China Drnl 1p+N RCD Earth Leakage Circuit Breaker 30mA ELCB 1p+N, Find details about China Earth Leakage Circuit Breaker, ELCB from Drnl 1p+N RCD Earth Leakage Circuit Breaker 30mA ELCB 1p+N
Technical Data | SDRNL (SAA) |
Standards | AS/NZS 61009 - 1 |
Magnetic tripping characteristics | B,C |
Residual tripping characteristics | A , AC |
Rated current(A) | 6, 10, 16, 25,32 |
Rated residual current | 10mA, 30 mA, 100mA |
Calibration temperature | 30ºC |
Rated voltage 1P | 240V |
Frequency | 50/60 |
Maximum service voltage | 264 |
Tripping Duration: | Instaneous<0.1s |
Power supply | Top or bottom |
Selectivity class | 3 |
Residual making and breaking capacity | 2000A |
Short circuit capacity | 6000A |
Isolation application (IEC 60947-2) | Yes |
Insulation resistance (Mohm) | 1,000 |
Insulation voltage (V) | 500 |
Dielectric rigidity (V) | 2,500 |
Vibration resistance | 1.5g |
Endurance (operations) electrical | >6,000 |
mechanical | >20,000 |
Protection degree outside | IP20 |
inside enclosure | IP40 |
Self extinguishing degree (UL 94) | V2 |
Tropicalisation (IEC 60068-2) | +55ºC/95% RH |
Operating temperature | -5/+55ºC |
Storage temperature | -25/+70ºC |
Terminal capacity (top & bottom) min / max | 1-16mm |
Terminal torque (top / bottom) | 3 |
Busbar systems | Yes |
Accessories | No |
Dimensions (mm) | 72(H)81(L)18(W) |
Weight (g) | 105 |
Standards | AS/NZS 61009 - 1 |
Magnetic tripping characteristics | B,C, D |
Residual tripping characteristics | AC |
Rated current(A) | 6,10,16,20,25,32 |
Rated residual current(mA) | 30, 100,300 |
Calibration temperature | 30ºC |
Rated voltage 1P | 240V |
Frequency | 50/60 |
Maximum service voltage | 264 |
Tripping duration: | Instaneous<0.1s |
Power supply | Line & Load |
Selectivity class | 3 |
Residual making and breaking capacity | 2000A |
Short circuit capacity | 10000A |
Isolation application (IEC 60947-2) | Yes |
Insulation resistance (Mohm) | 1,000 |
Insulation voltage (V) | 500 |
Dielectric rigidity (V) | 2,500 |
Vibration resistance | 1.5g |
Endurance (operations) electrical | >4,000 |
mechanical | >20,000 |
Protection degree outside | IP20 |
inside enclosure | IP40 |
Self extinguishing degree (UL 94) | V2 |
Tropicalisation (IEC 60068-2) | +55ºC/95% RH |
Operating temperature | -5/+55ºC |
Storage temperature | -25/+70ºC |
Terminal capacity (top & bottom) min / max | 1-16mm |
Terminal torque (top / bottom) | 3 |
Busbar systems | Yes |
Accessories | No |
Dimensions (mm) | 72(H)81(L)18(W) |
Weight (g) | 105 |
Electrical features | Rated current In | A | 6A,10A 16A 20A 32A 40A, 50A, 63A |
Poles | P | 1.2.3.4 | |
Rated voltage Ue | V | 240/415 | |
Insulation voltage Ui | V | 500 | |
Rated frequency | Hz | 50/60 | |
Rated breaking capacity | A | 6000, | |
Rated impulse withstand voltage (1.2/50) Uimp | V | 6000 | |
Dielectric test voltage at ind. Freq. for 1 min | Kv | 2 | |
Pollution degree | 2 | ||
Thermo-magnetic release characteristic | B, C, D | ||
Mechanical features | Electrical life | t | 8000 |
Mechanical life | t | 20000 | |
Protection degree | IP20 | ||
Reference temperature for setting of thermal element | ° C | 30 | |
Ambient temperature (with daily average ≤ 35 ° C) | ° C | -5~+40 (special application please refer to temperature compensation correction) | |
Storage temperature | ° C | -25~+70 |
Technical Data | IEC 898 |
Standards | 1P/2P/3P / 4P |
Poles | C |
Magnetic tripping characteristics | 6 10 16 20 25 32,40,50,63A |
Rated current(A) | 6kA |
Rated short-circuit capacity(Icn): | DC250V DC550V DC750V DC800V DC1000V DC1200V |
Rated voltage | 6kV |
Rated withstand voltage (Uimp): | 1000 |
Rated insulation voltage(Ui): | Yes |
Contact position indication | 3 |
Energy limiting class: | >2000 |
Electrical Life: | >1500 |
Mechanical Life: | Screw terminal |
Connection terminal: | Pillar terminal with clamp |
1~16mm | |
Connection capacity: | Symmetrical DIN rail 35mm |
Installation: | Panel mounting |
OF: Auxiliary contact | |
Accessories: | FB: Auxiliary alarm |
QY: under/over volage protector | |
FL: Shunt release |
Test | Type | Current | Start State | Trip / Not-trip Time Limit | Expected Result | Note |
a | c | 1.05 ln | Cold | t ≥1h | Not-trip | |
b | c | 1.30 ln | Foollows test a | t<1h | Trip | The current will rise to expected value within 5S |
c | c | 7 ln | Cold | t ≥0.1s | Not-trip | |
d | c | 15ln | Cold | t<0.1s | Trip |
Operating Voltage (Ue) | 1P=125V DC or 250V DC, 2P=550V DC or 800V DC 3P=750V DC or 800V DC, 4P=1000 V DC or 1200V DC |
Rated insulation voltage (Ui) | 12V-1200 VDC |
Breaking capacity (Icu) | 10 kA |
Impulse voltage (Uimp) | 6 kA |
Electrical connection | By the bottom for In and Out |
Number of poles | 1P, 2P, 3P, 4P |
Standards | IEC 60947-2 EN 60947-2 SAA CE TUV |
Rated service breaking capacity (Ics) | 100 % of the Icu | |
Endurance (O-C) | Electrical | 1,500 cycles (where L/R=2 ms) |
Mechanical | 20, 000 cycles | |
Mechanical | 20, 000 cycles | |
Degree of pollution | 2 | |
Category | A (no delay in accordance with IEC / EN 60947-2 standards) | |
Degree of protection (IEC 60529) | IP40 | |
Tropicalisation | Relative humidity: 95 % at 55°C in accordance with IEC 60068-2 and GB 14048.2 standards | |
Temperature | Operating | -25°C to 70 °C |
Storage | -40°C to 85°C |
Type | DZ47 C45, C45N |
Number of poles | 1P, 2P, 3P, 4P |
Rated Current(A) | 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63A |
Breaking Capacity(A) | 6000/ 4500 |
Rated Voltage(V) | 230/400V |
Rated Frequency(Hz) | 50/60Hz |
Endurance | ≥4000 |
Circumstance Temp.(°C) | -5°C ~ +40°C |
Electrical Life | ≥6000 |
Mechanical Life | ≥20000 |
Terminal protection | IP20 |
Type | C65-DPN |
Number of poles | 1P |
Rated Current(A) | 1, 2, 3, 4, 6, 10, 16, 20, 25, 32A |
Breaking Capacity(A) | 4500 |
Rated Voltage(V) | 220/ 240V |
Rated Frequency(Hz) | 50/60Hz |
Endurance | ≥4000 |
Tripping characteristics | B 3In ~ 5In; C 5In ~ 10In |
Type | C65 C60 |
Number of poles | 1P, 2P, 3P, 4P |
Rated Current(A) | 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63A |
Breaking Capacity(A) | 6000/ 4500 |
Rated Voltage(V) | 230/400V |
Rated Frequency(Hz) | 50/60Hz |
Endurance | ≥4000 |
Circumstance Temp.(°C) | -5°C ~ +40°C |
Electrical Life | ≥6000 |
Mechanical Life | ≥20000 |
Terminal protection | IP20 |
Type | NC100 |
Number of poles | 1P, 2P, 3P, 4P |
Rated Current(A) | 32, 40, 50, 63, 80, 100, 125A |
Breaking Capacity(A) | 10000 |
Rated Voltage(V) | 230/400V |
Rated Frequency(Hz) | 50/60Hz |
Endurance | ≥4000 |
Circumstance Temp.(°C) | -5°C ~ +40°C |
Electrical Life | ≥6000 |
Mechanical Life | ≥20000 |
Terminal protection | IP20 |
Type | SL7 |
Number of poles | 1P, 2P, 3P, 4P |
Rated Current(A) | 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63A |
Breaking Capacity(Icu) | 6KA/ 10KA |
Breaking capacity of rated operating short circuit(Ics) | 7500A |
Rated Voltage(V) | 230/400V |
Rated Frequency(Hz) | 50/60Hz |
Circumstance Temp.(°C) | -5°C ~ +40°C |
Electrical Life | ≥8000 |
Mechanical Life | ≥20000 |
Type and tripping current scope of instantaneous release | B 3In ~ 5In; C 5In ~ 10In; D 10In ~ 50In |
Terminal protection | IP20 |