M33 40kVA-60kVA Sine Wave Industrial Low Frequency Double Conversion UPS

China M33 40kVA-60kVA Sine Wave Industrial Low Frequency Double Conversion UPS, Find details about China UPS, Low Frequency Online UPS from M33 40kVA-60kVA Sine Wave Industrial Low Frequency Double Conversion UPS

Model NO.
M33 40-60K
Standby UPS
Sine Wave Output UPS
Output Capacity
Large Type
Equipment Mode
Decentralized
Brand
Kemapower
Power Source
Electric Power
Product Name
M33 40K-60K Low Frequency Online UPS
Trademark
KEMAPOWER
Transport Package
Safety Packing
Specification
M33-40-60K
Origin
China
HS Code
8504402000
Model NO.
M33 40-60K
Standby UPS
Sine Wave Output UPS
Output Capacity
Large Type
Equipment Mode
Decentralized
Brand
Kemapower
Power Source
Electric Power
Product Name
M33 40K-60K Low Frequency Online UPS
Trademark
KEMAPOWER
Transport Package
Safety Packing
Specification
M33-40-60K
Origin
China
HS Code
8504402000
M33 40K-60K Low Frequency Online UPS

* I/P: 220△/ 380△ / 460△, 208VY/ 380VY, 400VY, 415VY

* O/P:220△/ 380△ / 460△, 208VY/ 380VY, 400VY, 415VY ± 1%

* Capacity:40K/50K/60K

* Output PF: 0.8

* Wave Form:Pure sine wave

* Transfer Time:0 ms

* DC Voltage::384VDC(10K -- 80KVA),396VDC(100K--200KVA)

* Bat.:External Batteries

* Charge Current: 6-30A adjustable



Key features

♦Low frequency three phase on-line double conversion ups 10KVA--400KVA

♦220/380VAC 3P+N+G,110V/208VAC 3P+G optional

♦7 inche touch panel,display detailed running parameter and set the UPS work mode

♦DSP Controlled IGBT inverter

♦Setable UPS/ECO/INVERTER working mode

♦Event log by LCD panel

♦Three-phase separately adjustment to meet 100% unbalance loads

♦Cold start fuction and Auto restarting when mains resume

♦Full protection,overload,over voltage,short circuit,over temperature etc.

♦Static bypass and manual maintenance bypass

♦Advanced Battery Management,temperature compensation charging,setable charge current

♦Automatic charging in UPS off mode

♦RS-232 and Rs485 communication, SNMP or Dry Contact is option

♦Optional input harmonic filter or 12 pulse wave rectifier

♦Optional battery detection modules for per Cell battery

♦Option EPO function

♦Option parallel redundancy



Technical  specifications
Mode M33-40KM33-50KM33-60K
Nominal capacityKVA 405060
KW 324048
RECTIFIER (INPUT)Phase numberThree Phase
Input power factorStandard >= 0.9 ( 6pulse Rectifier+Filter ),  Optional >= 0.96 ( 12pulse Rectifier+Filter)
Input voltage220/380VAC (230V/400VAC or 240V/415VAC)±25% 3P+N+PE
    110V/208VAC( 120V/220VAC or  277V/480VAC ) optional
Input frequency50Hz±10% or 60Hz±10% (Selectable)
Total Harmonic Distortion (THDi)6pulse Rectifier<30%, Optional 12pulse Rectifier & Filter<5%
Output ripple wave<2%
Soft start0-100% 5sec
ChargingCharge modeConstant current, then constant voltage, charge with temperature compensation, automatic
switch Between Equalized charging and Float charging,
Folat charging voltage432VDC
Equalized charging voltage464VDC
Temeperature compensation voltage-3mV/ºC/cell
Charging current0.1C(Automatic adjust according to battery capacity)
Charging power20% of rated capacity
BatteryType VRLA/AGM/Gel, optional Lithium Battery
Capacity7~999AH settable (Configurate Battery Capacity according to Back-up Time)
Battery number32units 12V or 192units 2V batteries (Nominal Voltage 384VDC)
InvertorPhase numberThree Phase
Rated powerRated capacity*0.9
Nominal voltage220/380VAC (230V/400VAC or 240V/415VAC), 3P+N
110V/208VAC( 120V/220VAC or  277V/480VAC )  optional
Output voltage stability±1%( Stable load), ±3%( fluctuant load)
Frequency stability50Hz 60Hz<±0.5% ( Asynchronous )
Factor of wave crest>3:1
Output waveform distortion degreePure Sine Wave, Linear Load< 3%, Non-Linear Load<5%
Dynamic featureInstant voltage<±5% ( from 0 to100% ), Instant recover time<10ms
Unbalance load voltage<±5%
Overload protectionAt 115% load, normal work, At 125% load 10 min, At 150% load 1min, At 200% load 1S
Invertor efficiency>92%(full load)
BypassPhase number3 phase+N
Input nominal voltage220/380VAC (230V/400VAC or 240V/415VAC)  
110V/208VAC( 120V/220VAC or  277V/480VAC )optional
Output nominal voltage220/380VAC (230V/400VAC or 240V/415VAC)  
110V/208VAC( 120V/220VAC or  277V/480VAC ) optional
Switching time0ms(adopted static switch)
Protection FunctionInput protectionInput voltage, frequency over limited protection, Phase fault, Phase lack
Output prorectionOver current, short circuit, over voltage, low voltage
Battery protectionOver charge, over-discharge protection
Overheat protectionEnvironment over temperature protection, inverter over temperature protection
Hardware fault protectionAssistant power abnormal, breaker cut off, breaker overload, power devices over current/over voltage etc protection
SYSTEM PARAMETERSWork environmentTemp: -10~40ºC, relative humidity: 30%~90%, Altitude<2000m ( 1% decrease against 100
meters' rise, max. altitude 4000m )
Cooling method forced cooling
Communitation interfaceRS232/ RS485, optional dry contact, SNMP card ( for remote control via Internet)
Parallel operationTandem hot backup or parallel connection
Anti-surge capacity10/700μS, 5KV;  8/20μS, 20KA
Protection levellp31
Safety performanceVin-n Vout-n 3000Vac, creepage<3.5mA , insulating resistance>2MΩ(500VDC)
Noise(Db)48-55
Mechanical dimension(W*D*H)mm600*720*1500
Weight(Kg)342385402
Remark:all specification subject to change without notice,customer-made specification are acceptable