China Water to Air Glycol Air Fin Dry Coolers, Find details about China Dry Cooler, Dry Air Cooler from Water to Air Glycol Air Fin Dry Coolers
Products Features
1. Condensers are the first choice of refrigeraion and AC industry. Condenser with a capacity 8kW~1800kW and surface 20~4100 square meter which has wide application range. It is flexible to match which different size of compressor. Use low specific energy consumption fans, high efficiency inner groove copper tube and sine wave aluminum fin. Durable material with slim but rigid enclosure hard gloss powder coated sheet metal offers corrosion proof under hostile environment. There are top air outlet or side air outlet construct for C1 series, "V" type for C2 series. C2 float coil can prevent refrigerant leakage effictively, it ensures a durable and safety finned heat exchanger.
2. High efficiency heat exchanger: capacity designs for maximizing the heat transfer relative to the energy consumption of the fan. Tube and tube coupling design for low pressure drop in the coil on the media sides(maximum 100KPa at water designing condition). Our thermodynamic and aerodynamic designing software is long year tested and proved in Germany
3. Fan: only choose low specific energy consumption fans. Fan nozzle designs for maximum air flow and air throw.Our fans from the world`s leading manufacturer are practically proved to be reliable in operation and long lasting. Motor: protection class IP 54 and insulation class F. Air separator for each fan.
4. We facilitate you to have a long lasting and low maintainance operation. Durable material and rigid enclosure with hard gloss powder coated finish. Protective enclosure for both manifolds and U-bends. Unit design for outdoor installation. 100% leakage tested at 31bar.
Options
1. Coil design refrigerant: R414A, R407C
2. Multiple circuits.
3. Sub-cooling circuits.
4. Stainless steel or aluminum casing.
5. Coated aluminum, copper fins and anti-corrosion expoxy fin.
6. Explosion ploof motor.
7. Customized fin spacing.
Condition
Air inlet temp. 25ºC; condensing temp. 40ºC; refrigerant inlot temp. 65ºC; liquid sub-cooling 3K; relative humidity 40%; atmosphere pressure 1 bar(sea level)
Technical parameter
Air cooled condenser C2 series parameter(fin space 2.1mm)
Paramaters:
SHSL-D1 series (fin space 2.1mm)
Type | SHSL-D1-005-1x350 | SHSL-D1-006-1x350 | SHSL-D1-007-1x350 | SHSL-D1-009-1x450 | SHSL-D1-011-1x450 | SHSL-D1-013-1x450 | SHSL-D1-014-1x500 | SHSL-D1-017-1x500 | SHSL-D1-020-1x500 | ||||||
Capacity | Water | 35ºC outdoor temp. | Inlet | 45ºC, |
| KW | 4.89 | 5.90 | 6.83 | 9.39 | 10.99 | 13.33 | 14.32 | 17.01 | 19.80 |
outlet | 40ºC | Y | |||||||||||||
20% Glycol | Inlet | 45ºC |
| 4.72 | 5.69 | 6.69 | 8.90 | 10.61 | 13.05 | 13.91 | 16.11 | 19.29 | |||
outlet | 40ºC | Y | |||||||||||||
Medium | Water flow | M3/h | 0.85 | 1.03 | 1.20 | 1.63 | 1.91 | 2.30 | 2.50 | 3.00 | 3.50 | ||||
Pressure drop | kPa | 36.00 | 31.00 | 58.00 | 25.00 | 40 | 80 | 50 | 60 | 40 | |||||
Air flow |
| M3/h | 2828 | 2712 | 2492 | 6199 | 5827 | 5225 | 8469 | 8168 | 7601 | ||||
Y | |||||||||||||||
Fan motor | Phase | 1 | 1 | 1 | 3 | 3 | 3 | 3 | 3 | 3 | |||||
| W | 140 | 140 | 140 | 540 | 540 | 540 | 830 | 830 | 830 | |||||
Y | |||||||||||||||
| A | 0.60 | 0.60 | 0.60 | 1.10 | 1.10 | 1.10 | 1.45 | 1.45 | 1.45 | |||||
Y | |||||||||||||||
Fan | No X φ | 1x1x350 | 1x1x350 | 1x1x350 | 1x1x450 | 1x1x450 | 1x1x450 | 1x1x500 | 1x1x500 | 1x1x500 | |||||
Sound pressure level |
| dB(A) | 31 | 31 | 31 | 43 | 43 | 43 | 49 | 49 | 49 | ||||
Y | 10m |
Application
Industrial field: process engineering, heat / power plant, power generation, chemical industry, air conditioning chiller, heat transformer, smelting, etc.. It is suitable for all equipment which needs heat dissipation and is installed in the open air.
Sucessful case: