Variable Frequency Resonant AC Hipot Tester for Cable Test

China Variable Frequency Resonant AC Hipot Tester for Cable Test, Find details about China Resonant Hipot Tester, AC Hipot Test Set from Variable Frequency Resonant AC Hipot Tester for Cable Test

Model NO.
NRXZ
Power Source
AC 220V / 380V
Rated Capacity
5-500kw, Can Be Customized
Input Voltage
Three-Phase 380V / Single-Phase 220V, 45-65h
Output Voltage Frequency
30 - 300Hz
Rated Voltage
0 - 1000kv, Can Be Customized
Rated Current
1 - 10A, Can Be Customized
Output Waveform
Sine Wave
Temperature Range
-10ºC ~ 50ºC
Relative Humidity
< 90%Rh
Altitude
<1000m
Trademark
NANR
Transport Package
Plywood Case
Origin
Wuhan China
HS Code
9030390000
Model NO.
NRXZ
Power Source
AC 220V / 380V
Rated Capacity
5-500kw, Can Be Customized
Input Voltage
Three-Phase 380V / Single-Phase 220V, 45-65h
Output Voltage Frequency
30 - 300Hz
Rated Voltage
0 - 1000kv, Can Be Customized
Rated Current
1 - 10A, Can Be Customized
Output Waveform
Sine Wave
Temperature Range
-10ºC ~ 50ºC
Relative Humidity
< 90%Rh
Altitude
<1000m
Trademark
NANR
Transport Package
Plywood Case
Origin
Wuhan China
HS Code
9030390000
1. Product Introduction

NRXZ Series Variable Frequency Resonant AC Hipot Tester is mainly designed for AC withstand voltage test of primary electrical equipment in substation, such as transformer, GIS system, SF6 switch, cable, bushing and other capacitive equipment. The reactor uses separate design, not only can meet the requirements of high voltage and low current devices, but also meet the test requirements of low voltage and high current devices, with a wide scope, it is an idea withstand voltage equipment for high voltage test department and electrical installation, maintenance engineering units.

Variable Frequency Resonant AC Hipot Tester for Cable Test
2. Technical parameters

3.1 Operating condition
(1) Temperature: -10ºC ~ 50ºC
(2) Relative humidity: ≤ 90%RH;
(3) Altitude: ≤ 1000m
3.2 Inverter power supply (1 piece)
(1) Rated power: 5-500kW;
(2) Input voltage: Three-phase 380V±5% or single-phase 220V±5% 45~65Hz. When the power supply is 380V, rated load test can be done; when the power supply is 220V, only 1/2 load test can be done.
(3) Output voltage: 0~400V adjustable
(4) Output voltage frequency: 20~300Hz
(5) Frequency adjustment: 0.1Hz step adjustable
(6) Frequency instability: ≤ 0.02%
(7) Output current: 13~1250A
3.3 High voltage reactor (several pieces)
(1) Rated working voltage: 0~1000kV
(2) Rated working current: 1~10A
(3) Rated inductance: 30~600H
(4) Continuous working time: 15min
(5) Temperature rise: less than 60ºC
(6) Working frequency: 20~300Hz
3.4 Excitation Transformer
(1) Rated capacity: 3.5~500kVA
(2) Input voltage: when the capacity is 5.5~20kW, the input voltage is 200V/400V
When the capacity is 20~500kW, the input voltage is 400V
3.4. Capacitor voltage divider (one set):
(1) Capacitance: 300~5000pF
(2) Rated voltage: 10~1000kV
(3) Working frequency: 20~300Hz
(4) Accuracy: 1.0%


3. Product characteristics

1) The instrument has the functions of over-voltage, over-current, zero-position start-up, system detuning (flash-over), sectional voltage output, each sectional voltage can be preset test time independently.
2) The instrument adopts 7-inch or 10-inch touchable LCD screen, the contactor and circuit breaker of Schneider or ABB.
3) The test data can be real time printed and stored.
4) Its output circuit is equipped with special contactor, which can eliminate potential danger ultimately when touch the output line after shutdown.

5) Inputting wide range of voltage and frequency, 50Hz-60Hz frequency self-adaptive, allow our instrument to work reliably both on generator and industrial power supply.
6) Here are four operating modes for the instrument with wide frequency modulation output(20~350Hz), which is not only money saved and also reliable for use, easy to carry. The working modes are: fully automatic mode, manual mode, automatic frequency searching mode and online mode.
7) Multiple inverter power supplies can be parallel output, which allowing different time purchased inverter power supplies paralleled as a big power single power supply to use. There's no need to purchase extra-large power inverter power supply. This function was pioneered by our company, which is money saved for customer.

4. Patent Certificate

As a professional manufacturer of Variable Frequency Resonant AC Hipot Tester, we have professional R&D team to master the core technology, we had awarded the design patent certificate in 2016.
Variable Frequency Resonant AC Hipot Tester for Cable Test
Variable Frequency Resonant AC Hipot Tester for Cable Test
Variable Frequency Resonant AC Hipot Tester for Cable Test
Variable Frequency Resonant AC Hipot Tester for Cable Test
Variable Frequency Resonant AC Hipot Tester for Cable TestVariable Frequency Resonant AC Hipot Tester for Cable TestVariable Frequency Resonant AC Hipot Tester for Cable Test
Variable Frequency Resonant AC Hipot Tester for Cable TestVariable Frequency Resonant AC Hipot Tester for Cable Test