Pipe Network FM200 Gas Fire Extinguisher

China Pipe Network FM200 Gas Fire Extinguisher, Find details about China Pipe Network, FM200 Cylinder from Pipe Network FM200 Gas Fire Extinguisher

Model NO.
QMQ4.2/70N-JXJA; QMQ4.2/90N-JXJA; QMQ4.2/100N-JXJA
Effective Range
5m
Retirement Life
8 Years
Dry Powder Type
FM200
Power Source
Gas Fire Extinguisher
Trademark
JianAn
Origin
Jiangxi Jianan
HS Code
84241000
Model NO.
QMQ4.2/70N-JXJA; QMQ4.2/90N-JXJA; QMQ4.2/100N-JXJA
Effective Range
5m
Retirement Life
8 Years
Dry Powder Type
FM200
Power Source
Gas Fire Extinguisher
Trademark
JianAn
Origin
Jiangxi Jianan
HS Code
84241000
Product advantage:
Accurate and reliable actions
 Simple operation and maintenance, beautiful appearance No harm to the human living environment
Mature fire extinguishing technology,no residue after fire extinguishing
The composition remaining life is short in the atmosphere Good storage and stable performance
Installation Notes:
• Installation requirements on equipment line, the equipment use 1.5 m2 multiple copper cores.There are five lines in total.two starting lines are in parallel, two feedback lines are in parallel, also one grounding line.
• The system requirements, when two or more protection areas adopt combined distribution systems. One combined distribution systems shall not protect over 8 area.
• The agent volume of the fire combined distribution systems shall be determined as maximum storage volume.The system agent storage volume shall be the sum of the fire extinguishing design volume and the residential volume in the pipes.
• The nozzle requirements, the protection height and radius shall comply with the following provisions:
The maximum protection height shall not exceed 6.5m;
The minimum protection height shall not be less than 0.3m:
When the installation height is less than 1.5m,the protection radius shall not exceed 4.Sm;
When the installation height is not be less than 1.5m, the protection radius shall not exceed 7.Sm; install the nozzle as the top side.the highest distance to the top shall not be exceed than O.Sm:
The protection area requirements :
The protection area shall be divided as per single enclosure space; when the suspended level and the floor in the same district need to be protected simultaneously, they may be combined into one protection area;
 When the pipe network fire extinguishing system is adopted, the area of the protection area shall
not exceed 800m2 , and the capacity shall not exceed 3600 m3;
The fire endurance of the fencing structure, doors and windows shall not be less than O.Sh; the fire endurance of the suspended ceiling shall not be less than 0.25h. The allowable pressure of the protection area fencing structure shall not be less than 1200 Pa.

Applications:
Electronic computer room, a data processing center, telecommunications facilities, process control, expensive medical equipment, industrial equipment, library, museum and art gallery, clean room,flammable liquid storage area, etc.
The place where the fire is easy to happen, like paint-spraying production line, aging-electrical equipment, rolling machine, printing machine, oil switch, oil immersed transformer, melt impregnating tank, tank, large generators, drying equipment, cement production process of pulverized coal, and the ship's engine room, cargo hold, etc.
 Technical Parameters:
Working Pressure(MPa): 4.2(20ºC)
Max Working Pressure(MPa):5.3(50ºC)
Max filling density of fire extingusiher agent:950KG/M3
Spray time of fire extinguisher agent:<=10s
Working Pressure of expellant bottle group:6MPa
Volume of expellant bottle group:4L
Working volatge of the system: DC24V
Working current of the systesm:1.3A
Ambient temperature:0-50ºC
Starting method: Automatic/Manual mechanical emergency