MODEL (GW Series) | HV/LV Model | ||||
HV Model(1-12KW) LV Model(1-6KW) | |||||
Line Mode Specifications: | |||||
Input Voltage | Input Voltage Waveform | Sinusoidal (utility or generator) | |||
Nominal Input Voltage | LV 120Vac | HV 230Vac | |||
Low Line Disconnect | Normal:85Vac±4% Wide:80Vac±4% | Normal:184Vac±4% Wide:135Vac±4% | |||
Low Line Re-connect | Normal:95Vac±4% Wide:85Vac±4% | Normal:194Vac±4% Wide:145Vac±4% | |||
High Line Disconnect | Normal:136Vac±4% Wide:140Vac±4% | Normal:263Vac±4% Wide:263Vac±4% | |||
High Line Re-connect | Normal:131Vac±4% Wide:135Vac±4% | Normal:253Vac±4% Wide:253Vac±4% | |||
Max AC Input Voltage | 150Vrms | 270Vrms | |||
Input Frequency | Nominal Input Frequency | 50Hz/ 60Hz (Auto detection) | |||
Low Line Frequency Re-connect | 51+0.3Hz for 60Hz; 41+0.3Hz for 50Hz; | ||||
Low Line Frequency Disconnect | 50+0.3Hz for 60Hz; 40+0.3Hz for 50Hz; | ||||
High Line Frequency Re-connect | 64+0.3Hz for 60Hz; 54+0.3Hz for 50Hz; | ||||
High Line Frequency Disconnect | 65+0.3Hz for 60Hz; 55+0.3Hz for 50Hz; | ||||
main functions | Output Voltage Waveform | As same as Input Waveform | |||
Over-Load Protection (SMPS load) | Air switch | ||||
Output Short Circuit Protection | Air switch | ||||
Max Bypass Overload Current | 30A/40A/50A | ||||
Battery Invert Mode Specifications: | |||||
output | Output Voltage Waveform | Sine wave | |||
Rated Output Power (KW) | LV:1~6KW | HV: 1~12KW | |||
Power Factor | 0.9~1.0 | ||||
Nominal Output Voltage (V) | LV:120Vac ±10%rms | HV:230Vac ±10%rms | |||
Nominal Output Frequency (Hz) | 60Hz ± 0.3Hz 50Hz ± 0.3Hz | ||||
DC Voltage | Nominal DC Input Voltage | 12VDC/24VDC/48VDC | |||
DC Voltage range | 10-15.5Vdc for 12VDC 20-31.0Vdc for 24VDC 40-62.0Vdc for 48VDC | ||||
Low Battery Alarm | 10.5Vdc ± 0.3Vdc for 12V battery 21.0Vdc ± 0.6Vdc for 24V battery 42.0Vdc ± 1.2Vdc for 48V battery | ||||
Low DC input Shut-down | 10.0Vdc ± 0.3Vdc for 12V battery 20.0vdc± 0.6Vdc for 24V battery 40.0Vdc ± 1.2Vdc for 48V battery | ||||
High DC input Alarm & Fault | 16Vdc ± 0.3Vdc for 12V battery 32Vdc ± 0.6Vdc for 24V battery 64Vdc ± 1.2Vdc for 48V battery | ||||
High DC input Recovery | 15.5Vdc ± 0.3Vdc for 12V battery 31.0Vdc ± 0.6Vdc for 24V battery 62.0Vdc ± 1.2Vdc for 48V battery | ||||
AC Charger | Nominal Charge Current | 20A/35A/50A/70A/90A(5 stages adjustable charging current) | |||
Charge Current Regulation | ± 5Adc | ||||
Over Charge Protection | Bat.V≥15.5VDC for 12V battery Bat.V≥31.0VDC for 24V battery Bat.V≥62.0VDC for 48V battery beeps 0.5s every 1s & fault after 60s | ||||
Algorithm | Three stage: Boost CC (constant current stage) → Boost CV (constant voltage stage) → Float (constant voltage stage) | ||||
Solar charger | Rated Charge Current | 40A | 60A | ||
Rated charge battery Voltage type | 12V/24V/48V | 12V/24V | |||
Max.PV open circuit array voltage | 12V for 40Vdc 24V for 55Vdc 48V for 110Vdc | ||||
Charger mode | MPPT | ||||
PV Low Voltage Re-connect | PV≥Bat.V=3V | ||||
PV Low Voltage Disconnect | PV<=Bat.V | ||||
Efficiency | ≥97% | ||||
Efficiency | Efficiency (Battery Mode) | ≥85% | |||
Efficiency (Line Mode) | >98% | ||||
Transfer Time | Ac to Dc | 20ms (Max) | |||
Dc to Ac | 15ms (Max) | ||||
System parameter | Over-Load Protection | 110% <load<150%, beeps 0.5s every 1s, and Fault after 60s off the output, Load>150%, beeps 0.5s every 1s, and Fault after 20s. | |||
Output Short Circuit Protection | Current limit (Fault after 10s) | ||||
Surge rating (10s) | 1:3 (VA) | ||||
Power saver | Load <=25W (Enabled on "P/S auto" setting of Remote control) | ||||
Protections | Low battery, over charging, over load , over temp. | ||||
Indicators | LED+LCD Display | ||||
General Specifications | Operating Temperature Range | 0°C to 40°C | |||
Storage temperature | -15ºC ~60ºC | ||||
Operation humidity | 5% to 95%(non-condensing) | ||||
Audible Noise | 60dB max |