Voltage-Limited Type Class II Surge Protection Device

China Voltage-Limited Type Class II Surge Protection Device, Find details about China SPD, Surge Protector from Voltage-Limited Type Class II Surge Protection Device

Model NO.
SP30-275VT/2P/4P-FM
Shape
Cuboid
Material
Low Voltage SPD
Certification
TUV
Brand
OEM
Trademark
Anhuang
Transport Package
Packing in Carton/According to Your Demand
Specification
Class II/class C SPD
Origin
China
HS Code
8536200000
Model NO.
SP30-275VT/2P/4P-FM
Shape
Cuboid
Material
Low Voltage SPD
Certification
TUV
Brand
OEM
Trademark
Anhuang
Transport Package
Packing in Carton/According to Your Demand
Specification
Class II/class C SPD
Origin
China
HS Code
8536200000
Voltage-limited type - CLASS II(MOV)  Surge Protector Device

Voltage-Limited Type Class II Surge Protection Device
                                                                                                           SP30-275VT/2P/4P-F
 
Voltage-Limited Type Class II Surge Protection Device
Type 3 surge protective device especially designed for low-voltage power supply system at the boundaries from lightning protection zone 1-2 and higher.
*Class II/class C SPD, max discharge current 30kA 8/20
*Pluggable design surge arrester for easy replacement
*Comply with IEC61643-11 and UL1449-4th
*The power module surge protector shall be replaced immediately when the deterioration indication window is "red".

 
Part No.SP30-275VT/2P/4P-FM
In accordance withIEC61643-11:2011; UL1449 4th
Category IEC/VDEType 2, Class II
Max. continuous operating voltage (AC) Uc275V
Nominal discharge current(8/20) In15kA
Max. discharge current(8/20) Imax30kA
Voltage protection level/Up @In<1,2kV
Response time25 ns
leakage current ≤20
Backup fuse(only required if not already provided in mains)64A gL/gG
Action time of the deterioration indicator device(320mA) ≤1  
Operating temperature range- 40ºC ~ + 80ºC
Cross-sectional area, solid/ flexible (min.) 2 mm2
Cross-sectional area, solid/ flexible (max.) 5mm2 / 4.5mm2
Torque applied by the screws2.0-2.5 Nm
Installation form35mm DIN-rail in accordance with EN 50022/DIN46277-3
Enclosure materialthermoplastic; extinguishing degree UL94 V-0
Housing protection levelIP20
Installation width2 modules, DIN 43880
Thermal disconnectorInternal  green - normal ; red - failure
Remote alarm contactoptional
Additional data for Remote Alarm Contacts   /
Remote alarm contact type                                                                Isolated Form C
Switching capability Un/In/