China PVC Insulated Nylon Jacketed Thhn or Thwn 6AWG Copper Electric Wire, Find details about China Thhn 6AWG, Thhn 6AWG Wire from PVC Insulated Nylon Jacketed Thhn or Thwn 6AWG Copper Electric Wire
1 Standard:
UL83.
2.Construction:
Conductor: Annealed Copper, solid or stranded sizes 14AWG up to 1000MCM
Insulation: Premium Grade Flame Retardant Polyvinyl Chloride( PVC)
Jacket: Tough Polyamide (Nylon)
3 Applications
General purpose building wire for services, feeders and branch circuits.
Temperature rating not to exceed:
THHN/THWN: 90°C dry and dump, 600V
THHN/THWN: 75 °C wet or in oil, 600V
THWN-2: 90°C Dry, wet or in oil,600V
4. Standard&Test Specification:
THHN/THWN-2 Conforms to following standards:
UL83 for Thermoplastic Insulated Wire and Cables(THHN/THWN-2)
5 Specification of THHN cable:
Conductor | Insulation Thickness mil | Jacket Thickness mils | Nominal O.D. mils | Approx. Weight per 1000' (lbs.) | Allowable Ampacities | |
Size AWG or kcmil | Number of Strands | 90°C | ||||
14 | 7 | 15 | 4 | 109 | 16 | 15 |
12 | 7 | 15 | 4 | 128 | 24 | 20 |
10 | 7 | 20 | 4 | 161 | 38 | 30 |
8 | 7 | 30 | 5 | 213 | 63 | 55 |
6 | 7 | 30 | 5 | 249 | 95 | 75 |
4 | 7 | 40 | 6 | 318 | 152 | 100 |
3 | 7 | 40 | 6 | 346 | 189 | 115 |
2 | 2 | 40 | 6 | 378 | 234 | 130 |
1 | 19 | 50 | 7 | 435 | 299 | 145 |
1/0 | 19 | 50 | 7 | 474 | 372 | 170 |
2/0 | 19 | 50 | 7 | 518 | 462 | 195 |
3/0 | 19 | 50 | 7 | 568 | 575 | 225 |
4/0 | 19 | 50 | 7 | 624 | 718 | 260 |
250 | 37 | 60 | 8 | 694 | 851 | 290 |
300 | 37 | 60 | 8 | 747 | 1012 | 320 |
350 | 37 | 60 | 8 | 797 | 1174 | 350 |
400 | 37 | 60 | 8 | 842 | 1334 | 380 |
500 | 37 | 60 | 8 | 926 | 1655 | 430 |
600 | 61 | 70 | 9 | 1024 | 1987 | 475 |
750 | 61 | 70 | 9 | 1126 | 2464 | 535 |
1000 | 61 | 70 |