China 1kVA High Frequency Online UPS, Find details about China UPS, UPS Power from 1kVA High Frequency Online UPS
Specifications: | ||||
Model | CX1K | CX1KL | ||
Capacity | VA/W | 1000VA/800W | ||
Input | Nominal Voltage | 200/208/220/230/240VAC | ||
Voltage Range | 115~300VAC | |||
Harmonic Distortion | <10% (Nonlinear load) | |||
Power Factor | 0.98 | |||
Frequency Range | 50Hz:46~54Hz; 60Hz:56~64Hz | |||
Output | Voltage | 200/208/220/230/240(1±1%)VAC | ||
Frequency | 50/60Hz (Adjustable); 50Hz AC Mode: Follow AC Mode (AC Range 46~54Hz); Battery Mode: 50Hz (1±0.2%) 60Hz AC Mode: Follow AC Mode (AC Range 56~64Hz); Battery Mode: 60Hz (1±0.2%) | |||
Wave Form | Pure sine wave | |||
Power Factor | 0.8 | |||
Harmonic Distortion | ≤4% (Linear load); ≤7% (Nonlinear load) | |||
Overload Capacity | 105%~150% 45S~25S; 150%~200% 25s~300ms; ≥200% 200ms | |||
Current Crest Ratio | 3∶1 | |||
Connections | IEC320*4 | |||
Efficiency | Battery Mode | 81% | ||
AC Mode | 85% | |||
Battery | Type | Sealed free maintenance lead acid battery | ||
Nominal DC voltage | 24VDC | 36VDC | ||
Quantity | 12VDC×2 | 12VDC×3 | ||
Backup Time (Full Load) | >2.5min (Built in batteries12V7AH) | Depends on requested Back-up time | ||
Charge Current (Max) | 1A | 5A | ||
Charge Voltage (VDC) | 27.4V±0.2VDC | 41.1V±0.2VDC | ||
Recharge Time | 7 hours filling to 90% (standard) | Depends on external battery capacity (long-term) | ||
Bypass | Automatic Transfer | On overload and UPS failure | ||
Before UPS Power-on | Default "ON" user adjustable to "YES" | |||
Transfer Time | 0 ms; Less than 4ms from inverter to bypass and vice versa | |||
indicators | LCD Display | UPS status, Battery capacity, loading, Fault code (LCD: I/P &O/P voltage&frequency, Battery voltage) | ||
Audible | Bypass, On battery mode, Battery low, Overload, Fault | |||
Acoustic Noise | At 1 Meter Distance | <45dB | ||
Communications | Intelligent RS232 serial port | Software support Windows family software, Linux, Sun network operating system, IBM Aix, Compaq True64 SGI IRIX, FreeBSD, HP-UX and MAC | ||
SNMP (Optional) | Remote control UPS through SNMP management and Internet | |||
USB (Optional) | Windows family software and Mac OS | |||
Environmental | Operating Temperature | 0~40ºC | ||
Operating Humidity | 20~90% (No condensing) | |||
Physical Parameter | L*W*H (mm) | 373*145*219 | ||
Net Weight (Kgs) | 9.5 | 5 |