60kVA Industrial Heavy Duty Transformer Based Three Phase 3pH Low Frequency Online UPS

China 60kVA Industrial Heavy Duty Transformer Based Three Phase 3pH Low Frequency Online UPS, Find details about China UPS, Low Frequency Online UPS from 60kVA Industrial Heavy Duty Transformer Based Three Phase 3pH Low Frequency Online UPS

Model NO.
M33 40-60K
Standby UPS
Sine Wave Output UPS
Output Capacity
Large Type
Equipment Mode
Decentralized
Brand
Kemapower
Power Source
Electric Power
Product Name
M33 40K-60K Low Frequency Online UPS
Trademark
KEMAPOWER
Transport Package
Safety Packing
Specification
M33-40-60K
Origin
China
HS Code
8504402000
Model NO.
M33 40-60K
Standby UPS
Sine Wave Output UPS
Output Capacity
Large Type
Equipment Mode
Decentralized
Brand
Kemapower
Power Source
Electric Power
Product Name
M33 40K-60K Low Frequency Online UPS
Trademark
KEMAPOWER
Transport Package
Safety Packing
Specification
M33-40-60K
Origin
China
HS Code
8504402000
M33 40K-60K Low Frequency Online UPS

* I/P: 220△/ 380△ / 460△, 208VY/ 380VY, 400VY, 415VY

* O/P:220△/ 380△ / 460△, 208VY/ 380VY, 400VY, 415VY ± 1%

* Capacity:40K/50K/60K

* Output PF: 0.8

* Wave Form:Pure sine wave

* Transfer Time:0 ms

* DC Voltage::384VDC(10K -- 80KVA),396VDC(100K--200KVA)

* Bat.:External Batteries

* Charge Current: 6-30A adjustable



Key features

♦Low frequency three phase on-line double conversion ups 10KVA--400KVA

♦220/380VAC 3P+N+G,110V/208VAC 3P+G optional

♦7 inche touch panel,display detailed running parameter and set the UPS work mode

♦DSP Controlled IGBT inverter

♦Setable UPS/ECO/INVERTER working mode

♦Event log by LCD panel

♦Three-phase separately adjustment to meet 100% unbalance loads

♦Cold start fuction and Auto restarting when mains resume

♦Full protection,overload,over voltage,short circuit,over temperature etc.

♦Static bypass and manual maintenance bypass

♦Advanced Battery Management,temperature compensation charging,setable charge current

♦Automatic charging in UPS off mode

♦RS-232 and Rs485 communication, SNMP or Dry Contact is option

♦Optional input harmonic filter or 12 pulse wave rectifier

♦Optional battery detection modules for per Cell battery

♦Option EPO function

♦Option parallel redundancy



Technical  specifications
Mode M33-40KM33-50KM33-60K
Nominal capacityKVA 405060
KW 324048
RECTIFIER (INPUT)Phase numberThree Phase
Input power factorStandard >= 0.9 ( 6pulse Rectifier+Filter ),  Optional >= 0.96 ( 12pulse Rectifier+Filter)
Input voltage220/380VAC (230V/400VAC or 240V/415VAC)±25% 3P+N+PE
    110V/208VAC( 120V/220VAC or  277V/480VAC ) optional
Input frequency50Hz±10% or 60Hz±10% (Selectable)
Total Harmonic Distortion (THDi)6pulse Rectifier<30%, Optional 12pulse Rectifier & Filter<5%
Output ripple wave<2%
Soft start0-100% 5sec
ChargingCharge modeConstant current, then constant voltage, charge with temperature compensation, automatic
switch Between Equalized charging and Float charging,
Folat charging voltage432VDC
Equalized charging voltage464VDC
Temeperature compensation voltage-3mV/ºC/cell
Charging current0.1C(Automatic adjust according to battery capacity)
Charging power20% of rated capacity
BatteryType VRLA/AGM/Gel, optional Lithium Battery
Capacity7~999AH settable (Configurate Battery Capacity according to Back-up Time)
Battery number32units 12V or 192units 2V batteries (Nominal Voltage 384VDC)
InvertorPhase numberThree Phase
Rated powerRated capacity*0.9
Nominal voltage220/380VAC (230V/400VAC or 240V/415VAC), 3P+N
110V/208VAC( 120V/220VAC or  277V/480VAC )  optional
Output voltage stability±1%( Stable load), ±3%( fluctuant load)
Frequency stability50Hz 60Hz<±0.5% ( Asynchronous )
Factor of wave crest>3:1
Output waveform distortion degreePure Sine Wave, Linear Load< 3%, Non-Linear Load<5%
Dynamic featureInstant voltage<±5% ( from 0 to100% ), Instant recover time<10ms
Unbalance load voltage<±5%
Overload protectionAt 115% load, normal work, At 125% load 10 min, At 150% load 1min, At 200% load 1S
Invertor efficiency>92%(full load)
BypassPhase number3 phase+N
Input nominal voltage220/380VAC (230V/400VAC or 240V/415VAC)  
110V/208VAC( 120V/220VAC or  277V/480VAC )optional
Output nominal voltage220/380VAC (230V/400VAC or 240V/415VAC)  
110V/208VAC( 120V/220VAC or  277V/480VAC ) optional
Switching time0ms(adopted static switch)
Protection FunctionInput protectionInput voltage, frequency over limited protection, Phase fault, Phase lack
Output prorectionOver current, short circuit, over voltage, low voltage
Battery protectionOver charge, over-discharge protection
Overheat protectionEnvironment over temperature protection, inverter over temperature protection
Hardware fault protectionAssistant power abnormal, breaker cut off, breaker overload, power devices over current/over voltage etc protection
SYSTEM PARAMETERSWork environmentTemp: -10~40ºC, relative humidity: 30%~90%, Altitude<2000m ( 1% decrease against 100
meters' rise, max. altitude 4000m )
Cooling method forced cooling
Communitation interfaceRS232/ RS485, optional dry contact, SNMP card ( for remote control via Internet)
Parallel operationTandem hot backup or parallel connection
Anti-surge capacity10/700μS, 5KV;  8/20μS, 20KA
Protection levellp31
Safety performanceVin-n Vout-n 3000Vac, creepage<3.5mA , insulating resistance>2MΩ(500VDC)
Noise(Db)48-55
Mechanical dimension(W*D*H)mm600*720*1500
Weight(Kg)342385402
Remark:all specification subject to change without notice,customer-made specification are acceptable