terminal No. | Content description | Functional definition |
A-01 | DC power output | Connected to the DC power switch, if you do not need, set the A01 and A02 linking |
B-01 | DC power input | Connected to the positive electrode of the battery |
A-02 | DC power input | Connected to the DC power switch, if you do not need, set the A01 and A02 linking |
B-02 | DC power output | Connected to positive input terminal (2) |
A-03 | DC power output | Connected to negative input terminal (1) |
B-03 | DC power input | Connected to the negative electrode of the battery |
A-04 | Enable signal input | Connected start signal output terminal(5) |
B-04 | Enable signal output | Connected to starter motor auxiliary relay |
A-05 | Fuel signal input | Connected to controller fuel signal output terminal (4), The middle of a normally closed contact in series emergency stop switch |
B-05 | Fuel signal output | Connected to the smoke oil solenoid valve |
A-06 | Control terminal | Connected to parking solenoid valve output terminal(6) |
B-06 | Normally closed | Selected according to the parking solenoid valve or heating jacket connection method |
A-07 | Common terminal | Normally closed and open public terminal, connect the power(B+) |
B-07 | Normally open | Selected according to the parking solenoid valve or heating jacket connection method |
A-08 | High water temperature switch signal output | Connected to controller high water temperature switch signal input side(11) |
B-08 | High water temperature switch signal output | Connected to the engine water temperature sensor switch signal the output terminal-WK |
A-09 | Low oil pressure switch signal output | Connected to controller low oil pressure switch signal input terminal (12) |
B-09 | Low oil pressure switch signal output | Connected to the engine oil pressure sensor switch signal output terminal-WK |
A-10 | The hydraulic analog signal output | Connected to controller hydraulic analog signal input terminal (44) |
B-10 | The hydraulic analog signal input | Connected to the engine oil pressure sensor analog signal output terminal-G |
A-11 | Water temperature analog signal output | Connected to the controller input of the analog signal of the water temperature(45) |
B-11 | Water temperature analog signal input | Connected to the engine water temperature sensor analog signal output terminal-G |
A-12 | Spare terminals | Users can customize as per their needs |
B-12 | Spare terminals | Users can customize as per their needs |
A-13 | Normally closed | Users can customize as per their needs |
B-13 | Normally open | Connected to "Socomec" ATS switch 205 |
A-14 | Transform time control | Connected to the controllers ATS conversion time control output terminal8 |
B-14 | Common terminal | Connected to "A-23A" relay normally closed terminal |
A-15 | rotational speed signal output | Connected to controller rotational speed signal input terminal (17) |
B-15 | rotational speed signal input | Connected to the speed sensor signal output terminal |
A-16 | rotational speed signal output | Connected to controller rotational speed signal input terminal (18) |
B-16 | rotational speed signal input | Connected to the speed sensor signal output terminal |
A-17 | The signal output of the charger | Connected to controller charger signal input terminal (9) |
B-17 | The signal input of the charger | Connected to the charger signal output terminal on the engine-WL |
A(B)-18 | Mains phase line L1output | Connected to the charger input terminal- L |
A-19 | Generation of current public output | Connected to controller common input terminal of the power generation current (42) |
B-19 | Generation of current public input | Connected to current transformer output of public |
A-20 | Power current 3 output | Connected to controller generation current input terminal (41) |
B-20 | Power current 3 input | Connected to the current transformer 3 output terminal |
A-21 | Power current 2 output | Connected to controller electricity generation current 2 input terminal(40) |
B-21 | Power current 2 input | Connected to the current transformer 2 output terminal |
A-22 | Power current 1 output | Connected to controller electricity generation current 1 input terminal(39) |
B-22 | Power current 1 input | Connected to the current transformer 1 output terminal |
A-23 | Normally closed | Connected to"B-14B"relay common terminal |
B-23 | Normally open | Connected to"Socomec"ATSswitch-203 |
A-24 | ATS-common terminal | Connected to"Socomec" ATS switch -201or202 |
B-24 | Mains zero line | Connected to mains zero line-N |
A-25 | Automatic start / stop | Connected to controller automatically start / stop input terminal(10) |
B-25 | Normally open | Can connect with pilot lamp |
A-26 | mains voltage L1 input | Connected to mains-L1 |
B-26 | Mains zero line | Connected to mains zero line-N |
A-27 | Power voltage zero line output | Connected to the controller electricity generation voltage zero line input side(38) |
B-27 | Power voltage zero line input | Connected to generator zero line output terminal |
A-28 | Generating voltage L3 output | Connected to the controller power voltage L3 Input terminal(37) |
B-28 | Generating voltage L3 input | Connected to the generator voltage L3 output terminal |
A-29 | Generating voltage L2 output | Connected to the controller power voltage L2 Input terminal(36) |
B-29 | Generating voltage L2 input | Connected to the generator voltage L2 output terminal |
A-30 | Generating voltage L1 output | Connected to the controller power voltage L1 Input terminal(35) |
B-30 | Generating voltage L1 input | Connected to the generator voltage L1 output terminal |