
HC+NOx | g/kW.h | 5.359 |
PM | g/kW.h | 0.092 |
Generator-Googol Power | ||
Generator Model | GP2750-4P | |
Capacity @ 0.8PF, H Rise Class | kW | 2200 |
Efficiency @ 0.8PF | % | 96 |
Duty | S1 | |
Bearing | Double | |
Insulation | H | |
Rise Temperature | H | |
Enclosure | IP23 | |
Over speed | rpm | 2250 |
Excitation System | AVR | |
AVR Model | MX321 | |
Poles | 4 |