Power Diesel Generator Set ( 27kVA -62.5kVA)

China Power Diesel Generator Set (27kVA-62.5kVA), Find details about China Diesel Generator Set, Generator Set from Power Diesel Generator Set (27kVA-62.5kVA)

Model NO.
27KVA-62.5KVA
Conditions of Use
Land Use
Usage
Common Units
Landuse Type of Unit
Ordinary
Excitation Mode
AC Rotating Exciter
Capacity
27-62.5kVA
Runnig Speed
1500rpm
Trademark
NDM
Transport Package
Plywood Case
Specification
ISO
Origin
China
HS Code
85021200
Model NO.
27KVA-62.5KVA
Conditions of Use
Land Use
Usage
Common Units
Landuse Type of Unit
Ordinary
Excitation Mode
AC Rotating Exciter
Capacity
27-62.5kVA
Runnig Speed
1500rpm
Trademark
NDM
Transport Package
Plywood Case
Specification
ISO
Origin
China
HS Code
85021200
PARAMETER:
ENGINE: DCEC 4B series diesel generator set, Rated power range is from 24kW to 50KW, 50Hz/60Hz, 1500 rpm/1800rpm
Engine model Rated power (50HZ) Rated power(60HZ)
4B3.9-G1/G2 24kw 27KW
4BT3.9-G1/G2 36 KW 40KW
4BTA3.9-G2 50KW 60KW

Alternator:
1. Variety: Customer can choose under different specification: Differ output power, single Phase or three Phase, two pole or four pole, single surpport or double support, for mainland or marine, and customer also can choose suitable transition connector or coupler.
2. Control system: Auto-voltage regulator have wet- proof, salt-proof, vibration-isolation fuctions.
3. Excition system: Any choosed permanent magnet alternator can solely supply electricity for excition system.
4. Insulation and proof: All alternator have H grade insulation and standard bad wether protection functions.

Highly integrated control system:
Three working model for choose: Stopage, automatic and hand startup model
Main fuction: Genset start, stopage fuction, displaying genset three Phase-voltage, current, engine water temperature, oil pressure, RPM and so on. And the governor is GAC governor.
Protection: When high water temperature, low oil pressure, over-speed, can automatically protect stopage, with the function of breakdown displaying.

Optional:
1. Sound-proof canopy.
2. Canopy with wheels.
3. Container type canopy

Genset model Rated power Engine Alternator:
KC22GFW 22KW 4B3.9G GM-20-4(Marathon) BCI 184F(Stamford)
KC33GFW 33KW 4BT3.9G GM-30-4(Marathon) BCI 184H(Stamford)
KC45GFW 45KW 4BTA3.9-G2 MP-80-4(Marathon) UCI 224E(Stamford)

Power Diesel Generator Set (27kVA-62.5kVA)
Power Diesel Generator Set (27kVA-62.5kVA)
Power Diesel Generator Set (27kVA-62.5kVA)
 
Generation SetModelKC20GFWKC30GFWKC45GFWKC75GFWKC90GFWKC100GFWKC145GFWKC200GFW
 Prime Power Rating Kw2030457590100140200
 Standby Rating Kw22335080100110150200
 Prime Power Rating Current (Amps)365481135162180261360
 MakerNEW DIESEL MACHINERY CO.,LTD
 Dimension (L*W*H)1689*710*11501830*710*11502100*800*14502500*800*15002500*800*15002600*900*15002650*900*16002650*990*1600
 Specific Fuel Consumption @ standby rating (Liter/hr)7.510.314.12530344558
EngineMakerDCEC
 Model4B3.9-G24BT3.9-G24BTA3.9-G26BT5.9-G26BTA5.9-G26BTAA5.9-G26CTA8.3-G26LTAA8.9-G2
 Standby/Prime power (kw)27/2440/3655/50100/90120/110130/120180/163240/220
 CoolingWater-Cooled
 AspirationNaturalTurbocharged and Aftercooled
 AftercoolingNoneNoneJWNoneJWCACJWCAC
 No. of Cylinder44466666
 RPM1500
 Bore (mm)102102102102102102114114
 Stroke (mm)120120120120120120135145
 Displacement (Liter)3.93.93.95.95.95.98.38.9
 Fuel0#
 GovernorGAC electronic
 Starting System24V Electrical
 Lub Oil Specification15W40-CF
 Lub Oil Capacity (Liter)10.910.910.916.416.416.423.827.6
 Coolant Capacity (Liter)8889.99.99.912.311.1
 Exhaust Pipe Size (mm)6767676767678989
AlternatorMaker (Brand)Newage (Stamford)
 Frame SizeBCI184FBCI184JUCI224EUCI274CUCI274DUCI274EUCI274GUCDI274K
 Voltage380-415 V
 RPM/Frequency1500/50hz
 No. of Phase3 phase
 Power Factor0.8 (lag)
 Automatic Voltage RegulatorSX460 (+/- 1.5%)AS440 (+/- 1.5%)
 Class of InsulationH
Control PanelMake   NDM
 Controller Brand/TypeKC800
 Breaker Rating (Amps)5060100A180200225315400A
Fuel TankRecom. capacity for running (hrs)8
BatteryRating (AH)--24V120AH165AH200AH